Professional Documents
Culture Documents
D.E.R. system
Sicherheitstechnik GmbH
D.E.R. system
We take new paths
INOTEC Sicherheitstechnik GmbH is a mediumsized company that develops innovative and customer-oriented solutions in the area of emergency and safety lighting. A dynamic team of flexible and competent employees ensures reliable support in all matters relating to products, planning and regulations. Modern, high-tech products set new standards around the world, such as emergency lighting systems with JOKER technology and the Dynamic Escape Routing system D.E.R. This catalogue contains the INOTEC Dynamic Escape Routing system D.E.R. and complementary products. Should you require additional functions or components, please do not hesitate to contact our regional technical sales staff directly.
Contents Page System description Copyright: INOTEC Sicherheitstechnik GmbH, Ense Reprinting and reproduction, even in excerpts, is permitted only with approval of the manufacturer. Subject to technical changes. The systems presented in the catalogue are not compatible with monitoring systems of the type INOTEC SVPC, SV central stations or multifunction controllers. Radio shielding acc. to DIN EN 55015 Application example Circuit schematic Luminaires overview System components and options Central monitoring 3-5 6-7 8-9 10 - 21 22 - 25 26 - 27
D.E.R. system
Follow us
Are escape routes always escape routes? Emergency exit luminaires with fixed directional signs are used to mark escape routes and fulfil the task of enabling people to reach safe locations in the event of a power failure or a necessary evacuation. But what happens if fire and smoke are blocking the nearest escape route? What to do when heavy smoke emissions mean it is no longer possible to work out where you are? How do you find the escape route when the escape route sign is no longer visible?
Do you have anything against a higher level of safety? INOTEC Sicherheitstechnik GmbH has taken on the problem of smoky escape routes with the aim of complementing fixed, unchangeable escape route signage with dynamic escape route guidance. A dynamic system has to fulfil two key tasks: on one hand, it must prevent anyone from escaping into an area that is already filled with smoke, and on the other, it must ensure that the people already in smoky areas can still find their way to the escape route. The solution is the Dynamic Escape Routing system (D.E.R.). Emergency exit luminaires with integrated LED matrix not only ensure static designation of escape routes, they can also be used for indicating an alternative escape route direction. Smoke-filled areas or escape routes can be visually blocked off in this way with a red, X-shaped pattern of LEDs. Because why should an escape route remain signposted when it is smoky and no longer usable? Luminaires for floor installation or wall installation near the floor are used for orientation in smoke-filled areas. In event of a fire, the running light function of these lights points the direction of the path to the emergency door and safety. The flashing function of the D.E.R. system can be useful for a building evacuation even when there is no fire.
D.E.R. system
We take new paths
Functionality of the D.E.R. system The D.E.R. system communicates with the building's existing fire detection system. Potential-free contacts, activated by the fire alarm system, send a signal to the D.E.R. interface. The D.E.R. controller evaluates the defined information of the fire alarm system and activates the escape route direction patterns stored in the controller. This automatically activates the D.E.R. luminaires, which indicate the safe escape route with running lights, for example. The green LED arrows are used to indicate the direction. At the same time, the emergency doors that should no longer be used are visually blocked with red flashing LED X's. Flashing lights mounted close to the floor near emergency doors additionally indicate the escape routes so that these remain identifiable even in the presence of smoke. Should the fire or smoke spread farther, the D.E.R. system can respond by activating other escape route plans and rearranging the luminaires accordingly. Even very small systems, starting with individual luminaires, can be implemented with limited functions by activating the luminaires directly via potential-free contacts of the fire alarm system. The high flexibility of the D.E.R. system results not only from its dynamic nature but also the option of connection to INOTEC emergency light systems as well as to any secured mains (AC/DC) with an appropriate voltage level.
Regulations As a result of use of the innovative D.E.R. system in airports, hospitals, theatres, train stations etc., there has also been a response in terms of regulations. In January 2001, the German Federation of Institutions for Statutory Accident Insurance and Prevention (HVBG) published the regulation BGR 216 "Visual Safety Guidance Systems (Including Safety Guidance Lighting)", which requires the use of nearto-floor safety guidance systems for buildings with increased risk under certain conditions. For example, this includes buildings with more than three storeys, building complexes with multiple interconnecting individual buildings, buildings with a large share of outside
D.E.R. system
Follow us
personnel and buildings with a large share of people with reduced mobility (bed-ridden or physically disabled persons). EN 50172 lists safety guidance systems that can increase the effectiveness when used along escape routes in addition to typical safety lighting luminaires. In the Technical Rule for Workplaces "Safety Lighting, Visual Safety Guidance Systems" ASR A3.4/3 from May 2009, the Committee for Workplaces (ASTA) describes in detail the use of visual safety guidance systems for workplaces with reference to ASR A2.3, which in turn regulates the cases in which a visual safety guidance system for escape routes is required. Apart from the current regulatory situation, additional applications have arisen in practice for dynamic escape route guidance systems. For example, such a system can be used to compensate for some structural fire protection measures. Fire Safety Award The D.E.R. system was honoured by fire safety experts as a key development for increasing the safety of people by being awarded the Germany Fire Safety Award 2004.
D.E.R. system
Application example
The various D.E.R. components make it possible to realise flexible, dynamic escape route guidance that is adapted to the specific building. In event of smoke or fire, the people present will be guided safely out of the danger zone via the escape routes that are still open.
D.E.R. system
D.E.R. in practical use D.E.R. luminaires can be useful for everyday orientation. The LED luminaires of series FS1000 are used for route designation or as accent lights in parking buildings or rooms intentionally kept dark, such as cinemas/theatres.
D.E.R. system
Circuit schematic
24 V signal via pot.-free contacts of the fire alarm control panel
LSA 8
G/
+24V
RS232
reset
RTG
INOTEC
Fluchtweg. Bel. Fluchtweg. Bel. Betrieb Betrieb Dienstag Muster Montag Muster 27.0311:30 Menue 27.03. 12:00 Menue
2 2
InoLan TxD
VISU
Drucker Centronics
Key-Board
T R
T R
T R
T R
T R
T R
T R
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
1
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
2
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
3
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
4
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
3
INOTEC
Betrieb Batt.-Betrieb Strung LadeStrung
Drucker Centronics
Reset
CPS 220 / 64
Key-Boa rd
Netz
Batterie
16AT Ein
10AT
Ladeteil 220V/7,5A
LSA 8
24 V plug-in unit for CPS 220/64 SV
2,5A
5 AT 50
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
CP 4x2A
1
F
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
G/
+24V
RS232
3,15 A
2
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
When using the 24 V plug-in unit, CPUSB or CLS, remote monitoring is only possible via InoWeb-Control software in connection with an InoWeb module!
3
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
reset
RTG
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
F
3,15 A
3,15 A
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
= BL / NM = DL / M
InoWeb TxD
2
F
CPS 220 / 64
Netz
Batterie
InoWeb module
16AT Ein
10AT
Ladeteil 220V/7,5A
CPUSB 24V
G/
+24V
RS232 reset
InoWeb TxD
RTG
D.E.R. system
Circuit schematic
Fire section
FL series
5
2 3 2
INOTEC
Sicherheitstechnik GmbH Am Buschgarten 17 D-59469 Ense D.E.R Power Supply PSU 48
FB series
SEV
UE UE IE UA IA : 230 V ~ 50/60 Hz : 183,5 - 260 V : 0,38 A : 48 V : 1A : -5...+45C
FS series
3
ON P/N : 965300
INOTEC
INPUT
N L
OUTPUT
+ -
2 3
INOTEC
UE UE IE UA IA
Sicherheitstechnik GmbH Am Buschgarten 17 D-59469 Ense : 230 V ~ 50/60 Hz : 183,5 - 260 V : 0,38 A : 48 V : 1A : -5...+45C
SEV
FS series
3
ON P/N : 965300
INOTEC
INPUT
N L
OUTPUT
+ -
2
0 1 0 1
2 3 2 3
5
0 1 0 1 0 1 0 1
9
7 8
2 3 2 3 2 3 2 3
4 5 6
4 5 6
4 5 6
S2000 module
S2000 module
S2000 module
Fire section
Fire section
Fire section
7 8
7 8
7 8
7 8
4 5 6
4 5 6
4 5 6
7 8
D.E.R. system
We develop for you
Extremely durable stainless steel luminaire Green LED arrows for direction indication Running light function Control and automatic function monitoring via segment controller SEV or SEV/A Technical data FS 1000 BE Art. No. 800 002 Art. No. 800 004
40
Flush oor installation Cable inlet from side Cable inlet from below
113
Housing material: Light source: Input voltage: IBat Emerg. : Connection terminals: Perm. temperature range: Protection category: Protection class:
Stainless steel LEDs 48 V DC 36 mA Suitable for wires 2x2x0.8 and pass-through wiring - 15...+ 40C IP 54 III (safety extra-low voltage 48 V DC)
83
5 19
Flush carpet installation Cable inlet from side Cable inlet from below
120
83
5 19
Stainless steel luminaires for wall installation in cavity wall box Green LED arrows for direction indication Running light function Control and automatic function monitoring via segment controller SEV or SEV/A Technical data
50
Housing material: Light source: Input voltage: IBat Emerg. : Connection terminals: Perm. temperature range: Protection category: Protection class:
Stainless steel LEDs 48 V DC 36 mA Suitable for wires 2x2x0.8 and pass-through wiring - 15...+ 40C IP 20 III (safety extra-low voltage 48 V DC)
90 58
74
6,5
10
D.E.R. system
Plan with us
Tunnel or corridor luminaire Easily visible even from an extreme angle Green LED arrows for direction indication Running light function Control and automatic function monitoring via segment controller SEV or SEV/A FS 7000 Art. No. 800 170
300
Technical data Housing material: Light source: Input voltage: IBat Emerg. : Connection terminals: Perm. temperature range: Protection category: Protection class:
Stainless steel LEDs 48 V DC 63 mA 2.5 mm for pass-through wiring - 15...+ 40C IP 54 III (safety extra-low voltage 48 V DC)
56
Stainless steel luminaire Green LED arrow matrix for direction indication Running light function Control and automatic function monitoring via segment controller SEV or SEV/A Technical data
110
309
50
Housing material: Light source: Input voltage: IBat Emerg. : Connection terminals: Perm. temperature range: Protection category: Protection class:
Stainless steel LEDs 48 V DC 200 mA 2.5 mm for pass-through wiring - 15...+ 40C IP 54 III (safety extra-low voltage 48 V DC)
185
11
D.E.R. system
We develop for you
Tunnel luminaire Green LED arrow matrix for direction indication Integrated safety luminaire 10W LLp (optional LEDs) Control and automatic function monitoring via D.E.R. controller Electronics with output for a flashing luminaire of the FB series FL 3001 WE Art. No. 800 155 L10
450 150
450
245
Technical data Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class:
Colours Silver-grey Special colours Append the colour code to art. no.: e.g. Stainless steel V4A powder-coated LEDs, 10W LLp (optional LEDs) 230V 10% AC / 220V 20% DC 94 mA 31.4 VA 2.5 mm for pass-through wiring - 15...+ 40C
200
IP 65 I
Art. No. Colour code ... ... L10 L99
Channel luminaire Modular design Freely selectable content: - LED arrow matrix for direction indication - Escape symbol backlit with LEDs - Green Xenon flashing lamp Control and automatic function monitoring via D.E.R. controller Adjustable length, e.g. to door width Electronics with output for a flashing luminaire of the FB series
280
171
je nach Ausfhrung
75
Technical data Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class: Viewing distance:
Colours Special colours Append the colour code to art. no.: e.g. Aluminium LEDs 230V 10% AC / 220V 20% DC 75 mA (minimum value depending on design) 24.6 VA (minimum value depending on design) 2.5 mm for pass-through wiring - 15...+ 40C IP20 I 20 m Art. No. Colour code ... L99
Please use the corresponding table at www. inotec-licht.de for specifying the luminaire content.
12
D.E.R. system
Plan with us
LED arrow matrix for direction indication Control and automatic function monitoring via D.E.R. controller Electronics with output for a flashing luminaire of the FB series Technical data FL 6000 IP54 Art. No. 800 050 L10 Wall surface installation
313
62,5
Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class:
Colours Silver-grey Special colours Append the colour code to art. no.: e.g.
Sheet steel powder-coated LEDs 230V +/- 10% AC; 220V +/- 20% DC 49 mA 19.3 VA 2.5 mm for pass-through wiring - 15...+ 40C IP 54 I Art. No. Colour code ... ... L10 L99
LED arrow matrix for direction indication Escape symbol backlit with LEDs Control and automatic function monitoring via D.E.R. controller Electronics with output for a flashing luminaire of the FB series Technical data
195
549
62,5
Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class: Viewing distance:
Colours Silver-grey Special colours Append the colour code to art. no.: e.g.
Sheet steel powder-coated LEDs 230V +/- 10% AC; 220V +/- 20% DC 75 mA 24.6 VA 2.5 mm for pass-through wiring - 15...+ 40C IP 54 I 20 m Art. No. Colour code ... ... L10 L99
195
13
D.E.R. system
We develop for you
Single-sided luminaire with LED arrow matrix for direction indication Escape symbol backlit with LEDs Control and automatic function monitoring via D.E.R. controller Electronics with output for a flashing luminaire of the FB series FL 6100 Art. No. 800 084 L10
284 54
Wall installation
Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class: Viewing distance:
Colours Silver-grey Special colours Append the colour code to art. no.: e.g.
Sheet steel powder-coated LEDs 230V 10% AC / 220V 20% DC 75 mA 24.6 VA 2.5 mm for pass-through wiring - 15...+ 40C
284
Technical data
Ceiling installation
Suspended installation
ca. 825
Wall installation
14
313
D.E.R. system
Plan with us
Double-sided luminaire with LED arrow matrix for direction indication Escape symbol backlit with LEDs Control and automatic function monitoring via D.E.R. controller Electronics with output for a flashing luminaire of the FB series FL 6200 D Art. No. 800 087 L10
284 100
Ceiling installation
Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class: Viewing distance:
Colours Silver-grey Special colours Append the colour code to art. no.: e.g.
Sheet steel powder-coated LEDs 230V 10% AC / 220V 20% DC 123 mA 45 VA 2.5 mm for pass-through wiring - 15...+ 40C
322
Technical data
Suspended installation
800 014 LXX FL 6200 D IP54 Art. No. 800 096 L10
284 123
Ceiling installation
308
Chain installation
306
15
D.E.R. system
We develop for you
Single-sided aluminium profile luminaire with LED arrow matrix for direction indication Escape symbol backlit with LEDs Control and automatic function monitoring via D.E.R. controller Electronics with output for a flashing luminaire of the FB series FL 7186 Art. No. 800 240 Wall installation
Technical data Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class: Viewing distance:
Aluminium LEDs 230V 10% AC / 220V 20% DC 75 mA 24.6 VA 2.5 mm for pass-through wiring - 15...+ 40C
142,4
502,4
80
Ceiling installation
IP 20 I 20 m
180
402
502
80
Suspended installation
142
500
502
80
16
D.E.R. system
Plan with us
Double-sided aluminium profile luminaire with LED arrow matrix for direction indication Escape symbol backlit with LEDs Control and automatic function monitoring via D.E.R. controller Electronics with output a flashing luminaire of the FB series Technical data FL 7286 D Art. No. 800 259 Ceiling installation
402
180
502
80
Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class: Viewing distance:
Aluminium LEDs 230V 10% AC / 220V 20% DC 75 mA 24.6 VA 2.5 mm for pass-through wiring - 15...+ 40C
Suspended installation
IP 20 I 20 m
142
500
502
80
17
D.E.R. system
We develop for you
Single-sided luminaire in modular design (1 module) Freely selectable content Symbols or templates backlit with LEDs Control and automatic function monitoring via D.E.R. controller or central battery system CPS 220/64 SV with 24 V plug-in unit or 24 V substation (24 V version) Monitoring also possible with emergency lighting system CLS 24 SV (24 V version). Three additional control inputs for external control commands Energy supply generally possible via 24 V or 48 V outside network. FL 5101 Art. No. 800 010V L04 Wall installation 24 V
160 130
53
Can be equipped with: - Escape symbol as pictogram (LEDs white) - Directional arrow as pictogram (LEDs white) - Directional arrow as template (LEDs white or green) - Blocked symbol as template (LEDs red) Technical data
160
55 6
IBat Emerg.
(24 V version): Connection terminals: Perm. temperature range: Protection category: Protection class: Viewing distance:
Sheet steel powder-coated LEDs 24V +/- 20% (24 V version) 63 mA (white+green LEDs) or 126 mA (red LEDs) 2.5 mm for pass-through wiring - 15...+ 40C IP 40 III (24 V version) 20 m
Colours White textured Slate grey Special colours Append the colour code to art. no: e.g.
Art. No. Colour code ... ... ... L04 L16 L99
Please use the corresponding table at www. inotec-licht.de for specifying the luminaire content.
18
155
D.E.R. system
Plan with us
Single-sided luminaire in modular design (3 modules) Freely selectable content Symbols or templates backlit with LEDs Control and automatic function monitoring via D.E.R. controller or central battery system CPS 220/64 SV with 24 V plug-in unit or 24 V substation (only 24 V version) Monitoring also possible with emergency lighting system CLS 24 SV (24 V version) and central battery system CPS 220/48/64 (230 V version) Three additional control inputs for external control commands Energy supply generally possible via 24 V, 48 V or 230 V outside network. FL 5103 Art. No. 800 012V L16 Art. No. 800 018V L16 Wall installation 24 V 230 V
400 130
53
Can be equipped with: - Escape symbol as pictogram (LEDs white) - Directional arrow as pictogram (LEDs white) - Directional arrow as template (LEDs white or green) - Blocked symbol as template (LEDs red) Technical data
FL 5103 WE Art. No. 800 013V L04 Art. No. 800 019V L04
400
55 6
Sheet steel powder-coated LEDs 24V +/- 20% (24 V version) 230V +/- 10% AC; 220V +/- 20% DC (230 V version) Per module 63 mA (white+green LEDs) or 126 mA (red LEDs) Per module 9 mA (white+green LEDs) or 18 mA (red LEDs) Per module 2 VA (white+green LEDs) or 4 VA (red LEDs) 2.5 mm for pass-through wiring - 15...+ 40C IP 40 III (24 V version) or I (230 V version) 20 m Art. No. Colour code ... ... ... L04 L16 L99
155
Please use the corresponding table at www. inotec-licht.de for specifying luminaire content.
19
D.E.R. system
We develop for you
Single-sided luminaire in modular design (5 modules) Freely selectable content Symbols or templates backlit with LED Control and automatic function monitoring via D.E.R. controller or central battery system CPS 220/64 SV with 24 V plug-in unit or 24 V substation (24 V version) Monitoring also possible with emergency lighting system CLS 24 SV (only 24 V version) and central battery system CPS 220/48/64 (230 V version) Three additional control inputs for external control commands Energy supply generally possible via 24 V, 48 V or 230 V outside network. FL 5105 Art. No. 800 014V L04 Art. No. 800 022V L04 Wall installation 24 V 230 V
640 130
53
Can be equipped with: - Escape symbol as pictogram (LEDs white) - Directional arrow as pictogram (LEDs white) - Directional arrow as template (LEDs white or green) - Blocked symbol as template (LEDs red) Technical data
FL 5105 WE Art. No. 800 015V L16 Art. No. 800 023V L16
640 155
55 6
Sheet steel powder-coated LEDs 24V +/- 20% (24 V version) 230V +/- 10% AC; 220V +/- 20% DC (230 V version) Per module 63 mA (white+green LEDs) or 126 mA (red LEDs) Per module 9 mA (white+green LEDs) or 18 mA (red LEDs) Per module 2 VA (white+green LEDs) or 4 VA (red LEDs) 2.5 mm for pass-through wiring - 15...+ 40C IP 40 III (24 V version) or I (230 V version) 20 m Art. No. Colour code ... ... ... L04 L16 L99
Please use the corresponding table at www. inotec-licht.de for specifying luminaire content.
20
D.E.R. system
Plan with us
Plastic flashing luminaire (polystyrene) Xenon flashing lamp Control via luminaires of the FL series or via S2024 module (S2024 module only in combination with D.E.R. controller) FB 5000 24V Art. No. 800 021 Wall / ceiling installation
45
Technical data Housing material: Light source: Input voltage: IBat Emerg. : Connection terminals: Perm. temperature range: Protection category: Protection class:
Green plastic cover (polycarbonate) Xenon flashing lamp 24 V DC 117 mA Up to 1.5 mm - 15...+ 40C
IP 67 II
75 45
Supply modules for connection to - D.E.R. luminaires of the FL series (ET 9/24) - Central battery system CPS 220 (J-ET 9/24) - D.E.R. controller and secured network 230 V (S 2024) in module housing incl. connection terminal adapter Flashing luminaire for wall installation in cavity wall box Green plastic disc Control via luminaires of the FL series or via S2000 module (S2000 module only in combination with D.E.R. controller)
77
50
Technical data Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class:
Stainless steel Xenon flashing lamp 230V 10% AC / 220V 20% DC 20 mA 7.3 VA Up to 1.5 mm - 15...+ 40C IP 20 I
90 58
74
6,5
Xenon flashing luminaire Green plastic disc Control via luminaires of the FL series or via S2000 module (S2000 module only in combination with D.E.R. controller)
Wall installation
Technical data Housing material: Light source: Input voltage: IBat Emerg. : SMains: Connection terminals: Perm. temperature range: Protection category: Protection class: Colours
White textured Special colours Append the colour code to art. no: e.g.
Sheet steel powder-coated Xenon flashing lamp 230V 10% AC / 220V 20% DC 20 mA 7.3 VA Up to 1.5 mm - 15...+ 40C
50
90
21
D.E.R. system
We develop for you
Regulated power supply With mains and overload display via LED (only PSU 24 and 48-1) Output electrically isolated acc. to EN 60950 (safety low voltage) Suitable for flush mounting on DIN profile rails Various designs with various output current levels For supplying the segment controller SEV with luminaires of the FS series (48 V) and the interface LSA8 (24 V) PSU 24 Art. No. 965 301 Supply device
45
60
70
90
60
Housing material: Input voltage: Output voltage: Output current: Overload capability: Perm. temperature range: Protection category: Protection class:
Thermoplastic 230 V +/- 15% AC, 184- 260V DC 24 V (PSU 24) or 48 V (PSU 48-1) 1.5 A (PSU 24) and 1 A (PSU 48-1) Sustained short-circuit-proof -20 C ... +55 C IP20 (terminal) I
Supply device
45
70
90
Supply device
Housing material: Input voltage: Output voltage: Output current: Overload capability: Perm. temperature range: Protection category: Protection class:
Aluminium 230 V AC 120- 370 V DC 48 V DC 1.6 A (PSU 48-1.6) and 5 A (PSU 48-5) Sustained short-circuit-proof -10 C ... +60 C IP20 (terminal) I
125,2
100
55,5
Supply device
125,2
100
125,5
22
D.E.R. system
Plan with us
Segment controller for programming, control, management and testing of up to 96 FS luminaires. Connection to D.E.R. controller via 2-wire bus line. Two-line display, buttons for programming and testing, red LED for fault indication. 48 V input voltage via regulated power supply of type PSU 48. SEV
Art. No. 990 053
Technical data
70 90
Housing material: Input voltage: Output voltage: Address range: Wire connection: Perm. temperature range: Power consumption: Protection category: Dimensions:
Plastic DIN rail housing 48 V 48 V SEV 01-99 Luminaires 01-96 Double-use terminal 1.5 mm - 15 ...+ 50 C
Independent segment controller for programming, control, management and testing of up to 96 FS luminaires. Two-line display, buttons for programming and testing, red LED for fault indication. Wide voltage input (24 to 48 V DC) for pattern creation. Two patterns can be programmed. Automatic function test. Potential-free fault signalling contacts (NO-contacts). 48 V input voltage via regulated power supply of type PSU 48.
58
58
70
90
Technical data Housing material: Input voltage: Output voltage: Address range: Wire connection: Perm. temperature range: Power consumption: Protection category: Dimensions:
Plastic DIN rail housing 48 V 48 V SEV 01-99 Luminaires 01-96 Double-use terminal 1.5 mm - 15 ...+ 50 C
23
D.E.R. system
We develop for you
24 V circuit plug-in unit or substation CPUSB with 2 circuits for central battery system CPS 220/64 in combination with TFT convenient control unit for supply, control and monitoring of 24 V D.E.R. luminaires (FL 5000 series). Mixed operation within one circuit with 24 V INOTEC LED system luminaires. - 2-pole protection per circuit - Individual luminaire control and monitoring - Max. 20 luminaires per circuit - Control and monitoring without data line - Luminaires can be individually programmed and addressed - 2 output circuits in protection class III (SELV) at 2.5 A - 2 switching inputs can be freely assigned to each luminaire CPUSB 220/64/1-2.5/24V Art. No. 922 261 CP 24 V 2 x 2.5 A
Art. No. 979 009
Interface for connection to D.E.R. controller (max. 3 units per controller). Escape route patterns programmed in the D.E.R. controller can be activated via 8 switching inputs of the module. The input voltage of the LSA 8.1 channels may be from 15 to 30 V DC. The input voltage is connected to the inputs via potential-free contacts, such as from a fire alarm system.
Supply device
58
70
90
Function-monitored control module for connection to an FW99 card (BUS) and a secured power supply (e.g. CPS 220). Consumers of up to 120 W can be switched via the module.
S 2000
Art. No. 851 012
Technical data Housing material: Input voltage: Output voltage: Perm. temperature range: Protection class: Wire connection:
Polycarbonate UL V0 230V 50/60 Hz, 220V +/- 20% DC 230V 50/60 Hz, 220V +/- 20% DC - 15 ...+ 50 C I 2.5 mm single core or 1.5 mm braided with cable end sleeve
40
30
90
S 2024 Monitoring, supply and control module for 1 to 6 power LEDs for connection to the FW99 card of a D.E.R. controller (BUS) and a secured power supply (e.g. CPS 220). Flashing function, switching on and off of the connected LEDs 2-pole socket board for connection of the LEDs Also suitable for supplying and activating the flashing luminaire FB 5000 24V.
Art. No. 850 037
Technical data Housing material: Input voltage: Output voltage: Perm. temperature range: Protection class: Wire connection:
Polycarbonate UL V0 230V 50/60 Hz, 220V +/- 20% DC 24 V DC - 15 ...+ 50 C I 2.5 mm single core or 1.5 mm braided with cable end sleeve
40
30
90
24
D.E.R. system
Plan with us
Fully automatic microprocessor-controlled testing device for monitoring of max. 1584 addresses in connection with INOTEC luminaires of the FL series, S2000 or S2024 modules and segment controllers SEV. Suitable for inclusion of max. 6 plug-in cards (FW99 and Visu). Serial data bus via 2-wire, unshielded data line, e.g. YR 2 x 0.8 mm. Freely programmable, automatic function test of all connected luminaires, modules and segment controllers. Error messages: - Lamp defective - Transmission error - Device error The following standard functions are included: - All test results of the last two years are automatically saved and can be loaded at any time (up to 2000 events) - Printer interface for maintaining the required log book according to standards - Potential-free collective fault contact Options: The controller can also be expanded with expansion modules (max. 6 plug-in units each) (max. 16 plug-in units per controller). D.E.R. controller Art. No. 869 011
85
240
355
240
D.E.R. controller
85
Technical data Housing material: Mains voltage: Protection category: Protection class: Polycarbonate 230 V AC 10 %, 50/60 Hz 220 V DC 20 % II IP30 EMC protection in acc. with EN 55015
240 255
240
FW 99 module
Art. No. 851 011
Accessories FW 99 module Plug-in unit for D.E.R. controller for control, management and testing of max. 99 bus devices such as luminaires of the FL series, segment controllers SEV and S 2000 or S 2024 modules.
ViSU module Plug-in unit for D.E.R. controller as interface for data transmission to a PC via SVPCn software in connection with an InoLan module for visualisation of a D.E.R. system. InoLan module Converter between Ethernet and serial INOTEC-RTG data bus or RS 232.
InoLan
Art. No. 990 063
25
D.E.R. system
SVPCn Software
Logbook Panel : C02 ================================================= 0858 06.06.11 I 12:13 I Segment failure 3: Card is installed -------Failure --> Card 3 : Sum-failure -------Failure --> Card 3 : Data communication failure -----------------------------------------------------------------------------------------------0857 06.06.11 I 12:13 I Segment failure 2: Card is installed -------Failure --> Card 2 : Sum-failure -------Failure --> Card 2 : Data communication failure -----------------------------------------------------------------------------------------------0856 06.06.11 I 12:13 I Segment failure
Functionality:
Monitoring of up to 32 D.E.R. or NEA controllers Individual signalling of up to 47,520 addresses for D.E.R. systems Automatic function test Zoomable floor plan display (DXF files) Test log can be accessed and printed from the control components Each individual luminaire can be programmed via the interface Transmission via the existing Ethernet Programming can be secured against unauthorised access with a password
System requirements: Operating system: Win98/2000/XP/Vista/ 7 Business/Vista Enterprise Monitor: VGA (640x480), 256 colours or more Interface: INOLAN module via RJ45 port
26
D.E.R. system
InoLan
Betrieb Betrieb Strung Test Betrieb Strung Test Betrieb Strung Test Betrieb Strung Test Betrieb Strung Test
INOTEC
NE-SV-berwachung Betrieb
8:30
Strung Test
Menue ->
Drucker Cetronics
Key-board
T R
T R
T R
T R
T R
T R
Ethernet
DER
InoLan
Betrieb Betrieb Strung Test Betrieb Strung Test Betrieb Strung Test Betrieb Strung Test Betrieb Strung Test
INOTEC
NE-SV-berwachung Betrieb
8:30
Strung Test
Menue ->
Drucker Cetronics
Key-board
T R
T R
T R
T R
T R
T R
NEA
Red = failure
By using DXF les for representing the oor plan, the plan can be zoomed in and out. The luminaire status is highlighted in colour.
27
INOTEC Sicherheitstechnik GmbH Am Buschgarten 17 D - 59 469 Ense Tel Fax +49 29 38/97 30-0 +49 29 38/97 30-29 info@inotec-licht.de www.inotec-licht.de
28
Sicherheitstechnik GmbH
707 021
05/2011