APPLIED FOR VERY SHORT LINE CONNECTED WITH GRID VERY IMPORTANT LINE NOT TO BE AFFECTED BY PSB INTERTRIPPING WITHOUT ANY EXTERNAL EQUIPT,PLCC DIST PROTECTION NOT HAVING LOWEST SETTING HIGH STABILITY FOR PARALLEL FEEDERS
SEPARATE ONE PAIR OF PILOT WIRES USED TO TRANSMIT THE INFORMATION BETWEEN TWO
RELAYS
EACH RELAY ABLE TO COMPARE THE CURRENT FLOWING AT ITS RESPECTIVE END WITH CURRENT AT OTHER END
FOR A FAULT WITHIN THE PROTECTED FEEDER BOTH ENDS WILL TRIP NO TRIP FOR EXTERNAL FAULT THREE PHASE TRIP STABLE FOR PROPELY CONNECTED CTS&PILOT
SEPARATE PILOTWIRES FOR EACH FEEDERS PILOTS & RELAYS SHOULD WITHSTAND HV SURGES PILOT WIRES SHOULD BE MONITERED
MBCI FAULT AN BN CN AB BC C SETTING N=3 0.19KsIn 0.25KsIn 0.33KsIn 0.80KsIn 1.00KsIn 0.44KsIn SETTING N=6 0.12KsIn 0.14KsIn 0.17KsIn 0.80KsIn 1.00KsIn 0.44KsIn
ABC
0.5KsIn
0.5KsIn
INDIVIDUAL RELAY TESTING FOR PICK UP INDIVIDUAL RELAY PICKUP FROM OTHER END PILOT CONNECTION CONFORMING PILOT OPEN,PILOT SHORT,PILOT
REVERSE
1.POLARITY REVERSE
2.PHASES INTERPOSED
3.CT RATIO
4.PILOT REVERSE