FD series
50/60Hz
10P01E-A-0
Our new advanced technology has realized high efficiency, strong heating and long piping. This contributes to the environmental protection through energy saving and permits installation of the units (4~6HP) considering a heating operation under temperature conditions down to -20C and design flexibility has been improved by extension of piping length to 100m.
NEW
1.5~2.5HP
3HP
Line up
1.5 Hyper Inverter
4~6HP
HP
2.5
10
High efficiency
, The industry s highest COP levels are achieved by our latest technologies, such as new high efficient twin rotary compressors and the combination with new Hyper inverter outdoor units.
EER in cooling
COP in heating
3.62
3.71
3.50
Micro Hyper
Micro Hyper
Micro Hyper
Micro Hyper
Micro Hyper
Micro Hyper
4HP
5HP
6HP
4HP
5HP
6HP
Long piping
(in case of 4~6HP)
Strong heating
(in case of 4~6HP)
-20C : Heating operation down to -20C -15C : Nominal heating capacity maintained at -15C
Height difference Piping length
(Outdoor higher than Indoor)
-20C
Heating
+20C
30m
-15C
Cooling
+43C
50
100m
-30
-20
-10
10
20
30
40
50
(kW)
Heating capacity
50C
nominal heating capacity 14.0kW
Hyper Inverter
Hyper Inverter
8.8 0
Micro Inverter
-15C
nominal heating capacity
(kW at outdoor temperature of 7C)
2C
7C
Micro Inverter
model name FDT100VSX(4HP, 3phase 380V) FDT125VSX(5HP, 3phase 380V) FDT140VSX(6HP, 3phase 380V)
heating capacity at outdoor temperature of -15C
Please refer to our technical manual for installation conditions, operation range and heating/cooling capacities.
Micro Inverter
Compact Design of outdoor units
Line up
1.5 Micro Inverter 2 2.5 3 4 5 6 8
HP
10
Height
Height
390mm
Height
185mm
455mm
Width
Width
380mm
380mm
Depth
350mm
Depth
350mm
FDC200VS (8.0HP)
Fits into elevators
FDC250VS (10.0HP)
74 74 74 122 140
*Reduction
-8 -44 -51 -103 -85
Size reduction and high efficiency performance on the DC twin rotary compressors
(Micro Inverter 4-6HP)
Employment of DC twin rotary compressor has enabled to utilize a high-speed range of up to 120 rps at the maximum to secure the required capacity. Optimum compressor control has been realized by employing the vector control* and the starting current has been improved significantly compared with former models. Moreover, vibration has been reduced.
Reduction in height by 22.3% Reduction in volume by 44.1%
* Vector control means a. technique to realize an optimum control by converting the current wave to a smooth sinusoidal waveform
Height at 440 mm
Height at 342mm
133mm
Former model
New model
Controllability
Reliability in the protection of compressor has been improved by optimizing the controls of oil return, electronic expansion valve, etc.
Former compressor
High technology
POINT
POINT
2 3
POINT
Super heat control with low pressure sensor, works better in tough conditions
4 5
FDC200VS
(8.0HP)
970 mm
POINT
m 370
POINT
CLASS
A
B C D E F G
Energy
Air-conditioner
A B C D E F G
Less efficient
Annual energy consumption, kWh in cooling mode
(Actual consumption will depend on how the appliance is used and climate)
kW
Type
Heat output
kW
G: lower
Heating Cooling
-10 0 10 20
A: higher
Heating performance
+20C +43C
Noise
(dB(A) re 1 pW)
-30
-20
30
40
50
FDT.FDTC
Previous
New
FDT125~140
365mm
298
mm
FDT40~71
270mm
reduction!!
18%
Previous
New
246
mm
reduction!!
9%
High efficiency
Reduction of air flow pressure loss
Expansion of outlet air flow area realizes reduction of pressure loss caused by air flow in the indoor unit. Load of fan motor is decreased and efficiency is increased.
Convenience
Signal output
A dry contact is equipped on an indoor unit to meet a possible need for signal output on the site.
CnT
XR2 XR3 XR4 XR5 XR5 XR1~5 : approx. DC12v Power source XR1 XR1 XR2 XR3 XR4 common output1 (run) output2 (heat) output3 (comp on) output4 (alarm) in put
Monitoring Function
Equipped with RS232C for connection directly to your PC monitoring and service tasks made simple with our service software (Mente PC).
-core
-core
Energy Conservation
A High Performance and Excellent Energy Conservation are achieved at the same time by an increased capacity of heat exchanger and employment of high efficiency DC motor etc.
Indoor unit
FDT40VD FDT50VD FDT60VD FDT71VD FDT100VD
* *
Micro Inverter
5.0 12.5 42,700 10,750 6.0 14.0 47,800 12,040 4.0 10.0 34,100 8,600 5.0 12.5 42,700 10,750 6.0 14.0 47,800 12,040 8.0 20.0 68,300 17,200 10.0 25.0 85,400 21,500
FDT125VD
NEW
FDT140VD
FDT100VD
FDT125VD
FDT140VD
FDC125VNX FDC125VSX
FDC140VNX FDC140VSX
FDC100VN FDC100VS
FDC125VN FDC125VS
FDC140VN FDC140VS
FDU125VD
NEW
FDU140VD
FDU100VD
FDU125VD
FDU140VD
FDU200VD
FDU250VD
FDC125VNX FDC125VSX
FDC140VNX FDC140VSX
FDC100VN FDC100VS
FDC125VN FDC125VS
FDC140VN FDC140VS
FDC200VS
FDC250VS
* *
* *
* *
* *
* *
FDUM125VD
NEW
FDUM140VD
FDUM100VD
FDUM125VD
FDUM140VD
FDC125VNX FDC125VSX
FDC140VNX FDC140VSX
FDC100VN FDC100VS
FDC125VN FDC125VS
FDC140VN FDC140VS
FDEN125VD
NEW
FDEN140VD
FDEN100VD
FDEN125VD
FDEN140VD
FDC125VNX FDC125VSX
FDC140VNX FDC140VSX
FDC100VN FDC100VS
FDC125VN FDC125VS
FDC140VN FDC140VS
[ INDOOR UNIT ]
CEILING CASSETTE -4way-
FDT
Point
CLASS
RC-E4
(Option)
RCH-E3
(Option)
RCN-T-36W-E
(Option)
Point
2 Installation Workability
Checking from access ports with detachable covers at each corner, arrangement of installation balance of indoor unit can be available without removing a panel. Workability is improved and time of installation is reduced. Point
For wireless control simply insert the infrared receiver kit on a corner of the panel
Point
Easy checking of drain pan condition is available by removing corner lid only. Due to new design changing fan motor is available without removing a panel. Temporally setting of drain pan is also available.
Drain can be discharged upwards by 700mm from the ceiling surface. It allows a piping layout with a high degree of freedom Depending on the installation location and 260mm flexible hose as a standard equipment supports easy workability.
10
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity kW ISO-T1(JIS) (Min~Max) Nominal heating capacity kW ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating kW COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) A Indoor Sound Ievel*1 dB(A) Outdoor Indoor Air flow CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Unit+Panel Net weight Panel Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference Cooling O/U Operating temperature range Heating O/U 4.0 (1.8~4.7) 4.5 (2.0~5.4) 0.93/1.15 4.30/3.91 A/A 5(12) FDT40ZIXVD FDT40VD SRC40ZIX-S FDT50ZIXVD FDT50VD SRC50ZIX-S FDT60ZIXVD FDT60VD SRC60ZIX-S
1Phase 220-240V 50Hz, 1Phase 220V 60Hz 5.0 (2.2~5.6) 5.4 (2.5~6.3) 1.29/1.29 3.88/4.19 A/A 5(14) 5.6 (2.8~6.3) 6.7 (3.1~7.1) 1.57/1.85 3.57/3.62 A/A
40 Unit:246x840x840 Panel:35x950x950 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) T-PSA-3AW-E Pocket Plastic net x1 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E 640x800(+71)x290 1,300x970x370 750x880(+88)x340 43 105 60 Scroll Rotary 1.4(15) 4.5(30) 2.95(30) 6.35/12.7 9.52/15.88 30 100 50 20 30 30 20 15 15 -15~43*2 -20~20 -15~20
7.1 (3.2~8.0) 8.0 (3.6~9.0) 1.90/2.07 3.74/3.86 A/A 5(17) Hi:35 Me:33 Lo:31 Cooling:51 Heating:48 Hi:21 Me:19 Lo:17 Cooling:60 Heating:50
Indoor unit
10.0 (4.0~11.2) 11.2 (4.0~12.5) 2.50/2.58 4.00/4.34 A/A 5(24) Hi:40 Me:37 Lo:35 Cooling:48 Heating:50 Hi:27 Me:24 Lo:20 100 Unit:298x840x840 Panel:35x950x950 32.5(Unit:27 Panel:5.5)
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity kW ISO-T1(JIS) (Min~Max) Nominal heating capacity kW ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating kW COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) A Indoor Sound Ievel*1 dB(A) Outdoor Indoor Air flow CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Unit+Panel Net weight Panel Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference Cooling O/U Operating temperature range Heating O/U FDT125VNXVD FDT125VD FDC125VNX FDT140VNXVD FDT140VD FDC140VNX FDT100VSXVD FDT100VD FDC100VSX FDT125VSXVD FDT125VD FDC125VSX FDT140VSXVD FDT140VD FDC140VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz 12.5 (5.0~14.0) 14.0 (4.0~17.0) 3.28/3.43 3.81/4.08 A/A 14.0 (5.0~16.0) 16.0 (4.0~18.0) 4.19/4.20 3.34/3.81 A/A
3Phase 380-415V 50Hz, 3Phase 380V 60Hz 10.0 (4.0~11.2) 11.2 (4.0~16.0) 2.50/2.58 4.00/4.34 A/A
14.0 12.5 (5.0~16.0) (5.0~14.0) 16.0 14.0 (4.0~20.0) (4.0~18.0) 4.19/4.20 3.28/3.43 3.34/3.81 3.81/4.08 A/A A/A 5(26) 5(15) Hi:42 Me:40 Lo:37 Hi:43 Me:41 Lo:38 Hi:40 Me:37 Lo:35 Hi:42 Me:40 Lo:37 Hi:43 Me:41 Lo:38 Cooling:48 Heating:50 Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52 Hi:30 Me:27 Lo:23 Hi:27 Me:24 Lo:20 Hi:30 Me:27 Lo:23 100 Unit:298x840x840 Panel:35x950x950 32.5(Unit:27 Panel:5.5) T-PSA-3AW-E Pocket Plastic net x1 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E 1,300x970x370 105 Rotary 4.5(30) 9.52/15.88 100 30 15 -15~43*2 -20~20
Indoor unit
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *2 :: If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 40/50ZIXVD 39dB, 60ZIXVD 46dB, 71VNXVD 46dB, 100/125/140VNXVD 51dB, 100/125/140VSXVD 51dB Air flow: 40/50ZIXVD 20CMM, 60ZIXVD 28CMM, 71VNXVD 28CMM, 100/125/140VNXVD 37CMM, 100/125/140VSXVD 37CMM
11
[ INDOOR UNIT ]
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
CLASS
Fits into standard 600 x 600 ceiling
FDTC 40/50/60VD
Wired remote control Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-TC-24W-ER
(Option)
Point
1 Quiet operation
35dB
Point
2 CLEARERAir Flow
(dB)
36 35 34 33 32 31 30 29 28 27 26 25
3dB Down
32dB 30dB
5dB Down
Point
New shape & angled louver redirects the air current away from the ceiling, to reduce ceiling stains
3 Installation Workability
For wireless control simply insert the infrared receiver kit on a corner of the panel wireless remote control RCN-TC-24W-ER
Previous (Cooling/Heating)
New (Cooling)
New (Heating)
FDTC40/50/60VD
Point
4 Compact Concept
Point
of exterior dimensions of a indoor unit are 570mm each, the installation work can be conducted smoothly with a beautiful finishing in 2x2 ceiling size.
12
248
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating Cooling/Heating COP Cooling/Heating Energy label Inrush current (Max. running current) kW kW kW 4.0 (1.8~4.7) 4.5 (2.0~5.4) 1.04/1.10 3.85/4.09 A/A 5(12) Cooling : Hi:42 Me:36 Lo:30 Heating : Hi:42 Me:36 Lo:32 47 Cooling : Hi:11.5 Me:9 Lo:7 Heating : Hi:11.5 Me:9 Lo:8 40 Unit:248x570x570 Panel:35x700x700 18.5(Unit:15 Panel:3.5) TC-PSA-25W-E Pocket Plastic net x1 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER 640x800(+71)x290 43 Scroll 1.4(15) 6.35/12.7 30 20 20 -15~43*2 -15~20 FDTC40ZIXVD FDTC40VD SRC40ZIX-S FDTC50ZIXVD FDTC50VD SRC50ZIX-S 1Phase 220-240V 50Hz, 1Phase 220V 60Hz 5.0 (2.2~5.6) 5.4 (2.5~6.3) 1.56/1.45 3.21/3.72 A/A 5(14) Cooling : Hi:46 Me:39 Lo:30 Heating : Hi:46 Me:39 Lo:32 48 Cooling : Hi:13.5 Me:10 Lo:7 Heating : Hi:13.5 Me:10 Lo:8 5.6 (2.8~6.3) 6.7 (3.1~6.7) 1.99/2.08 2.81/3.22 C/C FDTC60ZIXVD FDTC60VD SRC60ZIX-S
A dB(A)
*1 Sound Ievel
Indoor Outdoor
CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Unit+Panel Panel Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm Net weight kg Type of compressor Ref.amount precharged kg(m) Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference O/U Cooling Operating temperature range Heating O/U Air flow
Indoor
Indoor unit
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *2 :: If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 40/50/60ZIXVD 47dB Air flow: 40/50/60ZIXVD 13.5CMM
13
[ INDOOR UNIT ]
DUCT CONNECTED -High Static pressure-
FDU
Wired remote control RC-E4 RCH-E3
(Option) (Option)
CLASS
R410A
Fan control kit
(100~200Pa)
RCN-KIT3-E
(Option)
FDU 71/100/125/140VD
FDU 200/250VD
U-FCRA
Point
Point
High static pressure of 200 Pa (FDU200/250VD) extends the degree of freedom in the designing of air conditioners.
This is a real and earnest model for duct air-conditioning. A unit external static pressure of up to 200 Pa (FDU200/250VD) is possible. Precise air flow designing is possible.
Control box Slide type fan system Thin type duct connection opening
600mm
Fan motor
FDU100,125,140VD
Installation workability
FDU200,250VD
(FDU200,250VD)
Using piping attachment that has flared connection and brazed connection ends, there is no need conduct brazing work inside the outdoor unit.
Flared connection 19.05mm
232mm
14
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity kW ISO-T1(JIS) (Min~Max) Nominal heating capacity kW ISO-T1(JIS) (Min~Max) kW Power Consumption Cooling/Heating Cooling/Heating COP Cooling/Heating Energy label A Inrush current (Max. running current) Indoor 1 dB(A) Sound Ievel* Outdoor Indoor CMM Air flow Outdoor Pa External static pressure Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m difference O/U is lower Cooling O/U Operating temperature range Heating O/U
7.1 (3.2~8.0) 8.0 (3.6~9.0) 2.15/2.15 3.30/3.72 A/A 5(17) Hi:41 Lo:37 Cooling:51 Heating:48 Hi:20 Lo:17 Cooling:60 Heating:50 297x850x650 40
*FDU100VNXVD FDU100VD
FDC100VNX
10.0 (4.0~11.2) 11.2 (4.0~12.5)
*FDU125VNXVD FDU125VD
FDC125VNX
12.5 (5.0~14.0) 14.0 (4.0~17.0)
*FDU140VNXVD FDU140VD
FDC140VNX
14.0 (5.0~16.0) 16.0 (4.0~18.0)
750x880(+88)x340 60 2.95(30) 50
2.78/2.90 3.44/3.67 4.20/4.30 3.60/3.86 3.63/3.81 3.33/3.72 A/A A/A A/A 5(25) 5(29) 5(30) Hi:42 Lo:37 Hi:43 Lo:38 Cooling:48 Heating:50 Cooling:49 Heating:52 Hi:42 Lo:33.5 Hi:34 Lo:27 100 Standard:50, Max:130 350x1,370x650 63 Procure locally Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E 1,300x970x370 105 Rotary 4.5(30) 9.52/15.88 100 30 15 -15~43*2 -20~20
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity kW ISO-T1(JIS) (Min~Max) Nominal heating capacity kW ISO-T1(JIS) (Min~Max) kW Power Consumption Cooling/Heating Cooling/Heating COP Cooling/Heating Energy label A Inrush current (Max. running current) Indoor 1 dB(A) Sound Ievel* Outdoor Indoor CMM Air flow Outdoor Pa External static pressure Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m difference O/U is lower Cooling O/U Operating temperature range Heating O/U
10.0 (4.0~11.2) 11.2 (4.0~16.0) 2.78/2.90 3.60/3.86 A/A 5(16) Hi:42 Lo:37 Cooling:48 Heating:50 Hi:34 Lo:27
*FDU125VSXVD FDU125VD
FDC125VSX 3Phase 380-415V 50Hz
12.5 (5.0~14.0) 14.0 (4.0~18.0) 3.44/3.67 3.63/3.81 A/A 5(18) Hi:43 Lo:38 Cooling:48 Heating:50 Hi:42 Lo:33.5 100 Standard:50, Max:130 350x1,370x650 63 Procure locally Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E 1,300x970x370 105 Rotary 4.5(30) 9.52/15.88 100 30 15 -15~43*2 -20~20
*FDU140VSXVD FDU140VD
FDC140VSX
14.0 (5.0~16.0) 16.0 (4.0~20.0) 4.20/4.30 3.33/3.72 A/A 5(19) Cooling:49 Heating:52
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of FDU71/100/125/140 is 60Pa and that of FDU200/250 is 100Pa. 1 Indicates the these somewhat higher due *2 :: External staticvalue in an anechoic chamber. During operationcontrol.values areexternal static pressure to ambient conditions. external static pressure is ''High static pressure is changeable to be set by the remote Standard is factory setting. MAX * pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa. *3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
15
[ INDOOR UNIT ]
DUCT CONNECTED -Middle Static pressure-
FDUM
Wired remote control Wireless remote control RC-E4
(Option)
CLASS
RCH-E3
(Option)
Filter kit UM-FL1E : for 50 UM-FL2E : for 60, 71 UM-FL3E : for 100, 125, 140 RCN-KIT3-E
(Option) (option)
external static pressure loss:5pa
Point
1 Various Adaptability
Static pressure Pa
model 50/60/71VD 100VD 125/140VD Standard 50 60 60
Outline drawing(Unit:mm)
Model FDUM50VD
(50Hz)
Max 85 90 85
Selectable static pressure and Flexible duct design with selectable air suction (direct suction /duct suction) can meet wide pattern of installation.
Point
Drain can be discharged upwards by 600mm from the ceiling surface. It allows a piping layout with a high degree of freedom Depending on the installation location.
Models FDUM60V,71VD
Models FDUM100V,125V,140VD
16
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) kW (Min~Max) Nominal heating capacity ISO-T1(JIS) kW (Min~Max) Power Consumption Cooling/Heating kW Cooling/Heating COP Cooling/Heating Energy label Inrush current (Max. running current) A Indoor Sound Ievel*1 dB(A) Outdoor Indoor Air flow CMM Outdoor 50Hz/60Hz Static pressure Pa Exterior dimensions Height x Width x Depth mm Net weight kg Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm Net weight kg Type of compressor Ref.amount precharged kg(m) Ref.piping size Liquid/Gas Ref.piping length m Vertical height O/U is higher m difference O/U is lower m Cooling O/U Operating temperature range Heating O/U
5.0 (2.2~5.6) 5.4 (2.5~6.3) 1.52/1.41 3.29/3.83 A/A FDUM50ZIXVD FDUM50VD SRC50ZIX-S FDUM60ZIXVD FDUM60VD SRC60ZIX-S FDUM71VNVD FDUM71VD FDC71VNX FDUM100VNXVD FDUM100VD FDC100VNX
2.14/2.16 2.72/2.95 3.32/3.70 3.68/3.80 A/A A/A 5(17) 5(24) 5(14) Hi:37 Me:35 Lo:32 Hi:35 Me:32 Lo:29 Hi:34 Me:31 Lo:28 47 Cooling:51 Heating:48 Cooling:48 Heating:50 48 Hi:16 Me:15 Lo:14 Hi:13 Me:12 Lo:11 Hi:20 Me:18 Lo:15 Hi:28 Me:25 Lo:22 40 Cooling:60 Heating:50 100 Standard:50/40, Max:85/90 Standard:50/40, Max:85/100 Standard:60/60, Max:90/100 299x750x635 299x950x635 350x1,370x635 34 40 59 Procure locally Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E 640x800(+71)x290 1,300x970x370 750x880(+88)x340 43 105 60 Rotary Scroll 1.4(15) 4.5(30) 2.95(30) 6.35/12.7 9.52/15.88 30 100 50 20 30 20 15 -15~43*2 -20~20 -15~20
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) kW (Min~Max) Nominal heating capacity ISO-T1(JIS) kW (Min~Max) Power Consumption Cooling/Heating kW Cooling/Heating COP Cooling/Heating Energy label Inrush current (Max. running current) A Indoor Sound Ievel*1 dB(A) Outdoor Indoor Air flow CMM Outdoor 50Hz/60Hz Static pressure Pa Exterior dimensions Height x Width x Depth mm Net weight kg Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm Net weight kg Type of compressor Ref.amount precharged kg(m) Ref.piping size Liquid/Gas Ref.piping length m Vertical height O/U is higher m difference O/U is lower m Cooling O/U Operating temperature range Heating O/U
FDUM125VNXVD FDUM125VD FDC125VNX FDUM140VNXVD FDUM140VD FDC140VNX FDUM100VSXVD FDUM100VD FDC100VSX FDUM125VSXVD FDUM125VD FDC125VSX FDUM140VSXVD FDUM140VD FDC140VSX
4.34/4.69 3.62/3.77 3.23/3.41 3.45/3.71 A/B A/A 5(15) 5(26) Hi:37 Me:35 Lo:32 Hi:38 Me:36 Lo:33 Hi:38 Me:36 Lo:33 Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:48 Heating:50 Cooling:49 Heating:52 Hi:28 Me:25 Lo:22 100 Standard:60/55, Max:85/100 Standard:60/55, Max:85/100 Standard:60/60, Max:90/100 350x1,370x635 59 Procure locally Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E 1,300x970x370 105 Rotary 4.5(30) 9.52/15.88 100 30 15 -15~43*2 -20~20
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of indoor units is 60Pa. 1 Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *2 :: If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 50ZIXVD 35dB, 60ZIXVD 38dB, 71VNXVD 38dB, 100/125/140VNXVD 41dB, 100/125/140VSXVD 41dB Air flow: 50ZIXVD 14CMM, 60ZIXVD 18CMM, 71VNXVD 23CMM, 100/125/140VNXVD 34CMM, 100/125/140VSXVD 34CMM
17
[ INDOOR UNIT ]
CEILING SUSPENDED
FDEN
CLASS
FDEN 40/50/60/71/100/125/140VD
RC-E4
(Option)
RCH-E3
(Option)
RCN-E1R
(Option)
Point
Point
The refrigerant pipe from the unit can be arranged in three directions, rear, right and up. The drain pipe can be arranged in two directions, left and right. This will allow a free layout of piping for various installation conditions. The unit can only be serviced from the bottom.
All models fit compactly on ceiling. (Height-210mm or 250mm). Plain, modern design featuring rounded edges gives room a comfortable atmosphere. FDEN40VD, 50VD weights 30kg the lightest level in the industry. Convenient and quick installation.
300 or more
e d
150 or more
173
40
b c
40 Air outlet 690 195 235 271 Indication board Note(1) The slope of drain piping inside the unit is able to take incline of 10mm. 53 109 Drain hole connection(1) (VP20 (I.D.20))
5 or more
Obstacles
Dimension Table
model a 1022 1272 1572 b 990 1240 1540 c 1070 1320 1620 d 215 215 255 e 210 210 250 FDEN40,50 FDEN60,71 FDEN100~140
308
18
10
53
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source
1Phase 220-240V 50Hz, 1Phase 220V 60Hz 4.0 5.0 (1.8~4.7) (2.2~5.6) 4.5 5.4 (2.0~5.4) (2.5~6.3) 1.04/1.13 1.59/1.58 3.85/3.98 3.14/3.42 A/A B/B 5(12) Hi:39 Me:38 Lo:37 47 Hi:11 Me:9 Lo:7 40 210x1,070x690 28 7.1 10.0 (3.2~8.0) (4.0~11.2) 8.0 11.2 (3.6~9.0) (4.0~12.5) 2.11/2.11 2.80/2.88 3.36/3.79 3.57/3.89 A/A A/A 5(17) 5(24) 5(14) Hi:44 Me:41 Lo:39 Hi:41 Me:39 Lo:38 48 Cooling:51 Heating:48 Cooling:48 Heating:50 Hi:18 Me:14 Lo:12 Hi:26 Me:23 Lo:21 Hi:18 Me:14 Lo:12 100 Cooling:60 Heating:50 210x1,320x690 250x1,620x690 37 49 Pocket Plastic net x2 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-E1R 640x800(+71)x290 1,300x970x370 750x880(+88)x340 43 105 60 Scroll Rotary 1.4(15) 4.5(30) 2.95(30) 6.35/12.7 9.52/15.88 30 50 20 30 20 15 -15~43*2 -15~20 -20~20 5.6 (2.8~6.3) 6.7 (3.1~7.1) 1.95/2.12 2.87/3.16 C/D
Nominal cooling capacity ISO-T1(JIS) kW (Min~Max) Nominal heating capacity ISO-T1(JIS) kW (Min~Max) kW Power Consumption Cooling/Heating Cooling/Heating COP Cooling/Heating Energy label A Inrush current (Max. running current) Indoor *1 Sound Ievel dB(A) Outdoor Indoor Air flow CMM Outdoor Exterior dimensions Height x Width x Depth mm Net weight kg Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm Net weight kg Type of compressor Ref.amount precharged kg(m) Ref.piping size Liquid/Gas Ref.piping length m Vertical height O/U is higher m difference m O/U is lower O/U Cooling Operating temperature range Heating O/U
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) kW (Min~Max) Nominal heating capacity ISO-T1(JIS) kW (Min~Max) kW Power Consumption Cooling/Heating Cooling/Heating COP Cooling/Heating Energy label A Inrush current (Max. running current) Indoor Sound Ievel*1 dB(A) Outdoor Indoor Air flow CMM Outdoor Exterior dimensions Height x Width x Depth mm Net weight kg Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference O/U Cooling Operating temperature range Heating O/U FDEN125VNXVD FDEN125VD FDC125VNX FDEN140VNXVD FDEN140VD FDC140VNX FDEN100VSXVD FDEN100VD FDC100VSX FDEN125VSXVD FDEN125VD FDC125VSX FDEN140VSXVD FDEN140VD FDC140VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz 12.5 (5.0~14.0) 14.0 (4.0~17.0) 3.86/3.77 3.24/3.71 A/A 14.0 (5.0~16.0) 16.0 (4.0~18.0) 4.98/4.69 2.81/3.41 C/B 10.0 (4.0~11.2) 11.2 (4.0~16.0) 2.80/2.88 3.57/3.89 A/A
3Phase 380-415V 50Hz, 3Phase 380V 60Hz 12.5 14.0 (5.0~14.0) (5.0~16.0) 14.0 16.0 (4.0~18.0) (4.0~20.0) 3.86/3.77 4.98/4.69 3.24/3.71 2.81/3.41 A/A C/B 5(15) Hi:46 Me:44 Lo:43 Cooling:48 Heating:50 Cooling:49 Heating:52 Hi:29 Me:26 Lo:23
5(26) Hi:46 Me:44 Lo:43 Cooling:48 Heating:50 Cooling:49 Heating:52 Hi:29 Me:26 Lo:23
100
Hi:44 Me:41 Lo:39 Cooling:48 Heating:50 Hi:26 Me:23 Lo:21 100 250x1,620x690 49 Pocket Plastic net x2 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-E1R 1,300x970x370 105 Rotary 4.5(30) 9.52/15.88 50 30 15 -15~43*2 -20~20
100
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *2 :: If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 40/50ZIXVD 46dB, 60ZIXVD 50dB, 71VNXVD 50dB, 100VNXVD 46dB, 125/140VNXVD 50dB, 100VSXVD 46dB, 125/140VSXVD 50dB Air flow: 40/50ZIXVD 13CMM, 60ZIXVD 22CMM, 71VNXVD 22CMM, 100VNXVD 28CMM, 125/140VNXVD 32CMM, 100VSXVD 28CMM, 125/140VSXVD 32CMM
19
FDT
CLASS
FDT 100/125/140VD
RC-E4
(Option)
RCH-E3
(Option)
RCN-T-36W-E
(Option)
SPECIFICATIONS
Micro Inverter
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating Cooling/Heating COP Cooling/Heating Energy label Inrush current (Max. running current) Sound Ievel
3Phase 380-415V 50Hz, 3Phase 380V 60Hz 10.0 (4.0~11.2) 11.2 (4.0~12.5) 2.76/2.74 3.62/4.09 A/A Hi:40 Me:37 Lo:35 49 Hi:27 Me:24 Lo:20 12.5 (5.0~14.0) 14.0 (4.0~16.0) 4.05/3.77 3.09/3.71 B/A 5(15) Hi:42 Me:40 Lo:37 Cooling:50 Heating:51 Hi:30 Me:27 Lo:23 Cooling:75 Heating:73 14.0 (5.0~14.5) 16.0 (4.0~16.5) 4.98/4.57 2.81/3.50 C/B Hi:43 Me:41 Lo:38 51 Hi:30 Me:27 Lo:23
kW kW kW
10.0 (4.0~11.2) 11.2 (4.0~12.5) 2.76/2.74 3.62/4.09 A/A Hi:40 Me:37 Lo:35 49 Hi:27 Me:24 Lo:20
A dB(A)
*1
Indoor Outdoor
CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Unit+Panel Panel Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m difference O/U is lower O/U Cooling Operating temperature range Heating O/U
Air flow
Indoor
12.5 (5.0~14.0) 14.0 (4.0~16.0) 4.05/3.77 3.09/3.71 B/A 5(24) Hi:42 Me:40 Lo:37 Cooling:50 Heating:51 Hi:30 Me:27 Lo:23 Cooling:75 Heating:73
14.0 (5.0~14.5) 16.0 (4.0~16.5) 4.98/4.57 2.81/3.50 C/B Hi:43 Me:41 Lo:38 51 Hi:30 Me:27 Lo:23
Unit:298x840x840 Panel:35x950x950 32.5(Unit:27 Panel:5.5) T-PSA-3AW-E Pocket Plastic net x1 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E 845x970x370 81 Rotary 3.8(30) 9.52/15.88 50 30 15 -15~43*2 -20~20 83
20
Indoor unit
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *2 :: If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 100/125/140VNVD 51dB, 100/125/140VSVD 51dB Air flow: 100/125/140VNVD 37CMM, 100/125/140VSVD 37CMM
FDU
FDU 100/125/140VD
CLASS
A
*
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity kW ISO-T1(JIS) (Min~Max) Nominal heating capacity kW ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating kW COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) A Indoor *1 dB(A) Sound Ievel Outdoor Indoor Air flow CMM Outdoor External static pressure Pa Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m difference O/U is lower Cooling O/U Operating temperature range Heating O/U
*FDU100VNVD FDU100VD
*FDU125VNVD FDU125VD
RC-E4
(Option)
RCH-E3
(Option)
FDU 200/250VD
Fan control kit
(100~200Pa) [For 200/250VD] (option)
RCN-KIT3-E
(Option)
U-FCRA
FDC125VN FDC100VN 1Phase 220-240V 50Hz 10.0 12.5 (4.0~11.2) (5.0~14.0) 11.2 14.0 (4.0~12.5) (4.0~16.0) 2.88/2.99 4.04/3.79 3.09/3.69 3.47/3.75 B/A A/A 5(27) 5(25) Hi:43 Lo:38 Hi:42 Lo:37 Cooling:50 Heating:51 49 Hi:42 Lo:33.5 Hi:34 Lo:27 Cooling:75 Heating:73 Standard:50, Max:130 350x1,370x650 63 Procure locally Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E 845x970x370 81 Rotary 3.8(30) 9.52/15.88 50 30 15 -15~43*3 -15~43*2 -20~20
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP
Cooling/Heating kW kW kW
FDU140VNVD FDU140VD FDC140VN 1Phase 220-240V 50Hz 14.0 (5.0~14.5) 16.0 (4.0~16.5)
4.95/4.43 2.83/3.61 C/A 5(28) Hi:43 Lo:38 51 Hi:42 Lo:33.5
*FDU125VSVD FDU125VD
FDC125VS 3Phase 380-415V 50Hz
12.5 (5.0~14.0) 14.0 (4.0~16.0) 4.04/3.79 3.09/3.69
Micro Inverter
*FDU140VSVD FDU140VD
FDC140VS
14.0 (5.0~14.5) 16.0 (4.0~16.5) 4.95/4.43 2.83/3.61
3Phase 380-415V 50Hz, 3Phase 380V 60Hz 20.0 25.0 (7.0~22.4) (10.0~28.0) 22.4 28.0 (7.6~25.0) (9.5~31.5) 50Hz:6.59/6.08 50Hz: 9.91/8.50 60Hz:6.58/5.84 60Hz:10.21/8.22 50Hz:3.03/3.68 50Hz:2.52/3.29 60Hz:3.04/3.83 60Hz:2.45/3.41 50Hz:E/C 60Hz:E/B B/A 5(27) 5(24) 52 51 Cooling:57 Heating:58 57 50Hz:68, 60Hz:80 50Hz:51, 60Hz:60 Cooling:150 Heating:145 Standard:100, Max:200 360x1,570x830 92
Cooling/Heating Energy label A Inrush current (Max. running current) Indoor 1 dB(A) Sound Ievel* Outdoor Indoor CMM Air flow Outdoor 2 Pa External static pressure * Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference O/U Cooling Operating temperature range Heating O/U
81
A/A C/A B/A 5(16) 5(19) 5(18) Hi:42 Lo:37 Hi:43 Lo:38 51 Cooling:50 Heating:51 49 Hi:34 Lo:27 Hi:42 Lo:33.5 Cooling:75 Heating:73 Standard:50, Max:130 350x1,370x650 63 Procure locally Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E 845x970x370 83 Rotary 3.8(30) 9.52/15.88 50 30 15 -15~43 *3 -20~20
-15~20
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of FDU100/125/140 is 60Pa and that of FDU200/250 is 100Pa. 1 Indicates the these somewhat higher due *2 :: External staticvalue in an anechoic chamber. During operationcontrol.values areexternal static pressure to ambient conditions. external static pressure is ''High static pressure is changeable to be set by the remote Standard is factory setting. MAX * pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa. *3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
21
FDUM
CLASS
FDUM 100/125/140VD
Filter kit UM-FL3E : for 100, 125, 140
(option)
external static pressure loss:5pa
RC-E4
(Option)
RCH-E3
(Option)
RCN-KIT3-E
(Option)
SPECIFICATIONS
Micro Inverter
FDUM140VSVD FDUM100VSVD FDUM125VSVD FDUM100VNVD FDUM125VNVD FDUM140VNVD FDUM140VD FDUM100VD FDUM125VD FDUM100VD FDUM125VD FDUM140VD FDC140VS FDC100VS FDC125VS FDC100VN FDC125VN FDC140VN 1Phase 220-240V 50Hz, 1Phase 220V 60Hz 3Phase 380-415V 50Hz, 3Phase 380V 60Hz 10.0 14.0 12.5 10.0 14.0 12.5 kW (4.0~11.2) (5.0~14.5) (5.0~14.0) (4.0~11.2) (5.0~14.5) (5.0~14.0) 11.2 16.0 14.0 11.2 16.0 14.0 kW (4.0~12.5) (4.0~16.5) (4.0~16.0) (4.0~12.5) (4.0~16.5) (4.0~16.0) 50Hz:2.80/2.77 50Hz:4.95/4.89 50Hz:4.03/3.80 50Hz:2.80/2.77 50Hz:4.95/4.89 50Hz:4.03/3.80 Power Consumption Cooling/Heating kW 60Hz:2.80/2.80 60Hz:4.95/4.91 60Hz:4.03/3.85 60Hz:2.80/2.80 60Hz:4.95/4.91 60Hz:4.03/3.85 50Hz:3.57/4.04 50Hz:2.83/3.27 50Hz:3.10/3.68 50Hz:3.57/4.04 50Hz:2.83/3.27 50Hz:3.10/3.68 COP Cooling/Heating 60Hz:3.57/4.00 60Hz:2.83/3.26 60Hz:3.10/3.64 60Hz:3.57/4.00 60Hz:2.83/3.26 60Hz:3.10/3.64 Energy label A/A C/C B/A A/A C/C B/A Cooling/Heating 5(24) 5(15) Inrush current (Max. running current) A Hi:37 Me:35 Lo:32 Hi:38 Me:36 Lo:33 Hi:38 Me:36 Lo:33 Hi:37 Me:35 Lo:32 1 Indoor dB(A) Sound Ievel* 49 Cooling:50 Heating:51 51 49 Cooling:50 Heating:51 51 Outdoor Hi:28 Me:25 Lo:22 Indoor Air flow CMM Cooling:75 Heating:73 Outdoor Standard:60, Max:90/100 Standard:60/55, Max:85/100 Standard:60, Max:90/100 Standard:60/55, Max:85/100 Static pressure Pa Exterior dimensions Height x Width x Depth mm 350x1,370x635 Net weight kg 59 Air filter, Q'ty Procure locally Remote control(option) Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E Exterior dimensions Height x Width x Depth mm 845x970x370 Net weight kg 81 83 Type of compressor Rotary Ref.amount precharged kg(m) 3.8(30) Ref.piping size Liquid/Gas 9.52/15.88 Ref.piping length m 50 Vertical height O/U is higher m 30 difference m 15 O/U is lower Cooling O/U -15~43*2 Operating temperature range Heating O/U -20~20 Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max)
22
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of indoor units is 60Pa. 1 Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *2 :: If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 100/125/140VNVD 41dB, 100/125/140VSVD 41dB Air flow: 100/125/140VNVD 34CMM, 100/125/140VSVD 34CMM
FDEN
CEILING SUSPENDED
CLASS
FDEN 100/125/140VD
RC-E4
(Option)
RCH-E3
(Option)
RCN-E1R
(Option)
SPECIFICATIONS
Micro Inverter
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current)
kW kW kW
A dB(A)
*1 Sound Ievel
Indoor Outdoor
CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight Type of compressor kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m difference O/U is lower O/U Cooling Operating temperature range Heating O/U
Air flow
Indoor
FDEN140VNVD FDEN125VNVD FDEN100VNVD FDEN100VSVD FDEN125VSVD FDEN140VSVD FDEN100VD FDEN125VD FDEN140VD FDEN140VD FDEN125VD FDEN100VD FDC100VS FDC125VS FDC140VS FDC140VN FDC125VN FDC100VN 1Phase 220-240V 50Hz, 1Phase 220V 60Hz 3Phase 380-415V 50Hz, 3Phase 380V 60Hz 12.5 14.0 10.0 10.0 12.5 14.0 (5.0~14.5) (4.0~11.2) (4.0~11.2) (5.0~14.0) (5.0~14.5) (5.0~14.0) 16.0 14.0 11.2 11.2 14.0 16.0 (4.0~16.5) (4.0~16.0) (4.0~12.5) (4.0~12.5) (4.0~16.0) (4.0~16.5) 5.80/4.92 4.45/4.08 2.85/2.97 2.85/2.97 4.45/4.08 5.80/4.92 3.51/3.77 2.41/3.25 2.80/3.43 3.51/3.77 2.80/3.43 2.41/3.25 A/A E/C C/B A/A C/B E/C 5(24) 5(15) Hi:44 Hi:44 Hi:46 Me:44 Lo:43 Hi:46 Me:44 Lo:43 Me:41 Lo:39 Me:41 Lo:39 49 49 Cooling:50 Heating:51 Cooling:50 Heating:51 51 51 Hi:26 Hi:26 Hi:29 Me:26 Lo:23 Hi:29 Me:26 Lo:23 Me:23 Lo:21 Me:23 Lo:21 Cooling:75 Heating:73 250x1,620x690 49 Pocket Plastic net x2 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-E1R 845x970x370 81 83 Rotary 3.8(30) 9.52/15.88 50 30 15 -15~43*2 -20~20
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *2 :: If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 100VNVD 46dB, 125/140VNVD 50dB, 100VSVD 46dB, 125/140VSVD 50dB Air flow: 100VNVD 28CMM, 125/140VNVD 32CMM, 100VSVD 28CMM, 125/140VSVD 32CMM
23
MULTI SYSTEM
Up to Four indoor units can be connected to a single outdoor unit and simultaneously operated with a single remote control.
4way
Wall Mounted
Only used with outdoor units of Multi System
Micro Inverter
NEW
FDC125VNX FDC140VNX FDC100VNV FDC125VNV FDC140VNV FDC71VNX FDC100VNX FDC125VSX FDC140VSX FDC100VSV FDC125VSV FDC140VSV FDC200VSV FDC250VSV FDC100VSX 40 + 40 50 + 50 60 + 60 71 + 71 50 + 50 60 + 60 71 + 71 100 + 100 125 + 125 50 + 50 + 50 50 + 50 + 50 71 + 71 + 71 50+50+50+50 60+60+60+60
Diagrams below show the application as samples. For further information, refer to TECHNICAL MANUAL.
(Example)
Indoor unit
Outdoor unit
The branch piping (both gas and liquid lines) should always be arranged to have a level or perpendicular position.
2-Way Branch
Notes (1) When 40-60 models of indoor units are applied to this combination, the reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size from 9.52mm to 6.35mm at indoor unit side (are connection). Accordingly be sure to select the liquid piping size 9.52mm from branch to indoor unit. (2) The reducer 4 is for FDC71 and 100 models only.
Floor
Floor
Liquid pipe
ID9.52 180
Symbol
Reducer
6.35 flared nut 50 105 2 piece
Symbol
Reducer
OD15.88 80 ID12.7 10 2 piece
Symbol
3-Way Branch
8 ID9.52 210
ID9.52 8
ID15.88
Notes (1) Symbol 1 to 4 in the drawing shows the symbols of branch piping parts in the chart respectively. (2) Branch piping should always be arranged to have level or perpendicular position.
Floor
Floor
24
Ideal for the installation in large area and L-shaped rooms, the V Multi System has an extensive degree of flexibility in the selection of indoor units. Specifically, the selection of indoor units with different capacities in different types can be made.
V Multi System
Different models and capacities can be selected.
4way
Ceiling Suspended
NEW
FDC71VNX
FDC140VNX FDC140VSX FDC140VNV FDC140VSV 71 + 71 50 + 50 + 50 FDC200VSV 100 + 100 71 + 125 71 + 71 + 71 FDC250VSV 125 + 125 60 + 60 + 125 71 + 71 + 100
Micro Inverter
40 + 40
50 + 50
50+50+50+50 60+60+60+60
Triple type
[Branch pipe set : DIS-TA1]
The indoor_outdoor piping length differences among indoor units are less than 3m.
(Example)
Model FDC140VNV/VSV
Indoor unit
Model FDC140 Item Indoor unit combinations 50+50+50 Liquid pipe Main pipe Branch pipe 9.52X t0.8 9.52Xt 0.8 Gas pipe Main pipe Branch pipe 15.88Xt 1.0 12.7X t0.8
3 Gas line
Floor
Notes (1) The reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size from 9.52mm to 6.35mm at indoor unit side (are connection). Accordingly be sure to select the liquid piping size 9.52mm from branch to indoor unit.
Gas pipe
Symbol
ID12.7x3 100
Liquid pipe
10 0
Symbol
ID9.52x3
Reducer
Symbol
8 10 300 8 237
30
100
80 80
30
ID15.88
10
ID9.52
ID9.52 8 105 50
14
Floor
Notes (1) Symbol 1 to 3 in the drawing shows the symbols of branch piping parts in the chart respectively. (2) Branch piping should always be arranged to have level or perpendicular position.
25
FDT
CLASS
SPECIFICATIONS
Set model name
FDT 40/50/60/71/100/125VD
RC-E4
(Option)
RCH-E3
(Option)
RCN-T-36W-E
(Option)
Indoor name Outdoor name Power source 1Phase 220-240V 50Hz, 1Phase 220V 60Hz Nominal cooling capacity 7.1 10.0 kW ISO-T1(JIS) (3.2~8.0) (4.0~11.2) (Min~Max) Nominal heating capacity 8.0 11.2 kW ISO-T1(JIS) (3.6~9.0) (4.0~12.5) (Min~Max) Power Consumption Cooling/Heating kW 1.85/1.99 2.56/2.66 COP Cooling/Heating 3.84/4.02 3.91/4.21 Energy label Cooling/Heating A/A A/A Inrush current (Max. running current) A 5(24) 5(17) Hi:33 Me:31 Lo:30 Indoor*2 Sound Ievel*1 dB(A) Cooling:51 Heating:48 Cooling:48 Heating:50 Outdoor 2 Hi:18 Me:16 Lo:14 Indoor* Air flow CMM Cooling:60 Heating:50 Outdoor 100 Exterior dimensions Height x Width x Depth mm Unit:246x840x840 Panel:35x950x950 kg Unit+Panel Net weight 27.5(Unit:22 Panel:5.5) Panel T-PSA-3AW-E Air filter, Q'ty Pocket Plastic net x1 (Washable) Remote control(option) Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E Exterior dimensions Height x Width x Depth mm 750x880(+88)x340 1,300x970x370 Net weight kg 105 60 kg(m) Ref.amount precharged 4.5(30) 2.95(30) Ref.piping size Liquid/Gas 9.52/15.88 m Ref.piping length 100 50 m Vertical height O/U is higher 30 m difference O/U is lower 15 Operating O/U Cooling -15~43*3 temperature range Heating O/U -20~20
SPECIFICATIONS
Set model name
Indoor name Outdoor name Power source 1Phase 220-240V 50Hz, 1Phase 220V 60Hz 3Phase 380-415V 50Hz, 3Phase 380V 60Hz Nominal cooling capacity 14.0 12.5 14.0 10.0 12.5 14.0 14.0 kW ISO-T1(JIS) (5.0~16.0) (5.0~14.0) (5.0~16.0) (4.0~11.2) (5.0~14.0) (5.0~14.5) (5.0~14.5) (Min~Max) Nominal heating capacity 16.0 14.0 16.0 11.2 14.0 16.0 16.0 kW ISO-T1(JIS) (4.0~18.0) (4.0~17.0) (4.0~18.0) (4.0~16.0) (4.0~18.0) (4.0~20.0) (4.0~20.0) (Min~Max) Power Consumption Cooling/Heating kW 3.88/3.70 3.06/3.22 3.88/3.76 2.56/2.66 3.06/3.22 3.88/3.70 3.88/3.76 COP Cooling/Heating 3.61/4.32 4.08/4.35 3.61/4.26 3.91/4.21 4.08/4.35 3.61/4.32 3.61/4.26 Energy label Cooling/Heating A/A A/A A/A A/A A/A A/A A/A Inrush current (Max. running current) A 5(26) 5(15) 2 Hi:33 Me:31 Lo:30 Hi:35 Me:33 Lo:31 Hi:33 Me:31 Lo:30 Hi:33 Me:31 Lo:30 Hi:35 Me:33 Lo:31 Hi:33 Me:31 Lo:30 Indoor* Sound Ievel*1 dB(A) Cooling:48 Heating:50 Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52 Outdoor Hi:18 Me:16 Lo:14 Hi:21 Me:19 Lo:17 Hi:18 Me:16 Lo:14 Indoor*2 Hi:21 Me:19 Lo:17 Hi:18 Me:16 Lo:14 Hi:18 Me:16 Lo:14 Air flow CMM 100 Outdoor Exterior dimensions Height x Width x Depth mm Unit:246x840x840 Panel:35x950x950 kg Unit+Panel Net weight 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) Panel T-PSA-3AW-E Air filter, Q'ty Pocket Plastic net x1 (Washable) Remote control(option) Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E Exterior dimensions Height x Width x Depth mm 1,300x970x370 Net weight kg 105 kg(m) Ref.amount precharged 4.5(30) Ref.piping size Liquid/Gas 9.52/15.88 m Ref.piping length 100 m Vertical height O/U is higher 30 m difference O/U is lower 15 Operating O/U Cooling -15~43*3 temperature range Heating O/U -20~20
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 71/100VNXPVD 39dB, 100VSXPVD 39dB, 125/140VNXPVD 46dB, 125/140VSXPVD 46dB, 140VNXTVD 39dB, 140VSXTVD 39dB Air flow: 71/100VNXPVD 20CMM, 100VSXPVD 20CMM, 125/140VNXPVD 28CMM, 125/140VSXPVD 28CMM, 140VNXTVD 20CMM, 140VSXTVD 20CMM
26
Indoor unit
Indoor unit
SPECIFICATIONS
Set model name
Micro Inverter
FDT100VNPVD FDT125VNPVD FDT140VNPVD FDT140VNTVD FDT100VSPVD FDT125VSPVD FDT140VSPVD Twin Triple Twin Indoor name FDT50VD FDT50VD FDT60VD FDT71VD FDT71VD FDT50VD FDT60VD Outdoor name FDC140VN FDC125VS FDC140VS FDC100VS FDC140VN FDC100VN FDC125VN Power source 1Phase 220-240V 50Hz, 1Phase 220V 60Hz 3Phase 380-415V 50Hz, 3Phase 380V 60Hz Nominal cooling capacity 10.0 14.0 10.0 12.5 14.0 12.5 14.0 kW ISO-T1(JIS) (4.0~11.2) (5.0~14.5) (4.0~11.2) (5.0~14.0) (5.0~14.5) (5.0~14.0) (5.0~14.5) (Min~Max) Nominal heating capacity 11.2 16.0 11.2 14.0 16.0 14.0 16.0 kW ISO-T1(JIS) (4.0~12.5) (4.0~16.5) (4.0~12.5) (4.0~16.0) (4.0~16.5) (4.0~16.0) (4.0~16.5) (Min~Max) Power Consumption Cooling/Heating kW 2.94/3.09 4.65/4.63 2.94/3.09 3.95/3.70 4.51/4.58 3.95/3.70 4.51/4.58 COP Cooling/Heating 3.40/3.62 3.01/3.46 3.40/3.62 3.16/3.78 3.10/3.49 3.16/3.78 3.10/3.49 Energy label Cooling/Heating A/A B/B A/A B/A B/B B/A B/B 5(15) Inrush current (Max. running current) A 5(24) Hi:33 Hi:35 Hi:33 Hi:33 Hi:33 Hi:35 Hi:33 Indoor*2 *1 Sound Ievel dB(A) Me:31 Lo:30 Me:33 Lo:31 Me:31 Lo:30 Me:31 Lo:30 Me:31 Lo:30 Me:33 Lo:31 Me:31 Lo:30 49 Cooling:50 Heating:51 51 Outdoor Cooling:50 Heating:51 49 51 Hi:21 Hi:18 Hi:21 *2 Hi:18 Me:16 Lo:14 Hi:18 Me:16 Lo:14 Indoor Me:19 Lo:17 Me:16 Lo:14 Air flow CMM Me:19 Lo:17 Cooling:75 Heating:73 Outdoor Exterior dimensions Height x Width x Depth mm Unit:246x840x840 Panel:35x950x950 29.5(Unit:24 Panel:5.5) 29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5) kg 27.5(Unit:22 Panel:5.5) Net weight Unit+Panel Panel T-PSA-3AW-E Air filter, Q'ty Pocket Plastic net x1 (Washable) Remote control(option) Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E Exterior dimensions 845x970x370 Net weight kg 81 83 Ref.amount precharged kg(m) 3.8(30) Ref.piping size Liquid/Gas 9.52/15.88 m 50 Ref.piping length m 30 Vertical height O/U is higher O/U is lower m 15 difference Cooling Operating O/U -15~43*3 temperature range Heating O/U -20~20 Powerful-Hi can be selected. Sound level: 100VNPVD 39dB, 125/140VNPVD 46dB, 140VNTVD 39dB, 100VSPVD 39dB, 125/140VSPVD 46dB Air flow: 100VNPVD 20CMM, 125/140VNPVD 28CMM, 140VNTVD 20CMM, 100VSPVD 20CMM, 125/140VSPVD 28CMM
Indoor unit
SPECIFICATIONS
Set model name
Micro Inverter
FDT140VSTVD FDT200VSTVD FDT200VSDVD FDT250VSDVD Triple Double Twin Indoor name FDT50VD FDT71VD FDT50VD FDT60VD Outdoor name FDC140VS FDC200VS FDC200VS FDC250VS Power source 3Phase 380-415V 50Hz, 3Phase 380V 60Hz Nominal cooling capacity 25.0 14.0 20.0 20.0 25.0 20.0 kW ISO-T1(JIS) (10.0~28.0) (5.0~14.5) (7.0~22.4) (7.0~22.4) (10.0~28.0) (7.0~22.4) (Min~Max) Nominal heating capacity 28.0 16.0 22.4 22.4 28.0 22.4 kW ISO-T1(JIS) (9.5~31.5) (4.0~16.5) (7.6~25.0) (7.6~25.0) (9.5~31.5) (7.6~25.0) (Min~Max) Power Consumption Cooling/Heating kW 8.30/7.75 4.65/4.63 6.49/6.12 6.58/6.15 8.28/7.70 6.58/6.02 COP Cooling/Heating 3.01/3.61 3.01/3.46 3.08/3.66 3.04/3.64 3.02/3.64 3.04/3.72 Energy label Cooling/Heating B/A B/B B/A B/A B/A B/A Inrush current (Max. running current) A 5(22) 5(15) 5(19) 5(19) 5(22) 5(19) Hi:42 Hi:40 Hi:33 Hi:35 Hi:33 Hi:33 Indoor*2 Sound Ievel*1 Me:40 Lo:37 Me:37 Lo:35 Me:31 Lo:30 Me:33 Lo:31 dB(A) Me:31 Lo:30 Me:31 Lo:30 51 57 57 Cooling:57 Heating:58 Outdoor 57 Cooling:57 Heating:58 Hi:27 Hi:21 Hi:18 Hi:30 Hi:18 Indoor*2 Me:24 Lo:20 Me:19 Lo:17 Air flow CMM Me:16 Lo:14 Me:27 Lo:23 Me:16 Lo:14 Cooling:150 Heating:145 Cooling:75 Heating:73 Cooling:150 Heating:145 Cooling:150 Heating:145 Outdoor Exterior dimensions Height x Width x Depth mm Unit:298x840x840 Panel:35x950x950 Unit:246x840x840 Panel:35x950x950 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) kg Unit+Panel Net weight 32.5(Unit:27 Panel:5.5) Panel T-PSA-3AW-E Air filter, Q'ty Pocket Plastic net x1 (Washable) Remote control(option) Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E 1,505x970x370 1,300x970x370 1,505x970x370 Exterior dimensions Height x Width x Depth mm 1,300x970x370 845x970x370 kg 140 122 140 Net weight 122 83 kg(m) 7.2(30) 5.4(30) 7.2(30) Ref.amount precharged 5.4(30) 3.8(30) 12.7/22.22 9.52/22.22 12.7/22.22 Ref.piping size Liquid/Gas 9.52/22.22 9.52/15.88 Ref.piping length m 70 70 50 Vertical height O/U is higher m 30 O/U is lower difference m 15 O/U Cooling Operating -15~43*3 O/U temperature range Heating -15~20 -20~20 -15~20 The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. FDT250VSPVD FDT200VSPVD Twin FDT125VD FDT100VD FDC250VS FDC200VS Range of Outdoor unit usage Indoor unit Powerful-Hi can be selected. Sound level: 200/250VSPVD 51dB, 140VSTVD 39dB, 200VSTVD 46dB, 200VSDVD 39dB, 250VSDVD 46dB Air flow: 200/250VSPVD 37CMM, 140VSTVD 20CMM, 200VSTVD 28CMM, 200VSDVD 20CMM, 250VSDVD 28CMM
27
FDTC
CLASS
FDTC 40/50/60VD
RC-E4
(Option)
RCH-E3
(Option)
RCN-TC-24W-ER
(Option)
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) *1 Sound Ievel Air flow Indoor*2 Outdoor Indoor*2
kW kW kW A dB(A)
CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Unit+Panel Panel Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm Net weight kg kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference Operating O/U Cooling temperature range Heating O/U
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 71/100/125VNXPVD 47dB, 100/125VSXPVD 47dB, 140VNXTVD 47dB, 140VSXTVD 47dB Air flow: 71/100/125VNXPVD 13.5CMM, 100/125VSXPVD 13.5CMM, 140VNXTVD 13.5CMM, 140VSXTVD 13.5CMM
28
Indoor unit
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) Sound Ievel Air flow Indoor unit *1 Indoor*2 Outdoor Indoor*2
Micro Inverter
FDTC100VNPVD Twin FDTC50VD FDC100VN kW kW kW A dB(A) 10.0 (4.0~11.2) 11.2 (4.0~12.5) 2.84/3.08 3.52/3.64 A/A 5(24) Cooling : Hi:42 Me:36 Lo:30 Heating : Hi:42 Me:36 Lo:32 49 Cooling : Hi:11.5 Me:9 Lo:7 Heating : Hi:11.5 Me:9 Lo:8 FDTC60VD FDC125VN 1Phase 220-240V 50Hz, 1Phase 220V 60Hz 12.5 (5.0~14.0) 14.0 (4.0~16.0) 5.35/4.62 2.34/3.03 F/D 5(27) Cooling : Hi:46 Me:39 Lo:30 Heating : Hi:46 Me:39 Lo:32 Cooling:50 Heating:51 Cooling : Hi:13.5 Me:10 Lo:7 Heating : Hi:13.5 Me:10 Lo:8 Cooling:75 Heating:73 Unit:248x570x570 Panel:35x700x700 18.5(Unit:15 Panel:3.5) TC-PSA-25W-E Pocket Plastic net x1 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER 845x970x370 81 3.8(30) 9.52/15.88 50 30 15 -15~43*3 -20~20 FDTC125VNPVD FDTC140VNTVD Triple FDTC50VD FDC140VN 14.0 (5.0~14.5) 16.0 (4.0~16.5) 4.64/4.52 3.02/3.54 B/B 5(24) Cooling : Hi:42 Me:36 Lo:30 Heating : Hi:42 Me:36 Lo:32 51 Cooling : Hi:11.5 Me:9 Lo:7 Heating : Hi:11.5 Me:9 Lo:8
CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Unit+Panel Panel Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher O/U is lower m difference O/U Cooling Operating temperature range Heating O/U
Powerful-Hi can be selected. Sound level: 100/125VNPVD 47dB, 140VNTVD 47dB Air flow: 100/125VNPVD 13.5CMM, 140VNTVD 13.5CMM
SPECIFICATIONS
Set model name
Micro Inverter
FDTC140VSTVD FDTC200VSDVD FDTC250VSDVD Twin Triple Double Twin Indoor name FDTC60VD FDTC50VD FDTC50VD FDTC60VD FDTC50VD Outdoor name FDC125VS FDC140VS FDC200VS FDC250VS FDC100VS Power source 3Phase 380-415V 50Hz, 3Phase 380V 60Hz 20.0 25.0 14.0 Nominal cooling capacity 12.5 10.0 kW ISO-T1(JIS) (7.0~22.4) (10.0~28.0) (5.0~14.5) (5.0~14.0) (4.0~11.2) (Min~Max) 22.4 28.0 16.0 Nominal heating capacity 14.0 11.2 kW ISO-T1(JIS) (7.6~25.0) (9.5~31.5) (4.0~16.5) (4.0~16.0) (4.0~12.5) (Min~Max) 7.33/6.98 11.28/10.19 4.64/4.52 Power Consumption Cooling/Heating kW 5.35/4.62 2.84/3.08 2.73/3.21 2.22/2.75 3.02/3.54 COP Cooling/Heating 2.34/3.03 3.52/3.64 D/C F/E B/B Energy label Cooling/Heating F/D A/A 5(19) 5(22) 5(15) Inrush current (Max. running current) A 5(15) 5(15) Cooling : Hi:42 Me:36 Lo:30 Cooling : Hi:46 Me:39 Lo:30 Cooling : Hi:42 Me:36 Lo:30 Cooling : Hi:46 Me:39 Lo:30 *1 Indoor*2 Sound Ievel Heating : Hi:42 Me:36 Lo:32 Heating : Hi:46 Me:39 Lo:32 dB(A) Heating : Hi:42 Me:36 Lo:32 Heating : Hi:46 Me:39 Lo:32 Cooling:57 Heating:58 Cooling:50 Heating:51 Outdoor 51 57 49 Cooling : Hi:11.5 Me:9 Lo:7 Cooling : Hi:13.5 Me:10 Lo:7 Cooling : Hi:13.5 Me:10 Lo:7 Cooling : PHi:11.5 Me:9 Lo:7 Indoor*2 Air flow Heating : Hi:13.5 Me:10 Lo:8 Heating : Hi:11.5 Me:9 Lo:8 CMM Heating : Hi:11.5 Me:9 Lo:8 Heating : Hi:13.5 Me:10 Lo:8 Cooling:150 Heating:145 Cooling:75 Heating:73 Outdoor Unit:248x570x570 Panel:35x700x700 Exterior dimensions Height x Width x Depth mm 18.5(Unit:15 Panel:3.5) Unit+Panel kg Net weight TC-PSA-25W-E Panel Pocket Plastic net x1 (Washable) Air filter, Q'ty Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER Remote control(option) 1,505x970x370 1,300x970x370 845x970x370 Exterior dimensions Height x Width x Depth mm 140 122 83 kg Net weight 7.2(30) 5.4(30) 3.8(30) kg(m) Ref.amount precharged 9.52/22.22 12.7/22.22 9.52/15.88 Ref.piping size Liquid/Gas 50 Ref.piping length m 70 Vertical height O/U is higher 30 m 15 difference m O/U is lower Operating -15~43*3 O/U Cooling temperature range Heating -20~20 -15~20 O/U FDTC100VSPVD FDTC125VSPVD
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 100/125VSPVD 47dB, 140VSTVD 47dB, 200/250VSDVD 47dB Air flow: 100/125VSPVD 13.5CMM, 140VSTVD 13.5CMM, 200/250VSDVD 13.5CMM
Indoor unit
29
FDUM
external static pressure loss:5pa
CLASS
SPECIFICATIONS
Set model name
RC-E4
(Option)
RCH-E3
(Option)
RCN-KIT3-E
(Option)
Indoor name Outdoor name Power source Nominal cooling capacity kW ISO-T1(JIS) (Min~Max) Nominal heating capacity kW ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating kW COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) A Indoor*2 Sound Ievel*1 dB(A) Outdoor Indoor*2 Air flow CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm Net weight kg Ref.amount precharged kg(m) Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference Operating O/U Cooling temperature range Heating O/U
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP Cooling/Heating
kW kW kW
Energy label Cooling/Heating B/B B/B B/B A/A A/B B/B Inrush current (Max. running current) A 5(15) 5(26) Indoor*2 Hi:35 Me:32 Lo:29 Hi:34 Me:31 Lo:28 Hi:35 Me:32 Lo:29 Hi:34 Me:31 Lo:28 Sound Ievel*1 dB(A) Cooling:49 Heating:52 Cooling:49 Heating:52 Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52 Outdoor Indoor*2 Hi:20 Me:18 Lo:15 Hi:13 Me:12 Lo:11 Hi:13 Me:12 Lo:11 Hi:16 Me:15 Lo:14 Hi:20 Me:18 Lo:15 Hi:13 Me:12 Lo:11 Air flow CMM Outdoor 100 Exterior dimensions Height x Width x Depth mm 299x750x635 299x950x635 299x950x635 299x750x635 kg Net weight 34 40 40 34 Air filter, Q'ty Procure locally Remote control(option) Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E Exterior dimensions Height x Width x Depth mm 1,300x970x370 kg Net weight 105 kg(m) Ref.amount precharged 4.5(30) Ref.piping size Liquid/Gas 9.52/15.88 m 100 Ref.piping length m 30 Vertical height O/U is higher m O/U is lower 15 difference Operating O/U Cooling -15~43*3 temperature range Heating O/U -20~20
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 100VNXPVD 35dB, 100VSXPVD 35dB, 125/140VNXPVD 38dB, 125/140VSXPVD 38dB, 140VNXTVD 35dB, 140VSXTVD 35dB Air flow: 100VNXPVD 14CMM, 100VSXPVD 14CMM, 125/140VNXPVD 18CMM, 125/140VSXPVD 18CMM, 140VNXTVD 14CMM, 140VSXTVD 14CMM
30
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP Cooling/Heating
Micro Inverter
FDUM100VNPVD FDUM50VD FDC100VN 10.0 (4.0~11.2) 11.2 (4.0~12.5) 3.12/3.27 3.21/3.43 A/B Hi:34 Me:31 Lo:28 49 Hi:13 Me:12 Lo:11 299x750x635 34 FDUM125VNPVD Twin FDUM60VD FDC125VN 12.5 (5.0~14.0) 14.0 (4.0~16.0) 4.47/4.51 2.80/3.10 C/D 5(24) Hi:34 Me:31 Lo:28 Cooling:50 Heating:51 Hi:16 Me:15 Lo:14 Hi:35 Me:32 Lo:29 51 Hi:13 Me:12 Lo:11 34 Hi:34 Me:31 Lo:28 49 Hi:20 Me:18 Lo:15 Cooling:75 Heating:73 299x950x635 40 Procure locally Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E 845x970x370 81 3.8(30) 9.52/15.88 50 30 15 -15~43*3 -20~20 FDUM140VNPVD FDUM71VD FDC140VN 14.0 (5.0~14.5) 16.0 (4.0~16.5) 50Hz:5.00/4.94 60Hz:5.00/4.80 50Hz:2.80/3.24 60Hz:2.80/3.33 C/C FDUM140VNTVD Triple FDUM50VD FDC140VN 14.0 (5.0~14.5) 16.0 (4.0~16.5) 50Hz:5.09/5.03 60Hz:5.09/4.89 50Hz:2.75/3.18 60Hz:2.75/3.27 50Hz:D/D 60Hz:D/C FDUM100VSPVD Twin FDUM50VD FDC100VS 3Phase 380-415V 50Hz, 3Phase 380V 60Hz 10.0 (4.0~11.2) 11.2 (4.0~12.5) 3.12/3.27 3.21/3.43 A/B 5(15)
Energy label Cooling/Heating Inrush current (Max. running current) A Indoor*2 Sound Ievel*1 dB(A) Outdoor Indoor*2 Air flow CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight kg(m) Ref.amount precharged Ref.piping size Liquid/Gas Ref.piping length m Vertical height O/U is higher m difference m O/U is lower Operating O/U Cooling temperature range Heating O/U
299x750x635
83
Powerful-Hi can be selected. Sound level: 100VNPVD 35dB, 125VNPVD 38dB, 140VNPVD 38dB, 140VNTVD 35dB, 100VSPVD 35dB Air flow: 100VNPVD 14CMM, 125VNPVD 18CMM, 140VNPVD 23CMM, 140VNTVD 14CMM, 100VSPVD 14CMM
SPECIFICATIONS
Set model name
Micro Inverter
FDUM140VSPVD FDUM200VSPVD FDUM250VSPVD FDUM140VSTVD FDUM200VSTVD Triple Twin Indoor name FDUM125VD FDUM50VD FDUM71VD FDUM60VD FDUM71VD FDUM100VD Outdoor name FDC250VS FDC140VS FDC200VS FDC125VS FDC140VS FDC200VS Power source 3Phase 380-415V 50Hz, 3Phase 380V 60Hz Nominal cooling capacity 14.0 25.0 20.0 14.0 20.0 12.5 ISO-T1(JIS) kW (5.0~14.5) (10.0~28.0) (7.0~22.4) (5.0~14.5) (7.0~22.4) (5.0~14.0) (Min~Max) Nominal heating capacity 16.0 28.0 22.4 16.0 22.4 14.0 ISO-T1(JIS) kW (4.0~16.5) (9.5~31.5) (7.6~25.0) (4.0~16.5) (7.6~25.0) (4.0~16.0) (Min~Max) 50Hz:5.09/5.03 50Hz:5.00/4.94 Power Consumption Cooling/Heating kW 6.86/6.72 9.31/8.35 6.88/6.74 4.47/4.51 60Hz:5.09/4.89 60Hz:5.00/4.80 50Hz:2.75/3.18 50Hz:2.80/3.24 COP Cooling/Heating 2.92/3.33 2.69/3.35 2.91/3.32 2.80/3.10 60Hz:2.75/3.27 60Hz:2.80/3.33 Energy label Cooling/Heating C/C D/C C/C 50Hz:D/D 60Hz:D/C C/C C/D Inrush current (Max. running current) 5(15) A 5(22) 5(19) 5(19) 5(15) Indoor*2 Hi:34 Me:31 Lo:28 Hi:35 Me:32 Lo:29 Hi:37 Me:35 Lo:32 Hi:38 Me:36 Lo:33 Hi:34 Me:31 Lo:28 Hi:35 Me:32 Lo:29 Sound Ievel*1 dB(A) Cooling:50 Heating:51 Outdoor 57 57 51 Cooling:57 Heating:58 51 Indoor*2 Hi:16 Me:15 Lo:14 Hi:20 Me:18 Lo:15 Hi:13 Me:12 Lo:11 Hi:20 Me:18 Lo:15 Hi:28 Me:25 Lo:22 Air flow CMM Cooling:75 Heating:73 Cooling:150 Heating:145 Cooling:150 Heating:145 Cooling:75 Heating:73 Outdoor 350x1,370x635 299x950x635 Exterior dimensions Height x Width x Depth mm 299x750x635 1,300x970x370 59 40 kg Net weight 34 122 Air filter, Q'ty Procure locally Remote control(option) Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E Exterior dimensions Height x Width x Depth mm 1,505x970x370 1,300x970x370 1,300x970x370 845x970x370 845x970x370 kg Net weight 140 122 122 83 83 kg(m) Ref.amount precharged 7.2(30) 5.4(30) 5.4(30) 3.8(30) 3.8(30) Ref.piping size Liquid/Gas 12.7/22.22 9.52/22.22 9.52/22.22 9.52/15.88 9.52/15.88 m 70 70 50 Ref.piping length 50 m Vertical height O/U is higher 30 m O/U is lower difference 15 Operating O/U Cooling -15~43*3 temperature range Heating -20~20 -20~20 -15~20 -15~20 O/U FDUM125VSPVD
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of indoor units is 60Pa. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 125/140VSPVD 38dB, 200/250VSPVD 41dB, 140VSTVD 35dB, 200VSTVD 38dB Air flow: 125VSPVD 18CMM, 140VSPVD 23CMM, 200/250VSPVD 34CMM, 140VSTVD 14CMM, 200VSTVD 23CMM
31
FDEN
FDEN 40/50/60/71/100/125VD
CLASS
SPECIFICATIONS
Set model name
RC-E4
(Option)
RCH-E3
(Option)
RCN-E1R
(Option)
Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) kW (Min~Max) Nominal heating capacity ISO-T1(JIS) kW (Min~Max) Power Consumption Cooling/Heating kW COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) A Indoor*2 Sound Ievel*1 dB(A) Outdoor Indoor*2 Air flow CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m difference O/U is lower Operating O/U Cooling temperature range Heating O/U
SPECIFICATIONS
Set model name
FDEN125VNXPVD FDEN140VNXPVD FDEN140VNXTVD FDEN100VSXPVD FDEN125VSXPVD FDEN140VSXPVD FDEN140VSXTVD Twin Triple Twin Triple Indoor name FDEN71VD FDEN50VD FDEN50VD FDEN60VD FDEN71VD FDEN50VD FDEN60VD Outdoor name FDC140VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX FDC140VSX FDC125VNX Power source 3Phase 380-415V 50Hz, 3Phase 380V 60Hz 1Phase 220-240V 50Hz, 1Phase 220V 60Hz Nominal cooling capacity 12.5 14.0 14.0 10.0 12.5 14.0 14.0 ISO-T1(JIS) kW (5.0~14.0) (5.0~16.0) (5.0~16.0) (4.0~11.2) (5.0~14.0) (5.0~16.0) (5.0~16.0) (Min~Max) Nominal heating capacity 14.0 16.0 16.0 11.2 14.0 16.0 16.0 ISO-T1(JIS) kW (4.0~17.0) (4.0~18.0) (4.0~18.0) (4.0~16.0) (4.0~18.0) (4.0~20.0) (4.0~20.0) (Min~Max) Power Consumption Cooling/Heating kW 3.86/3.70 4.78/4.43 4.72/4.38 3.02/3.18 3.86/3.70 4.78/4.43 4.72/4.38 COP Cooling/Heating 3.24/3.78 2.93/3.61 2.97/3.65 3.31/3.52 3.24/3.78 2.93/3.61 2.97/3.65 Energy label Cooling/Heating A/A C/A C/A A/B A/A C/A C/A Inrush current (Max. running current) 5(26) A 5(15) 2 Indoor* Hi:39 Me:38 Lo:37 Hi:39 Me:38 Lo:37 Hi:41 Me:39 Lo:38 Hi:41 Me:39 Lo:38 Sound Ievel*1 dB(A) Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52 Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52 49 Outdoor Indoor*2 Hi:18 Me:14 Lo:12 Hi:11 Me:9 Lo:7 Hi:18 Me:14 Lo:12 Hi:11 Me:9 Lo:7 Air flow CMM 100 Outdoor Exterior dimensions Height x Width x Depth mm 210x1,070x690 210x1,070x690 210x1,320x690 210x1,320x690 kg Net weight 28 28 37 37 Pocket Plastic net x2 (Washable) Air filter, Q'ty Wired:RC-E4, RCH-E3 Wireless:RCN-E1R Remote control(option) 1,300x970x370 Exterior dimensions Height x Width x Depth mm 105 kg Net weight 4.5(30) kg(m) Ref.amount precharged 9.52/15.88 Ref.piping size Liquid/Gas 100 m Ref.piping length 30 m Vertical height O/U is higher 15 m difference O/U is lower Operating -15~43*3 O/U Cooling temperature range Heating -20~20 O/U
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 71/100VNXPVD 46dB, 100VSXPVD 46dB, 125/140VNXPVD 50dB, 125/140VSXPVD 50dB, 140VNXTVD 46dB, 140VSXTVD 46dB Air flow: 71/100VNXPVD 13CMM, 100VSXPVD 13CMM, 125/140VNXPVD 22CMM, 125/140VSXPVD 22CMM, 140VNXTVD 13CMM, 140VSXTVD 13CMM
32
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) Sound Ievel Air flow *1 Indoor*2 Outdoor Indoor*2
Micro Inverter
FDEN100VNPVD FDEN50VD FDC100VN kW kW kW A dB(A) 10.0 (4.0~11.2) 11.2 (4.0~12.5) 3.12/3.28 3.21/3.41 A/B FDEN140VNTVD FDEN125VNPVD FDEN140VNPVD Twin Triple FDEN50VD FDEN71VD FDEN60VD FDC140VN FDC140VN FDC125VN 1Phase 220-240V 50Hz, 1Phase 220V 60Hz 14.0 12.5 14.0 (5.0~14.5) (5.0~14.0) (5.0~14.5) 16.0 14.0 16.0 (4.0~16.5) (4.0~16.0) (4.0~16.5) 4.88/4.58 4.23/3.83 4.87/4.59 2.87/3.49 2.96/3.66 2.87/3.49 C/B C/A C/B 5(24) Hi:41 Me:39 Lo:38 Cooling:50 Heating:51 Hi:18 Me:14 Lo:12 51 FDEN100VSPVD Twin FDEN125VSPVD FDEN50VD FDEN60VD FDC100VS FDC125VS 3Phase 380-415V 50Hz, 3Phase 380V 60Hz 10.0 12.5 (4.0~11.2) (5.0~14.0) 11.2 14.0 (4.0~12.5) (4.0~16.0) 3.12/3.28 4.23/3.83 3.21/3.41 2.96/3.66 A/B C/A 5(15) Hi:41 Hi:39 Me:38 Lo:37 Me:39 Lo:38 49 Cooling:50 Heating:51 Hi:18 Hi:11 Me:9 Lo:7 Me:14 Lo:12 210x1,320x690 37
CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher O/U is lower m difference Cooling O/U Operating temperature range Heating O/U
Cooling:75 Heating:73 210x1,070x690 210x1,320x690 28 37 Pocket Plastic net x2 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-E1R 845x970x370 81 3.8(30) 9.52/15.88 50 30 15 -15~43*3 -20~20
83
Powerful-Hi can be selected. Sound level: 100VNPVD 46dB, 125/140VNPVD 50dB, 140VNTVD 46dB, 100VSPVD 46dB, 125VSPVD 50dB Air flow: 100VNPVD 13CMM, 125/140VNPVD 22CMM, 140VNTVD 13CMM, 100VSPVD 13CMM, 125VSPVD 22CMM
SPECIFICATIONS
Set model name Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) (Min~Max) Nominal heating capacity ISO-T1(JIS) (Min~Max) Power Consumption Cooling/Heating COP Cooling/Heating Energy label Cooling/Heating Inrush current (Max. running current) Sound Ievel Air flow *1 Indoor*2 Outdoor Indoor*2
Micro Inverter
FDEN140VSPVD FDEN200VSPVD FDEN250VSPVD FDEN140VSTVD FDEN200VSTVD FDEN200VSDVD FDEN250VSDVD Triple Twin Double Twin FDEN125VD FDEN50VD FDEN71VD FDEN50VD FDEN60VD FDEN100VD FDEN71VD FDC250VS FDC140VS FDC200VS FDC200VS FDC250VS FDC200VS FDC140VS 3Phase 380-415V 50Hz, 3Phase 380V 60Hz 25.0 25.0 14.0 20.0 20.0 14.0 20.0 (10.0~28.0) (10.0~28.0) (5.0~14.5) (7.0~22.4) (7.0~22.4) (5.0~14.5) (7.0~22.4) 28.0 28.0 16.0 22.4 22.4 16.0 22.4 (9.5~31.5) (9.5~31.5) (7.6~25.0) (4.0~16.5) (7.6~25.0) (4.0~16.5) (7.6~25.0) 9.01/8.05 9.50/8.69 4.87/4.59 6.47/5.97 4.88/4.58 6.40/5.90 7.43/7.26 2.77/3.48 2.63/3.22 3.09/3.75 2.87/3.49 2.87/3.49 3.13/3.80 2.69/3.09 D/B D/C C/B B/A C/B B/A D/D 5(19) 5(22) 5(22) 5(15) 5(19) 5(15) Hi:46 Hi:41 Hi:41 Hi:44 Hi:39 Hi:41 Hi:39 Me:44 Lo:43 Me:39 Lo:38 Me:39 Lo:38 Me:41 Lo:39 Me:38 Lo:37 Me:39 Lo:38 Me:38 Lo:37 57 51 57 51 Cooling:57 Heating:58 Cooling:57 Heating:58 Hi:18 Hi:26 Hi:11 Hi:29 Hi:18 Hi:18 Hi:11 Me:14 Lo:12 Me:23 Lo:21 Me:9 Lo:7 Me:26 Lo:23 Me:14 Lo:12 Me:14 Lo:12 Me:9 Lo:7 Cooling:75 Heating:73 Cooling:75 Heating:73 Cooling:150 Heating:145 Cooling:150 Heating:145 210x1,320x690 210x1,070x690 210x1,320x690 210x1,070x690 210x1,320x690 250x1,620x690 37 28 37 49 37 28 Pocket Plastic net x2 (Washable) Wired:RC-E4, RCH-E3 Wireless:RCN-E1R 1,300x970x370 845x970x370 1,300x970x370 1,505x970x370 845x970x370 1,505x970x370 122 83 140 140 122 83 5.4(30) 3.8(30) 7.2(30) 7.2(30) 5.4(30) 3.8(30) 9.52/22.22 9.52/15.88 12.7/22.2 12.7/22.22 9.52/22.22 9.52/15.88 50 70 70 50 30 15 -15~43*3 -20~20 -15~20 -20~20 -15~20
kW kW kW A dB(A)
CMM Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m difference O/U is lower O/U Cooling Operating O/U temperature range Heating
The data are measured under the following conditions(ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down. Powerful-Hi can be selected. Sound level: 140VSPVD 50dB, 200VSPVD 46dB, 250VSPVD 50dB, 140VSTVD 46dB, 200VSTVD 50dB, 200VSDVD 46dB, 250VSDVD 50dB Air flow: 140VSPVD 22CMM, 200VSPVD 28CMM, 250VSPVD 32CMM, 140VSTVD 13CMM, 200VSTVD 22CMM, 200VSDVD 13CMM, 250VSDVD 22CMM
33
SRK
CLASS
SRK 50/60ZJX-S
RC-E4
(Option)
RCH-E3
(Option)
Point
We used the same aerodynamic analysis technology as used in developing jet engines.
CFD (computational fluid dynamics), used in blade shape design of jet engines, has been applied to the design of air channels in air conditioners to develop the ideal air channel system (air circulation). The airflow of the jets created in this system enable a large volume of air to be blown with minimum power consumption, yet the air flow is uniform, quiet and reaches points a long distance from the blower.
SC-BIKN-E SC-BIKN-E
RC-E4
Point
Powerful airflow is realized by Jet technology. Good for large living rooms and shops. Increase your comfort.
SRK50/60ZJX-S
(in cooling operation)
890
220
3 (right, left)61.5
309 3.1
Terminal block
122.1
34
SPECIFICATIONS
Set model name
Twin
Triple
Twin
Triple
Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) kW (Min~Max) Nominal heating capacity ISO-T1(JIS) kW (Min~Max) kW Power Consumption Cooling/Heating Cooling/Heating COP Cooling/Heating Energy label A Inrush current (Max. running current) Cooling Indoor*2 1 Heating dB(A) Sound Ievel* Outdoor Cooling Indoor*2 Heating CMM Air flow Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight kg(m) Ref.amount precharged Ref.piping size Liquid/Gas m Ref.piping length m Vertical height O/U is higher m O/U is lower difference Cooling O/U Operating temperature range Heating O/U
SRK60ZJX-S SRK50ZJX-S SRK50ZJX-S SRK50ZJX-S SRK60ZJX-S SRK50ZJX-S FDC125VNX FDC100VSX FDC100VNX FDC140VNX FDC125VSX FDC140VSX 1Phase 220-240 50Hz, 1Phase 220V 60Hz 3Phase 380-415 50Hz, 3Phase 380V 60Hz 12.5 10.0 10.0 14.0 12.5 14.0 (5.0~14.0) (4.0~11.2) (4.0~11.2) (5.0~16.0) (5.0~14.0) (5.0~16.0) 14.0 11.2 11.2 16.0 14.0 16.0 (4.0~17.0) (4.0~16.0) (4.0~12.5) (4.0~18.0) (4.0~18.0) (4.0~20.0) 3.60/3.48 2.66/2.60 2.66/2.60 3.98/3.68 3.60/3.48 3.98/3.68 3.47/4.02 3.76/4.31 3.76/4.31 3.52/4.35 3.47/4.02 3.52/4.35 A/A A/A A/A A/A A/A A/A 5 (24) 5 (15) Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32 Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32 Cooling:48 Heating:50 Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52 Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8 Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8 Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5 Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5 100 309x890x220 15 Polypropylene net x2 (Washable) Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E 1,300x970x370 105 4.5(30) 9.52/15.88 100 30 15 -15~43*3 -20~20
SPECIFICATIONS
Set model name
Micro Inverter
SRK100VNPZJX SRK125VNPZJX SRK140VNTZJX SRK100VSPZJX SRK125VSPZJX SRK140VSTZJX
Twin
Triple
Twin
Triple
Indoor name Outdoor name Power source Nominal cooling capacity ISO-T1(JIS) kW (Min~Max) Nominal heating capacity ISO-T1(JIS) kW (Min~Max) Cooling/Heating kW Power Consumption Cooling/Heating COP Cooling/Heating Energy label A Inrush current (Max. running current) Cooling Indoor*2 Heating dB(A) Sound Ievel*1 Outdoor Cooling Indoor*2 Heating CMM Air flow Outdoor Exterior dimensions Height x Width x Depth mm kg Net weight Air filter, Q'ty Remote control(option) Exterior dimensions Height x Width x Depth mm kg Net weight kg(m) Ref.amount precharged Ref.piping size Liquid/Gas Ref.piping length m Vertical height O/U is higher m difference O/U is lower m Cooling O/U Operating temperature range Heating O/U
SRK50ZJX-S SRK50ZJX-S SRK60ZJX-S SRK60ZJX-S SRK50ZJX-S SRK50ZJX-S FDC100VS FDC140VN FDC125VN FDC125VS FDC140VS FDC100VN 3Phase 380-415 50Hz, 3Phase 380V 60Hz 1Phase 220-240 50Hz, 1Phase 220V 60Hz 10.0 14.0 12.5 12.5 14.0 10.0 (4.0~11.2) (5.0~14.5) (5.0~14.0) (5.0~14.0) (5.0~14.5) (4.0~11.2) 11.2 16.0 14.0 14.0 16.0 11.2 (4.0~12.5) (4.0~16.5) (4.0~16.0) (4.0~16.0) (4.0~16.5) (4.0~12.5) 2.72/2.86 4.53/4.05 4.25/4.29 4.25/4.29 4.53/4.05 2.72/2.86 3.62/3.92 3.09/3.95 2.94/3.26 2.94/3.26 3.09/3.95 3.62/3.92 A/A B/A C/C C/C B/A A/A 5 (24) 5 (15) Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32 Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32 51 51 Cooling:50,Heating:51 Cooling:50,Heating:51 49 49 Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8 Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8 Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5 Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5 Cooling:75,Heating:73 309x890x220 15 Polypropylene net x2 (Washable) Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E 845x970x370 81 83 3.8(30) 9.52/15.88 50 30 15 -15~43*3 -20~20
The data are measured under the following conditions (ISO-T1). Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 1 Indicates the value in *2 :: The values are for onean anechoic chamber. During operation these values are somewhat higher due to ambient conditions. *3 : If a cooling operation isindoor unit operation. outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural conducted when the * wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
35
Micro Inverter
Installation workability
Enhanced installation workability thanks to the extended pipe length longest level in the industry and pre-charged refrigerant.
Point
Micro Inverter
Height difference
(Outdoor higher than Indoor)
Height difference
(Outdoor higher than Indoor)
Piping length
Piping length 30m 50m 100m Height difference 20m 30m 30m
Piping length
HP 1.5~2.5 3 4~6
HP 4~6 8.10
Point
Refrigerant precharged piping length extends up to 30m. (1.5~2.5HP:15m) This eliminates the need to add refrigerant on site, which sets it free from trouble of excessive or insufficient charging of refrigerant, and allows carrying out the installation smoothly.
36
The RC-E4 controller enables extensive access to service and maintenance technical data combined with easy to use functions and a clear LCD display.
Timer operation
Up to 16 units
It can control up to 16 units individually, with pressing the AIR CON No. button.
AUTO restart
This function allows starting the air conditioner automatically when power supply is restored after power failure or by turning on the power switch.
Thermistor (option)
SC-THB-E3
In case sensor in the indoor units or the remote control sensor can not sense the room temperature correctly, or individual remote control in each room is not required but only censor is required (as when center control system is in place), install SC-THB-E3 at proper place in the rooms.
RCN-T-36W-E, RCN-TC-24W-ER
RCN-KIT3-E
RCN-E1R
When wireless remote control is used, the fan has 3 speed settings (Hi-Me-Lo) only.
37
Control System
KX6 series
SC-BIKN-E
SC-ADNA-E
SC-SL2NA-E
SC-ADNA-E
SC-ADNA-E
Central Control
SC-SL1N-E
SC-SL2NA-E
SC-SL3N-AE/BE
Start/stop control of up to 16 indoor units is possible either individually or collectively. With simple operations, you can effect centralized control.
Centralized control of up to 64 indoor units. It can allow connection with a weekly timer without using any interface.
Easy operation realized with a large color LCD and touch panel. Up to 128 indoor units can be controlled, when three SUPERLINK-2 systems are connected.
SC-WGWNA-A/B
(SC-WGWNA-B is with electric power calculation function)
SC-BGWN-A/B
(SC-WGWN-B is with electric power calculation function)
(BACnet gateway)
(LonWorks gateway)
SC-LGWN-A
Up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) are controlled from the Internet Explorer.
Additional engineering service cost etc. is required. Please consult your dealer when using this central control.
Up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) are controlled centrally from a BMS.
Additional engineering service cost etc. is required. In case of SC-BGWN-B, communication test by qualified person regarding electric cost calculation function is required before commissioning. Please consult your dealer when using this gateway.
Up to 96 indoor units (48 indoor unit x 2) are linked as an open network! Centrally controlled through LonWorks!
Additional engineering service cost etc. is required. Please consult your dealer when using this gateway.
38
(1) Functions
(a) Transmits the settings from the network option to the indoor units. (b) Returns the priority indoor unit data in response to a data request from the network option. (c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option. (d) A maximum of 16 units can be controlled (if in the same operation mode).
SL E board
A B X Y
A B X Y
Run Abnormal
ON
OFF SW3
Master/Sub address
Basic Connections
Outdoor unit Internal/external Crossing Indoor unit X Y SL E Board X Y A B Network A B options Remote control X Y
100
90
2-6
70
LED2
LED3
SW1 SW2
Connected to the remote controller terminals (no polarity) (the length should be 600 m or shorter) 200 m or shorter 300 m or shorter 400 m or shorter 600 m or shorter 0.5 mm2 x 2 cores 0.75 mm2 x 2 cores 1.25 mm2 x 2 cores 2.0 mm2 x 2 cores
Transmit the information of plural Master units to the network. Transmit the abnormalities of the Slave units to the network. Setting the plural Master/Slave units with the dip SW of the printed circuit board. Setting the Master/Slave remote controls with the dip SW of the remote control board.
Wireless Kit
Outdoor unit Internal/external Crossing Inside Inside
SL E Board
Set the SL E board dip SW to Master SW3-1 ON. The network option SLA-1E, SL1N-E is not allowed (This will disturb switching of the operation mode)
Wireless Kit
39
Mark A B C D E F
Item Service valve connection of the attached connecting pipe(gas 15.88(5/8")(Flare) side) Service valve connection(liquid side) 9.52(3/8")(Flare) Pipe/cable draw-out hole 20x3places Drain discharge hole M10x4places Anchor bolt hole 30x2places(front) 45(side) Cable draw-out hole 50(back)
Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave 1m or more space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The model name label is attached on the lower right corner of the front panel. (7) Connect the Service valve with local pipe by using the pipe of the attachment. (Gas side only)
Terminal block
B A
1300
35
612
624
85
170
85
50
50
C
970
10
50
15
50
55
155
52 27 50
160
70
50 15 50
190 20 40 60 60
580
15
200 60
15
L2
Intake
L3
Intake
L4
38
L1
Service space Outlet
L1 L2 L3 L4
410
370
55
20
40
262
388
103
Terminal block
148.4
33.5
L2
640 Check joint
Intake
L3
L4
Service space
B
40
Intake outlet
42.5
L1
40
12.4
93
D
43.5 327.3
Examples of installation
24.3
50.6 12
Dimensions
L1 L2 L3 L4
312.5
351.6
290
89
510 800
201
E
71.2
14.8
327.3
17.9
Mark A B D E
Item Refrigerant gas side pipe connection tap Refrigerant liquid side pipe connection tap Drain discharge port Anchor bolt hole
83.5
Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave a 1m or larger space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The unit name plate is attached on the lower right corner of the front panel.
40
FDC71VNX (unit:mm)
Mark A B C D E
Item Service valve connection (gas side) Service valve connection (liquid side) Pipe/cable draw-out hole Drain discharge hole Anchor bolt hole
223
2. R7 5
310
60 15
Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more the 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave 1m or more space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The model name label is attached on the lower right corner of the front.
47.5
L3
L2
340 380 418
Intake
L4
Service space
Intake
61
L1
61 150
D
580 880 150 88
27 32
19
outlet
Terminal block
C
750
B
30
48.5
30
Examples of installation
24
Dimensions
103.5
A
165.5 25
L1 L2 L3 L4
40
36
100
Terminal block
B A
845
51
A
F
195 110
110
195
242
279
150 52 27 50
10
50
50
55
50
70
C
970
40
50
15
15
50
VIEW A
E
190 60 40 20 60 580 200 60 15
L2
Intake
15
L3
Intake
Examples of installation
410
370
55
103
L4 L1
outlet Service space
Dimensions
38
L1 L2 L3 L4
C
20 40 262 388
41
FDC250VS (unit:mm)
42
MEMO
43
Refrigerant leakage
The refrigerant (R410A) used for Air conditioner is non-toxic and inflammable in its original state. However, in consideration of a state where the refrigerant leaks into the room, measures against refrigerant leaks must be taken in small rooms where the tolerable level could be exceeded. Take measures by installing ventilation devices, etc.
Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air intake port or enter and freeze in the outdoor unit.
Snow piling
In areas with heavy snow fall, the piled snow could block the air intake port. In this case, a frame that is 50cm or higher than the estimated snow fall must be installed underneath the outdoor unit.
Safety Precautions
Air-conditioner usage target
The air-conditioner described in this catalog is a dedicated cooling/heating device for human use. Do not use it for special applications such as the storage of foodstuffs, animals or plants, precision devices or valuable art, etc. This could cause the quality of the items to drop, etc. Do not use this for cooling vehicles or ships. Water leakage or current leaks could occur.
Installation
Always commission the installation to a dealer or specialist. Improper installation will lead to water leakage, electric shocks and fires. Make sure that the outdoor unit is stable in installation. Fix the unit to stable base.
Usage place
Do not install in places where combustible gas could leak or where there are sparks. Installation in a place where combustible gas could be generated, flow or accumulate, or places containing carbon fibers could lead to fires.
Before use
Mitsubishi Heavy Industries Ltd 16-5 2-Chome Kounan Minato-ku Tokyo 108-8215, Japan www.mhi.co.jp Our factories are ISO9001 and ISO14001 certified.
Certified ISO 9001 Certified ISO 14001
Certificate 04104 1998 0813 E5 BIWAJIMA PLANT MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO., LTD.
Certificate Number : 04100 1998 0813
Mitsubishi Heavy Industries, Ltd. Air-conditioning & Refrigeration Systems Headquarters Certificate number : JQA-0709
Mitsubishi Heavy Industries, Ltd. Air-conditioning & Refrigeration Systems Headquarters Certificate number : JQA-EM0256
BIWAJIMA PLANT
HB91-10P01E-A-0
February 2010(3B)R
Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.
Printed in Japan