Professional Documents
Culture Documents
Version 5 15-December-2005
This document contains Honeywell proprietary information. Information contained herein is to be used solely for the purpose submitted, and no part of this document or its contents shall be reproduced, published, or disclosed to a third party without the express permission of Honeywell International. HONEYWELL DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PURPOSE AND MAKES NO EXPRESS WARRANTIES EXCEPT AS MAY BE STATED IN ITS WRITTEN AGREEMENT WITH AND FOR ITS CUSTOMER. In no event is Honeywell liable to anyone for any direct, special, or consequential damages. The information and specification in this document are subject to change without notice.
Version 5
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Update History
Page 1 of 8
Version 5
System Type
Excel 5000 System (BNA) Excel 5000 System (LON) LonWorks System (LON) XLWeb System Legacy HVAC Controller System Honeywell Asset Locator System Life Safety System (FS90 or XLS1000) Life Safety System (FPS) Access Control System (PCSC, WSE) Temaline System Comments
Controllers
Excel 50/500 XC5010C v2.06.05 Excel 50/500 XC5010C LonMark v2.06.05 Honeywell Devices VAVII plug-in 4.2.4 XLWeb XL1000A500 Linux Flash Image 100-00, Excel Web Firmware 1-00-00 R7044 R7044 A/B, R7044 D/E/G, Microcells,R7044A/B 15.0, R7044D/E/G 10.4 FS90 CA v3.2 WSE Star II V2.74 only Temaline Please consult Temaline Release Bulletin 4.6.1 and Temaline Compatibility Tables.
XCL5010 v2.06.05
XL1000A1000 Excel Classic Linux Flash Image 1R7510A1005, 00-00, Excel Web R7510B1003,S1014, Firmware 1-00-00 S4003 Excel EMC W7161 A/B/C/D,3.5S or later
LJ v2.1
XL100C v2.06.05
UV plug-in V1.2.3
AE v2
XL50 v2.06.06
XL50 v2.06.06
Excel 12 plug-in 2.3.4.2 CHC plug-in V1.13 Thermostat plug-in V1.1.3 Wireless Receiver plug-in 1.1.3 XL12 plug-in 2.3.0.3
Connections
LON BNA I BNA 1C, BNA 2CS v3.0.0 H Excel 5000 Direct R310.1** Excel 5000 Direct R310.1** LPS R310.1** BACnet Direct R310.1** i.LON600 Router 1.05.01 i.LON600 Router 1.05.01 BNA 2CS or BNA 2DN v3.0.0.H BNPS R3.2 HAL-EIRIS R3.1 FPS R3.0 Temaline R4.6.1 i.LON600 Router 1.05.01 BNA 1C - C-bus only. BNA 2CS - C-bus or S-bus only. BNA 2DN - L1/L2 only ** Included on EBI R310.1 CD1
Point Servers
Software Services
BACstac Cimetrics BACstac 4.0E LNS 3.2 (Turbo) SP1 LNS 3.2 (Turbo) SP1 Update 1a Update 1a LNS 3.08 Included on the EBI CD1
LNS Server
Tools
XLToolkit CARE RSS PCSC Configuration Software Version 7.03 7.01.02, 5.01.02 Version 7.03 7.01.02, 5.01.02 2.08.09 Version 7.03 7.01.02, 5.01.02 2.08.09 Version 7.03 7.01.02 Version 7.03
LincNet versions below this release are not supported to run on the EBI server.
SEPARATE POINT SEPARATE POINT SERVER REQUIRED SERVER REQUIRED SUPPORTED SUPPORTED SUPPORTED SUPPORTED SUPPORTED SUPPORTED
SUPPORTED SUPPORTED
SUPPORTED SUPPORTED
SUPPORTED SUPPORTED
SUPPORTED SUPPORTED
NOT COMPATIBLE
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Systems Checklist
Page 2 of 8
Version 5 15-December-2005
EBI Server PC (Typical Spec with Windows XP Professional or Windows 2003 Server)
DELL Pentium 4, 3.0 GHz minimum
Station PC
Comments
Recommended Processor
Only Dell PCs are qualified to run EBI. Dual Intel processor configuration also supported. Hyperthreading is not supported on Windows 2000 See more detailed information below for EBI Server, NXN and Point Server PCs*
System Memory (RAM) Disk Video resolution Load device Storage device Serial connection
2 GB minimum 80 GB minimum
2 GB minimum 80 GB minimum
1 GB minimum 20 GB Minimum
CD-ROM SCSI tape drive, ZIP drive, CR-RW, DVD COM1, COM2 or Stallion EC8/64-PCI-K EasyConnection Smart Host Adaptor PCI bus with Stallion PA-EC-8D4K, 8-Port RS232/422/485 Async module (DB25)
CD-ROM Station serial connection not supported. Stations can connect serially through modems via RAS See Product Bulletin PB-191 for connection details
RS232/485 Convertor
Network connection
100 Mb Dell Onboard NIC or 3-Com Etherlink III (see comments) Intel Pro/100 S Dual Port Server Adapter (PCI) UL Projects must use UL listed hardware from Honeywell Center of Advance Solutions in North America UL Projects must use UL listed hardware from Honeywell Center of Advance Solutions in North America
For UL equipped systems, a Honeywell-labelled NIC for UL must be used. See UL web site (address below)
Internal speaker or Soundblaster Pro Flashpoint 3Dx Lite PCI Flashbus MV Lite PCI Twain compatible digital camera - Logitech Quick Cam Express (USB Internet Video Camera) - Black Box USB Video Adapter (IC167A) - 3COM Watchport V USB camera
Internal speaker or Soundblaster Pro Flashpoint 3Dx Lite PCI Flashbus MV Lite PCI Twain compatible digital camera - Logitech Quick Cam Express (USB Internet Video Camera) - Black Box USB Video Adapter (IC167A) - 3COM Watchport V USB camera Flashbus MV Lite PCI card has compatibility issues with Dell GX110 Limitation: Using the Black Box Twain Interface, only a 70% capture success rate is achieved,
Card printing
Epson StylusPro XL 132 column Epson compatible dot matrix printer qualified for local language (see comments)
132 column Epson compatible dot matrix printer qualified for local language (see comments)
The Epson LQ2070+ ESC P2 has been qualified for the English language
Report printing
Acecad Acecat III Interlink Electronics ePadInk Emulex 2500 series Lantronix MSS1-T Acola Cobox v1.02 Stallion EasyServer II Rev 1.10 Cobox UDS-200 (Encryption). SDS-1100 (Encryption) Digi One TS High Speed Intelligent 1 Port (RS232/422/485 Switchable)
Acecad Acecat III Interlink Electronics ePadInk Stallion EasyServer requires v6.2.0u4 or later firmware
Modem
Any Windows 2000 compatible modem (e.g. Netcomm M7F; US Robotics Sportster 14400 fax modem or US Robotics 56K fax modem - see comments)
Netcomm M7F; US Robotics Sportster 14400 fax modem or US Robotics Refer to interfaces & Options sheets for specific modem details 56K fax modem (see comments)
Predator LT2 (2 monitor) or LT4 (4 Monitor), Matrox G450 - Driver Version 5.52.010 or higher (2 Monitor)
Hardware obsolescence If you know that a device in the above list is obsolete or unavailable, please notify BC-Support. *EBI Server RAM guidelines In general, the more RAM the system has, the more smoothly it will run. The true RAM requirements of an EBI system are largely a matter of judgement, and cannot be quantified by a simple formula. The following guidelines may help to create a better understanding of the RAM requirements of your EBI System: EBI Server PC: a) 1 GB minimum RAM for the EBI Server PC b) If the sum of connections (i.e. Stations plus Channels) exceeds 10, add 64 MB for every 5 connections above 10. (e.g. 5 stations, 6 channels requires an additional 64 MB) c) Add 512Mb for Redundancy or DSA d) Add 256Mb for every point server installed on the EBI Server machine (see point server tab) Networked XLNET Node (NXN) PC: 256Mb minimum, 384Mb if more than 10 busses used HMIWeb displays or Asset Locator (EIRIS): 512 Mb RAM for stations required to display HTML based displays or badge icons To evaluate the adequacy of RAM on a running system: Page Faults/second should be < 1 when the Server is in a steady state . View this using the memory object in Windows 2000 Performance Monitor RAM should be at least (Total Commit Charge) * 0.75 View this using the memory object in Windows 2000 Performance Monitor For more detail, refer to section "System Monitoring and Assessing the Need for Hardware Upgrades" in the Installation Guide
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Hardware Compatibility
Page 3 of 8
Version 5 15-December-2005
EBI Server PC
Comments
Refer to DVM R200.1 Compatibility Matrix for full DVM system compatibility.
See Operating System sheet Internet Explorer 6.0 SP1 Windows IIS Components
See Operating System sheet Internet Explorer 6.0 SP1 Windows IIS Components
IIS Components are automatically installed with Windows Server versions and are updated by applying OS service packs. Included on EBI CD3 and the installation is based on the system licence. MDSE/SQL SP4 is included on the EBI CD set and is automatically installed. If an older version of MDAC is already installed, the installation program will now automatically prompt if you wish to proceed with installation of MDAC 2.8
Microsoft .NET Framework Custom ODR report building Office Software/Active Documents Server Application Development (Application Toolkit) Network application development (Network API) AnitVirus Software
Version 1.1 Crystal Reports 8.5 MS Access 2003 Microsoft Office 2003 Microsoft Visual Studio 6.0 SP5 (C/C++); Compaq Visual Fortran 6.1
Version 1.1 Crystal Reports 8.5 MS Access 2003 Microsoft Office 2003 Such applications can run only on the EBI Server PC Microsoft Visual Studio 6.0 SP5 (C/C++); Compaq Visual Fortran 6.1 Symantec AntiVirus Corporate Edition 8.1 (Norton) McAfee VirusScan Version 7.1.0 Version 6 Build 1.11 LincNet for Windows v05.10.02 (see comments) For applications on any networked PC - not only Station PCs Performance increases will be gained if the data directory is excluded from checking on the servers.
Symantec AntiVirus Corporate Edition 8.1 (Norton) McAfee VirusScan Version 7.1.0 Version 6 Build 1.11 LincNet for Windows v05.10.02 (see comments) v2.43 Version 7.03 Cimetrics BACstac 4.0E 7.01.02 5.01.02
Incident Reporting (IRIMS) PCSC configuration software RSLinx XLToolkit BACstac CARE
LincNet versions below this release are not supported to run on the EBI server. Used in Allen-Bradley interfaces XL Toolkit Version 7.03 is the only version that is supported by the QB XL Toolkit Import Wizard. Included on the EBI CD1 CARE remote sync server 2.08.09 is included on EBI CD1. CARE 5.00 Build 100 and CARE 5.01/7.01 Build 118+ are the only versions supported by the QB CARE Import Wizard
Used for LonWorks interface and EXCEL 5000 via LON. Do not install an LNS 3.08 network management tool on the same computer as the LonWorks Point Server or the EXCEL 5000 Point server via LON. This includes LonMaker 3.1 and earlier, CARE 5.01.01 and earlier and CARE 7.01.01. Used for LonWorks interface and EXCEL 5000 via LON. Do not install an LNS 3.08 network management tool on the same computer as the LonWorks Point Server or the EXCEL 5000 Point server via LON. This includes LonMaker 3.1 and earlier, CARE 5.01.01 and earlier and CARE 7.01.01.
LonMaker
LonMaker 3.1
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Software Compatibility
Page 4 of 8
Version 5 15-December-2005
Windows XP Professional Service Pack 2 Microsoft MSDE 2000 and MSDE 2000 SP4 are automatically installed by EBI. Windows Server 2003 Service Pack 1 Microsoft SQL 2000 Server and SQL 2000 Server SP4 are automatically installed by EBI. Windows 2000 Professional Service Pack 4 Microsoft MSDE 2000 and MSDE 2000 SP4 are automatically installed by EBI. Windows 2000 Server Service Pack 4 Microsoft SQL 2000 Server and SQL 2000 Server SP4 are automatically installed by EBI. Windows Components Windows Terminal Services
Recommended
Recommended
Recommended
Recommended
Recommended
Recommended
Recommended
Recommended
Supported
Supported
Supported
Supported
Supported
Supported
Supported
Supported
Supported
No
No
Supported
No
No
*Calculating Microsoft Client Access Licenses (CALs) Microsoft uses the concept of CALs to limit the number of client connections to servers using Windows 2000/2003 software. The total number of CALs used in an EBI configuration will determine which version of the Windows operating system is required. One CAL should be counted for every Station PC connected to the EBI Server. One additional CAL should be added for each additional PC using the EBI server as: - a File Server (for example if the client PC has a Server drive mapped). - a Print Server (where the client PC shares a printer on the server). - a Server for some other software package.
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Operating Systems
5 of 8
Version 5 15-December-2005
BNPS/IPPS PC
BACnet Direct PC
R310.1 DELL Pentium 4, 2.0 GHz minimum
Asset Locator-Elpas PC
R3.1 DELL Pentium 4, 2.0 GHz minimum R4.6.1
Temaline
R3.0
FPS
R1.0
IPPS
R3.2
XLS80e
The Temaline pointserver must DELL Pentium 4, 2.0 GHz minimum be installed on the same PC as EBI 256Mb for operating system 256Mb for operating system 256Mb for operating system 256Mb for operating system 256Mb for operating system 256Mb for operating system + 1 GB minimum for FPS + 256Mb for Lonworks Point + 128Mb for Excel 5000 Direct + 256Mb minimum for BNPS + 256Mb minimum for BACnet + 512Mb minimum for Elpas Redundancy / 512 MB Server and 128Mb for each 75 + 64 Mb for each 5 C-Busses Point Server Point Server minimum for FPS nondevices N/A d d 4GB for OS 4GB for OS 4GB for OS 4GB for OS 4GB for OS 4GB for OS N/A CD-ROM Dell Onboard NIC or 3-Com Etherlink III. Recommend 100MB CD-ROM Dell Onboard NIC or 3-Com Etherlink III. Recommend 100MB CD-ROM Dell Onboard NIC or 3-Com Etherlink III. Recommend 100MB CD-ROM Dell Onboard NIC or 3-Com Etherlink III. Recommend 100MB CD-ROM Dell Onboard NIC or 3-Com Etherlink III. Recommend 100MB
256Mb for operating system 256Mb for operating system + 256Mb minimum for BNPS + 256Mb minimum for BNPS
4GB for OS CD-ROM Dell Onboard NIC or 3-Com Etherlink III. Recommend 100MB
4GB for OS CD-ROM Dell Onboard NIC or 3-Com Etherlink III. Recommend 100MB
N/A N/A
BNPS/IPPS PC
Recommended Recommended Supported Supported
BACnet Direct PC
Recommended Recommended Supported Supported
Asset Locator-Elpas PC
Supported
Temaline
FPS
Recommended
IPPS
Recommended Recommended Supported Supported
XLS80e
Supported Supported Recommended Supported
N/A
Not Supported Recommended
N/A
Supported Supported
N/A
Supported Supported
N/A
*ELPAS and LonWorks Point Servers are not to be installed on the same PC as both use different versions of LNS as mentioned in the Software Compatibility Sheet. Allow 256 Mb of RAM for operating system plus RAM requirement for point servers. E.g. Lonworks Point Server with 150 devices plus Excel 5000 Direct with 10 Excel 5000 busses 256Mb (operating system) + 256Mb + 2*128Mb (Lonworks Point Server) + 128Mb + 2*64Mb (Excel 5000 Direct) = 1 GB RAM required Based on 55 parameters being used per LonWorks device
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Point Servers
6 of 8
Version 5 15-December-2005
XL100A XC5010A
1.01.32
1.01.32
Legacy Only
The Type A controller does not support report by exception for parameters "Condition" and "ModeState". Because of this, these parameters will be scanned whenever required. Try and limit the use of parameters ModeState and Condition on custom graphics as scanning these parameters will increase the bus load and can decrease overall performance. Excel 5000 Direct does not support any firmware version earlier than v1.01.32. Earlier versions must be upgraded.
XL80 XL100B XC5010B (XL500) XC5010C XCL5010 XL100C XC5010C LonMark XCL5010 LonMark XL100C LonMark XL50 Zone Manager (E-Link) BNA 1C, BNA 2CS BNA 1C, BNA 2CS XD505A XD508 XPC500 ISA XPC500 PCI XM100A XL500 controllers with XM100 modem capability (XC5010C, XCL5010,
1.03.04, 1.05.01
1.03.04, 1.05.01
Legacy Only
2.06.05
2.06.05
2.04.04, 2.06.05
2.04.04, 2.06.05
2.06.05
Excel 5000 Connection BNA I Excel 5000 Connection BNA II Excel 5000 Connection C-Bus Submodule Excel 5000 Connection C-Bus Interface Card EXCEL 5000 Modem Device
1 1 1 2 2 1 1 1 1
2.05.00, 2.06.06 1.02.01 3.0.0 H 3.0.0 H 1.27 1.3 1.01.16 1.0 1.02.06 2.03.05, 2.04.04, 2.06.05
2.05.00, 2.06.06 1.02.01 3.0.0 H 3.0.0 H 1.27 1.3 1.01.16 1.0P 1.02.06 2.04.04, 2.06.05 Netcomm SmartModem 56K Netcomm Roadster II 56 Ultra SVD Netcomm Roadster V.92 USB U.S.Robotics 56K FaxModem Netcomm RAVE AM5060 Westermo TD-35 Serial PnP Modem
2.06.06 Legacy Only 3.0.0 H 3.0.0 H Legacy Only (Use BNA) Legacy Only (Use BNA) Legacy Only (Use BNA) Legacy Only (Use BNA) Legacy Only 2.06.05 Netcomm SmartModem 56K Netcomm Roadster II 56 Ultra SVD Netcomm Roadster V.92 USB U.S.Robotics 56K FaxModem Netcomm RAVE AM5061 Westermo TD-35 Serial PnP Modem Westermo TD-35 Serial PnP Modem Netcomm SmartModem 56K U.S.Robotics 56K FaxModem Legacy Only
2.06.06 is required for EXCEL 5000 via LON Bootloader 1.0.3 BNA I required Bootloader 1.0.1 BNA II required
Drivers installed with Windows Hardware Discovery Wizard Firmware 2.06.05 with EXCEL 5000 via LON enabled does not support the dialup capability. XDM506 has not been tested. Modem device
It is highly recommended that modems contain internal reset circuitry such as SmartModem and Westermo modems. Modems must be a Windows compatible plug and play modem with corresponding modem driver. Modems can be connected via COM ports, multiple port serial boards, USB etc.
Westermo TD-35 Serial PnP Modem Netcomm SmartModem 56K U.S.Robotics 56K FaxModem
It is highly recommended that modems contain internal reset circuitry such as SmartModem and Westermo modems.
See PB-211 for details of modem initialisation and response strings. Supported modems must contain internal reset circuitry such as SmartModem and Westermo modems.
Excel Web
XL1000A500
Linux Flash Image 1-00-00 Excel Web Firmware 1-00-00 Linux Flash Image 1-00-00 Excel Web Firmware 1-00-00 VAVII plug-in 4.2.4 FCU2 plug-in 1.16 UV plug-in 1.2.3 CVAHU plug-in 1.2.4 HYD plug-in 1.14 CHC plug-in 1.13 Thermostat plug-in 1.1.3 Wireless Receiver plug-in 1.1.3 Excel 12 plug-in 2.3.4.2 Not tested PCLTA-20 PCLTA-21 Not tested 1.02.07 1.11.20 1.05.01 1.01.18 4.3.1
Linux Flash Image 1-00-00 Excel Web Firmware 1-00-00 Linux Flash Image 1-00-00 Excel Web Firmware 1-00-00 VAVII plug-in 4.2.4 FCU2 plug-in 1.16 UV plug-in 1.2.3 CVAHU plug-in 1.2.4 HYD plug-in 1.14 CHC plug-in 1.13 Thermostat plug-in 1.1.3 Wireless Receiver plug-in 1.1.3 Excel 12 plug-in 2.3.4.2 i.LON600 Router 1.05.01
XL1000A1000
LonWorks Devices
VAVII (W7751) FCU2 (W7752) UV (W7753) CVAHU (W7750) HYD (W7762) CHC (W7763) Thermostat (Q7300) Wireless Receiver (Q7790) Excel 12 and Smart I/O (W7704)
VAVII plug-in 4.2.4 FCU2 plug-in 1.16 UV plug-in 1.2.3 CVAHU plug-in 1.2.4 HYD plug-in 1.14 CHC plug-in 1.13 Thermostat plug-in 1.1.3 Wireless Receiver plug-in 1.1.3 Excel 12 plug-in 2.3.4.2 2.02 2.02 2.02 1.06 1.02.07 1.11.20 1.05.01 1.01.18 4.3.1
PCLTA-10 PCLTA-20 PCLTA-21 PCNSI i.LON100 i.LON100e2 i.LON600 Router i.LON1000 Router Loytec L-IP Router
SLTA-10 and i.LON10 not recommended for customer sites, testing/demonstration only.
Excel Plus R7044 Excel Classic R7510 Excel EMC (via S-Bus) Excel EMC (Via C- Bus) Excel IRC Legacy Controller Interface BNA I Legacy Controller Interface BNA I Legacy Controller Interface BNA II Legacy Controller Interface BNA II DeltaNet L2
1 1 2 2 1 1 1 2 2 1
R7044 A/B, R7044 D/E/G, Microcells R7510A1005, R7510B1003 W7161 A/B/C/D W7161 A/B/C/D R7451 BNA 2CS BNA 2DN BNA 2CS BNA 2DN
R7044A/B 9.6 and later, R7044D/E/G 4.3 R7044A/B 15.0, R7044D/E/G 10.3 and later S1014, S4001 3.5S or later 3.03 or later 8.0 or later 3.0.0.H 3.0.0.H 3.0.0 H 3.0.0 H VNC ver 3.3.3 R7 XBSi ver 2.3.3 Gateway ver 17.0 Delta Upgrade PROGCNFG.EXE version 7.3.3 S1014, S4002 3.5S 3.03 8.0 3.0.0.H 3.0.0.H 3.0.0.H 3.0.0.H VNC ver 3.3.3 R7 XBSi ver 2.3.3 Gateway ver 17.0 Delta Upgrade PROGCNFG.EXE version 7.3.3
R7044A/B 15.0, R7044D/E/G 10.4 S1014, S4003 3.5S or later 3.03 or later 8.0 or later 3.0.0.H 3.0.0.H 3.0.0.H 3.0.0.H VNC ver 3.3.3 R7 XBSi ver 2.3.3 Gateway ver 17.0 Delta Upgrade PROGCNFG.EXE version 7.3.3 3.2 2.1 2
It is recommended to upgrade the firmware to the tested firmware version It is recommended to upgrade the firmware to the tested firmware version It is recommended to upgrade the firmware to the tested firmware version
1 1 1 1
CA LJ AE XLS140
3.2 3.2 2.1 2.1 2 2 FPS 3.0, FNA firmware 1.0.1.E, FNA Bootloader FPS 3.0, FNA firmware 1.0.1.E, FNA Bootloader Fna_blups_v1.0.1.bin, XLS140 Fna_blups_v1.0.1.bin, XLS140 Bootloader 3.0.2, XLS140 Application 3.3.11, NCM 2.4.11 Bootloader 3.0.2, XLS140 Application 3.3.11, NCM 2.4.11 4.20D, 4.30 NCM 2.4.11 XLS CPU microcode (firmware) should be 3.41 or later which is supplied with SDU 3.4 or later. 4.20D, 4.30 NCM 2.4.11 SDU 3.4 and CPU microcode V3.41, LAN interface 32004871 series V3.0
Notifer (via XLS80e Point Server) Notifier (via BACnet Point Server) XLS (via XLS Scan Task)
2 1 1
The firmware for the XLS LAN interface (32004871 series) requires version 3.0 or later to support LAN failure detection. XLS200 and XLS1000 via XLS LAN interface (F-Box) or (32004871 series)
1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
MicroLPM MicroLPM Plus MicroLPM Plus 2 MicroLPM Plus 4 MicroELV Ultimate MicroLPM SIM32 IQ Series RSI HandKey II RSI ID3D 808S, 808SX, 808SN 804S, 804SX, 804SN 818SX, 814SX, 818SC 4100 Star I Star II
3.2 1.2b to 1.9.5 2.2b to 2.73 3.6b to 3.9.3 7.9.3 5.9.16 UM07.916J or higher SI +07.916yi 7.9.xx RSIdll32.dll Ver 2.5.0.1
No elevator control support. Direct connection to F&S bus via 2 serial ports only 1.2 3.9.5 7.9.9 5.9.16 UM07.916J or higher SI +07.916yi 7.9.12q RSIdll32.dll Ver 2.5.0.1 808sx y2k-comp REV0 28/4/98 not tested 818sc y2kcomp-revF 5/5/98 V2.24 5/5/98 V2.38_4100 Dec 7 2000 V2.74 only Galaxy 60 (V 4.5), Galaxy 500 (V 4.5), Galaxy 3144 (V4.97) Version 4.6.1 Stand-alone pin pad not supported. No elevator control. No dial up Stand-alone pin pad not supported. No dial up. Stand-alone pin pad not supported. ELV and Dialup are not supported Stand-alone pin pad not supported. No dial up. Stand-alone pin pad not supported. No elevator control. No dial up RS485 multi dropping is not recommended as there is a hardware issue with the controller that causes communications errors. Direct RS232 connection and dialup not supported. Ethernet interface is supported 1.95
Connection via Ethernet SIM board (32 input alarm panel) IQ controllers are available in two memory sizes: 8,000 and 20,000 card holders. IQ600 and IQ1000 consist of the IQ200 with IQ400 and IQ800 expansion boards respectively. IQ also available with SAM board (uLPM type)
V2.74 only
Galaxy 8 , Galaxy 18, Galaxy 60, Galaxy Galaxy 60 (V 4.5), Galaxy 500 (V 4.5), 128, Galaxy 500, Galaxy 504, Galaxy Galaxy 3-144 (V4.97), Ethernet (V 2.04) 512, Galaxy 3-144,Galaxy 3-520 Please consult Temaline Release Version 4.6.1 Bulletin 4.6.1 and Temaline Compatibility Tables. AD1650B, AD2050, AD2150, AD2350 Max 1000 Pacom 2030, Pelco CM9750, CM9760 WV-CU550 and WJ-SX550 WV-CU550 and WJ-SX550 LTC8300, TC8500, TC8600, TC8700, TC8800 VBLX4U Firmware version 3.96F Version 3 and 4 Version 7 and 8 firmware 1.43 2.47
Please consult Temaline Release Standard EBI Cardholder Management System (incl. CMS PhotoID) is replaced with Temaline Cardholder Management System. Bulletin 4.6.1 and Temaline Compatibility Tables. Support alarm transfer from EBI to the switcher only Support alarm transfer from EBI to the switcher, and PTZ Support alarm transfer from EBI and PTZ. Supports variable pan and tilt speeds. Supports alarm transfer from EBI to the switcher and monitoring of up to 64 alarm points in the switcher itself. Supports alarm transfer from EBI to the switcher and monitoring of up to 64 alarm points in the switcher itself.Support for switching upto 64 cameras and 16 monitors Support alarm transfer from EBI to the switcher, and PTZ New display included for this interface for display and control of camera-monitor mappings. Supports alarm transfer to EBI, PTZ operations, variable pan/tilt speeds, programmable sequences, display and control of switcher camera-monitor mappings
3 1 1 3 3 1 1
Not tested V4.25 V740.001 Not tested Not tested LTC8300 3.96F
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Page 7 of 8
Version 5 15-December-2005
2 2 2 2 1 1 1 1 1 2 2 1
Tecom Challenger
Version 8 V8-C-RAD:822E, v8.64 and v8.67 Version 6 panels with Version 7 firmware V35EX V38E Build 49/100 or higher Rev 4F or later Rev HPC1F I9000 V000 15/10/98 Not tested
No access control support Model Tecom Challenger (Panel V8, or panel V6 with firmware V7). No access control support. Pacific ONLY Digital point scanning and control only Digital point scanning and control only Direct interface to eff eff has been withdrawn. Please contact EMEA Product Management for more information.
V120.02
Native ORBIX Protocol Communicates via a COM port, terminal server or digiboard
V421.1
Only support up to 10000 cards. 420.1 and above are Y2K-compliant. Only supports up to 256 access groups. Requires a DOS 6 platform and a Digiboard PC/Xi. Supports Microlpm 1.2b to 1.95, MicroLPM Plus 2.2b to 2.73, MicroLPM Plus 2 3.6b to 3.9.3, MicroLPM Plus 4 7.9.3, SE 8xx and 4100, Otis EMS V1.51 and 1.6, EPL Prologic and EPL TMS900, Boral HLI Type 2, Microswitch SID 2000, Yamatake Honeywell MX100
Common Interfaces PLCs LCS 620 Modbus A-B Serial Allen-Bradley PLC5 Allen-Bradley SLC5 Allen-Bradley SLC500 A-B RSLinx Allen-Bradley PLC5 Allen-Bradley SLC5 Allen-Bradley SLC500 Allen-Bradley CL5550 UMC800 (Universal Multiloop Controller) Options Shift Management CardHolder Object Model (CHOM) Asset Locator-ELPAS Group Control license UL Compliance Alarm Pager
1 1 1 1 1
LCS IPC620-35
Ethernet, Dual Ethernet, Serial and Redundant Serial connections Modbus TCP and Modbus RTU supported. Gould Modbus protocol functions 01-06. Serial and Redundant Serial Direct RS-232; RS-232 to RS-485 converter; KF2 or redundant KF2 to Data Hiway+ KF3 to Data Hiway DH485 RS-232 to RS-485 converter; KF2 to Data Hiway+ DH485
V 2.1 1 1 1 1 2
V 2.1 Ethernet direct from EBI Server; 1784-KT to Data Hiway+; 1784-KTC to Control Net Ethernet direct from EBI Server; 1784-KT to Data Hiway+ Ethernet direct from EBI Server; 1784-KT to Data Hiway+ Ethernet direct from EBI Server; 1784-KT to Data Hiway+; 1784-KTC to Control Net Uses Honeywell's Universal Modbus protocol
Lighting Control Deadman Timer Guard Tour PeopleSoft Integration Cardholder Database Interface Incident Reporting (IRIMS) Networking Network API for Windows Network Server Web Toolkit Distributed Server Architecture (DSA) Open Systems AdvanceDDE client BACnet Client BACnet Server OPC Client
Control of point server points not supported. Control of point server points not supported. Control of point server points not supported. Global HRMS Release 7.5 using PeopleTools 7.5 Version 6 Build 1.11 Version 6 Build 1.11 See Software Compatibility Sheet 780.0.xx.3 (xx = 10 for read only, 20 for read/write version) 780.0.xx.3 (xx = 10 for read only, 20 for read/write version) Works with EBI R110 or later only. Tested and supported for IE 5.01, IE 5.5 and IE 6.0. 780.0.xx.3 (xx = 10 for read only, 20 for read/write version) Requires Windows 2000/2003 Server 1 1 1 1
Refer to PICS statement for BACnet compliance. Refer to PICS statement for BACnet compliance. Can also communicate with OPC Servers compialnt with OPC Data Access Standard version 1.0a. OPC DA 2.03 and 2.04 are also supported. OPC Version 2.0 Data Access specification. BSTR and DATE data types are not supported.
1 1
OPC Version 2.0 Data Access specification OPC Alarm and Events Specification Version 1.02, and the OPC Common Definitions and Interfaces specification Version 1.0 R300.6 Dialogic D/41D and Dialogic D/4PCI Phone Control 100.3 3.1 (D/41D) 5.1.1 (D/4PCI) 310.0
OPC Version 2.0 Data Access specification OPC Alarm and Events Specification Version 1.02, and the OPC Common Definitions and Interfaces specification Version 1.0 R300.6
Can also accept connections from OPC Version 1.0a clients. OPC Version 2.0 Data Access specification. OPC Alarm and Events Specification Version 1.02, and the OPC Common Definitions and Interfaces specification Version 1.0.
R300.6 Only compatible with Access 97 Requires Network Server option on EBI Server Phone Control 100.3 (D/41D) System Release 5.1.1 (D/4PCI) Available on separate media. Requires Network Server option on EBI Server. Tested and supported on IE 6.0 DNA V 3.1
DNA V Phone Control 100.3 System Release DNA V 3.1 (D/41D) System Release 5.1.1 (D/4PCI) 310.0
Equipment available yes (in HSC) 1 Primary interfaces (fully supported) 2 Secondary Interfaces (Less popular or regional yes (in HSC or regional TAC) interfaces) 3 Ported & Not Tested 4 Not Ported & Not Tested 5 Withdrawn no no no
Fully Tested yes (by HSC) yes (By HSC or regional TAC to HSC standards) no no no
EBI_Compatibility_Matrix_R310_1_Ver5.xls
Page 8 of 8