THE INSPECTION AND TESTING

IS VERY IMPORTANT FUNCTION


IN MATERIAL PROCUREMENT
DEPARTMENT

INSPECTION AND TESTING

Following are few points for quality inspection
Technical specification
All clauses are properly understood.
Relevant IS Specification
Verification of offered quantity
Packing and marking as per specification
Sampling
Marking on sample
Calibration of meter and machine

Following are few points for quality inspection
Testing in our presence
Test report
Calculation
Sealing



Acceptance Test of Transformer
The establishment and maintenance of a high
standard of both material and workmanship can be
only be achieved by continuous inspection during the
manufacturing stages and by subsequent testing of a
finished product.
In accordance with Indian standard 2026 the
transformer are subjected the following tests in order
to ensure their being electrically and mechanically
sound in every respect and also to make certain that
they meet the guaranteed performance

The test prescribes are as under
Ratio and polarity 1 no out of lot
Load losses and Impedance all transformer
Insulation resistance 1 no out of lot
Resistance of winding 1 no out of lot
No load losses No load current all transformer
Voltage test all transformer
a) Separate source all transformer
b) Induced over voltage all transformer.
Temperature rise test 1 no out of 100.
Impulse voltage test Type test.
Dynamic short circuit test. Type test.
Noise level test. Type test.


RATIO AND POLARITY TEST
The ratio and polarity tests are carried out on every
transformer to ensure that the turn ratio of windings
is correct and the tolerance as per IS standard is plus
minus .5 % of the declared no load ratio. This test is
initially carried out on the core and windings before
assembly in the tank. The ratio is again checked
when the transformer is in its tank and finally when
job is finished completely.
RATIO AND POLARITY TEST
The ratio meter itself is a single phase, double wound
transformer, having a constant primary winding and a
variable secondary winding. In carrying out the test, the
H.V winding of transformer being tested is connected in
opposition to the primary winding of the ratio meter,
while the L.V winding of the transformer is connected to
the terminals of the dial switches though ammeter. A
single phase voltage not exceeding 2000v is applied
across the primary winding of ratio meter, and the two
dial switches are adjusted until the ammeter reading
registered zero. A zero reading of ammeter is possible
only the polarity of transformer is true otherwise there
will be not possible to have zero reading.
Load loss test and impedance test.
These two tests are carried out simultaneously.
The test is necessary to know that losses and impedance are
within tolerance of guaranteed value at specified
temperature i.e 75 degree centigrade.
The test is performed by L.V winding shorted by shunt
applying rated current in H.V winding
Care shall be taken while these test is carried out. Such as
Preferred three wattmeter method.
Correctly measured voltmeter reading , this will be calculate
percentage impedance at 75 d centigrade. the peak short
circuit current is determine from percentage X/R ratio.
Thus importance of voltmeter reading is obvious.
NO LOAD LOSS AND CURRENT.
The test is necessary to know that losses and current
are within tolerance of guaranteed value at specified
frequency.
This test determine quality of core lamination,
assembly and level of flux density used.
Expected value of watt/kg for 1.6 tesla and 1.69 tesla
are 1.3 watts /kg and 1.56 watts /kg
Further the following points are important
Observe the rise in lo load current with voltage. If no
load current in case saturation of core. In this case no
load current will suddenly increase near rated voltage.

measurment of insulation resistances
For measurement of insulation resistance between
LT to earth, LT and H.T, use 1000volt , 2000 M
ohms meggar. As per experiences there is no
problem in achieving 200 Mohms value at room
temp. of these resistance for 11 KV and above
windings. Some time for LT and earth resistance is
low about 500 Mohms.

However following table is given with temperature
for minimum acceptable insulation resistance in M
ohms.

Temp in
deg
centigrad
e
20 30 40 50 60
HV 800 400 200 100 50
LV 400 200 100 50 25
MEASURMENT OF WINDING RESISTANCE.
It is the D.C resistance of the winding , which is measured
across two terminals available at the bushings. The
temperature of the windings is taken to be the average of the
top and bottom oil temperature. For better accuracy the
difference between top and bottom oil shall be minimum. This
is the reason for doing this test in the beginning. It is assume
that transformer has been under oil without excitation for
long time. This time should be at least 3 hours. In case of
distribution transformer measurement of winding resistance
is normally carried when there is no difference between top
and bottom oil temperature.
The time of measurement should be noted and used for
guidance in carrying temperature rise test. Following points
must be noted.


It is important to measure the cold winding
resistance and temperature accurately because:

These resistance are used to determine stray copper
losses and thereby total load losses.
These resistance are used in the temperature rise of
windings .
For low resistance double Kelvin bridge < 2 ohms and
resistance >2 ohms whet stone method may be used.
Standard electronic instrument can also used for
resistance measurement.
The variation between resistance of different winding
should not be too much. In no case more than 5%.


Voltage test - winding


The H.V and LV. Winding of all transformers are
adequately tested for insulation before leaving the
factory. these tests consist of a) separate source
test and b ) induced over voltage test.
Separate Source Test
All the ends L.V windings are connected to earth.
The H.V windings are connected to one H.V
terminal of testing transformer , other L.V terminal
of this transformer being earthed. the primary side
of testing transformer is excited from normal supply
at any convenient frequency between 25 Hz to 50
Hz. It is preferable to apply this test at the normal
frequency. 28 kv for H.V terminals and 3 kv for L.V
terminals.
Induced Over Voltage est.
In this test induced over voltage test, for one minute
equal to twice the normal rated voltage of the h.v
winding. During this test the supply frequency
should be increased by at least 100 % above the
normal value in order to avoid an excessive exciting
current. The H.V windings are left open circuited,
the test voltage being applied to the L.V windings.
Temperature rise test.
This test is basically to verify the temperature rise of the
winding and the oil. Since test is of relevance to the life of
insulation, class of insulation, this test is attached lot of
importance. As per our AT term we carry out this test one
from supply of 100 no of transformer.
Few importance points to be noted as under.
Minimum tap position as current is high.
Shunt shall be of proper size.
in the measurement of winding resistance allow sufficient
time for reduction of inductive effect of the transformer.
Ambient temperature shall be taken accurately.
See that there is no wind.
Check the current feeding in transformer is correct
IMPLUSE TEST
Voltage surges have always occurred on transmission
systems and these surges, whether arising from
lighting or switching. To prevent breakdown
equipment must be designed to withstand surges.
Standard impulse voltage level for 11 kv dist
transformer is 75 kv peak 1.2/50micro seconds wave
shape.
But DISCOM has asked to pass the implulse having
95 kv peak instead of 75 kv.
One reduced level 50 to 75 % of the test level, one full
wave at test level, two chopped waves , one full wave.

DYNAMIC ABILITY TO WITHSTAND SHORT
CIRCUIT.
The verification of the ability to withstand short
circuit is to be performed on high voltage winding
connected to three phase balanced source and low
voltage winding short circuited through current
measuring instruments.
The current to be supplied is depend on x/r ratio of
transformer. Short is for 0.5 secs duration and at 11
kv.
The equipment is declared passed if no deviation in
oscillograms observed and it passes on all routine
test after short circuit test.
ALL ALUMINIUM ALLOY CONDUCTOR
Applicable IS 398 PART IV
Sample criteria 10 % i.e one from 10 no of drum
Packing Conductor shall be supplied in standard length
of 2.0 KM+-3% in drum as per IS 1778
Not more than 1100 kg and 1500 kg for of 34
sq.mm and 54 sq.mm conductor resply.
Physical
verification

Drum and conductor shall be verify as per
specification.
ALL ALUMINIUM ALLOY CONDUCTOR
Marking a) Size and name of conductor.
b) PGVCL order No. and date.
c) Name of manufacturer and
address.
d) Number & length of conductor in
meters.
e) Drum number.
f) Net weight of empty drum with
lagging.
g) Gross weight of drum with
conductor and lagging.
h) Property of PGVCL.
i) Name of consignee.
j) Reference IS Number & ISI
Certification mark, if any.
ALL ALUMINIUM ALLOY CONDUCTOR
Acceptance test

(i)Measurement of lay ratio.

(ii) Measurement of diameters of
individual wire.

(iii) Measurement of resistance of
individual wire.

(iv) Breaking load test of individual
wire.

(v) Elongation test of individual wire.
Verification of drum as per IS 1778
The conductor supplied in wooden drum shall be as
per above IS.
The flange diameter shall be selcted from list of
drum.
the generally the flange diameter is between 1220 to
1345 mm, the barrel diameter is 600, traverse 710,
flange thickness is 2x32, bore diameter 80, thickness
og lagging 38, no of binder over external lagging 2
etc.











Cable as per IS 694 Twin flat 2.5 sq.mm and
4 core

Applicable IS

IS 694
packing Packing list.
2c, 4c 4 sq.mm and 6 sq.mm 100mtrs coil +-.5%
4c 10sq.mm 16 sq.mm non returnable drum as per
IS 10418 500 mtr +- .5%
Non standard lengh for 6 and 10 sq.mm cable not less
than 100 mtr. In other size no non standard lengh
The information must be
either stenciled on drums
or printed on the label
attached with the coil.

a) IS:694/1990
b) Manufacturers name, brandname or trademark.]
c) Type of cable and voltage grade.
d) Number of cores
e) Nominal cross sectional area of conductor.











Cable as per IS 694 Twin flat 2.5 sq.mm and
4 core

The information must
be either stenciled on
drums or printed on
the label
attached with the coil.

f) cable code.
g) Colour of core.
h) Length of cable on the reel, drum, or coil.
i) Number of lengths on reel, drum or coil.
j) Direction of rotation of drum(by means of
arrow).
k) Approximate gross weight and drum
number.
l) Country of manufacture.
m) Year of manufacture.
n) A/T No. and date.
o) Date of dispatch.
P) Property of PGVCL.
q) Details of consignee (on wooden drums
only).
r) ISI Mark.
Cable as per IS 694 Twin flat 2.5 sq.mm and
4 core

The word shall be duly embossed
on sheath of every meter of length
of all cables. The embossing
should be clear and visible.

a) PGVCL.
b) Voltage Grade.
c) IS Number.
d) Year of manufacture.
e) Trade mark of supplier with
manufacturers Name.
Acceptance test High voltage
Resistance
Tensile of conductor
Wrapping test
Thickness of insulation and sheath
Tensile strength and elongation of
insulation and sheath
Volumetric resistance at 27 and 70
degree centigrade.
Flammability
Verification length in drum or coil
Cable as per IS 1554 3.5 core pvc cable
Applicable IS 1554
packing Packing list.
The LT PVC cable of size 3 Core x 25sq.mm,50 sq.mm,70
sq.mm. shall be wound on non-returnable wooden drums
with standard length of 500 Mtrs. and 3
core x 150 Sq.mm shall be in standard length of 250 Mtrs.
(ii)The wooden drums shall be as per IS:10418/1982.
Non standard length not less than 100 mtr and only 3 % of
order.
The information
must be either
stenciled on
drums or printed
on the label
attached with the
coil.
a) IS:1554part1/1988
b) Manufacturers name, brandname or trademark.]
c) Type of cable and voltage grade.
d) Number of cores
e) Nominal cross sectional area of conductor.
Cable as per IS 1554 3.5 core pvc cable
The word shall be duly embossed
on sheath of every meter of length
of all cables. The embossing
should be clear and visible.

a) PGVCL.
b) Voltage Grade.
c) IS Number.
d) Year of manufacture.
e) Trade mark of supplier with
manufacturers Name.
Acceptance test High voltage
Resistance
Thickness of insulation and sheath and
inner sheath
Tensile strength and elongation of
insulation and sheath
Volumetric resistance at 27 and 70
degree centigrade.
Verification length in drum or coil
LT AERIAL BUNCHED CABLE OF SIZE 1Core X 35mm+25mm
Applicable IS IS 14255-1995
Packing The cable shall be wound in non-returnable drums
conforming to IS-10418/1982 Specification for
Reels and Drums for bare wire of the latest version thereof.

The standard length of drum will be 500 meter and longer
length up to 2 Km with + 1 % tolerance shall be acceptable.
Non standard Length:
Non-standard length not less than 50 % of the standard
length shall be accepted to extent of 10% of the
ordered quantity.
The drums shall
be marked
a) Manufactures name
b) Trade mark if any
c) Drum number
d) Size of Conductor
e) Size of Messenger
f) Voltage grade
g) Number of lengths of pieces of Cable in each
drum

Sample criteria As per IS
LT AERIAL BUNCHED CABLE OF SIZE 1Core X 35mm+25mm
Acceptance test

a) Tensile test (for Phase conductor)
b) Wrapping test (for Phase conductor)
c) Breaking load test for messenger conductor
d) Elongation test for messenger conductor
e) Conductor Resistance test
f) Test for thickness of insulation
g) Tensile strength and elongation at break test
h) Hot set test (For XLPE insulation)
i) Insulation Resistance test
j) High voltage test

LT AERIAL BUNCHED CABLE OF SIZE 1Core X 35mm+25mm
11 KV PIN/DISC INSULATOR
Applicable IS 731
Packing All insulators shall be packed in wooden crates . Where
more than one insulator is packed in a crate, wooden
separators shall be fixed between the insulators to keep
individual insulator in position, without movement within
the crates. Disc.
Insulators however, may be assembled in a string and then
packed inside a crate, in above fashion
Marking a) Name or trade mark of the manufacturer.
b) Month and year of manufacturer.
c) Minimum failing load.
d) Country of manufacture.
e) ISI Certification mark, if any.
f) Word UGVCL' marked stickers to be provided on each
insulator.
11 KV PIN/DISC INSULATOR
Sample criteria As per IS 731
Acceptance test a) Verification of dimensions and Visual examination.
b) Temperature cycle tests.
c) 24 Hours mechanical failing load test or
mechanical performance test. (For disc. insulators only)
d) Electro mechanical failing load test (for disc. insulators
only)
e) Mechanical failing load test (for pin insulators only)
f) Puncture test.
g) Porosity test.
h) Galvanizing test (for disc. insulators only)
11 KV PIN/ DISC INSULATOR
Lot size First
Sampling n1
Second
sampling n2
Acceptance
no c1
Rejection no
c2
101 to 500 5 10 0 2
501 to 800 7 14 0 3
801 to 1300 10 20 0 3
1301 to 3200 15 30 1 4
Above 8000 35 70 2 7
11 K.V PIN/ DISC INSULTOR
Lot shall be considered as conforming to the
requirement to acceptance tests if no of failures
found in the first sample n1 is less than or equal to
c1,if the no of failure is greater than or equal to c2
the lot shall be considered as not conforming to
acceptance test, and lot is to be rejected. But if no of
failure of sample below c2 , second samples are to be
selected as n2, no of failure in the two combine is
less than c2 the lot shall be considered as conforming
to the requirement of acceptance test, otherwise lot
is considered as fail
Porosity test
The fragments shall be immersed in 1% alcohol
solution (of fuchim in 10 grm mentholated spirit)
under pressure not less than 15x10 raised to 6 for
time such that product of test duration in hours and
test pressure in N/M square is not less than 180x10
raised to 6
The fragments shall be removed from solution
washed dried & again broken
By naked eyes it shall not reveal any dye penetration

11 kv G.I.PIN
Applicable IS IS 2486(Part II) -1989
Packing 50 Nos. (Max.) are to be packed in double gunny bags
Sample criteria Sample criteria shall be in accordance with IS 2486 Part I
Acceptance test a) Visual examination.
b) Verification of dimensions as per DISCOM drawing .
c) Checking of threads on heads.
d) Mechanical failing load test.
e) Galvanizing test.
11 KV DISC HARDWARE
Applicable IS IS 2486(Part II) -1989
Packing The hardware fittings shall be packed in double gunny
bags in 25 sets.
marking The aluminum socket shall be embossed/casted with
trade name for identification of manufacturer and -word
DISCOM".
Sample criteria Sample criteria shall be in accordance with IS 2486 Part I
or latest revision thereof.
Acceptance test a) Verification of dimensions within the limit of specified
tolerance as per relevant DISCOM drawings.
b) Mechanical failing load test as per IS 2486 Part I .
c) Mechanical slip strength on clamp as per IS 2486-1993
Part I .
d) Galvanizing test as per IS 2633/1986
LT SHACLE INSULATOR
Applicable IS IS : 7935/1975 Specification for insulator fitting upto
and including 1000 V.

Sample criteria Selection of sample as per IS-7935/1975.

Acceptance test i) Visual inspection.
ii) ii) Verification of dimensions as per Dr. No.
O&M x 242 (Rev-3).
iii) Checking of threads.
iv) Galvanizing test on bolt & nuts IS-2633/1986.


STAY INSULATOR
Applicable IS IS-5300/1969 (Second Reprint March-1981)
Marking a) Name or Trade mark of manufacturer.
b) Year of manufacture.
c) PGVCL
d) Minimum failing load in KN.
Packing Each Insulators should be wrapped with dry grass. This
shall be then packed
in either polythene or double gunny bags. No.of
insulator should not be more
than 50 Nos. per bag for type 'B' and 30 Nos. per bage
for type 'C
STAY INSULATOR
Acceptance test a) Visual examination.
b) Verification of dimensions.
c) Temperature Cycle test.
d) Mechanical strength test.
e) Porosity test (Applicable only to HT Guy
Insulator Type-C).
M.S NUT AND BOLT
Applicable IS IS: 1363/84
Packing The bolts and nuts duly assembled shall be
packed in sound double jute /
woven polythene bags and each pack shall
contain maximum 50 Kgs. Net
weight.
Sample criteria As per IS 1363/84
Acceptance test As per IS 1363/84
STRUCTURAL STEEL ITEMS
Applicable IS IS : 2062 / 1992
Marking As per IS : 2062 / 1992 each product except M. S. Flat
and M. S. Round Bars shall carry a tag or be
marked with the Manufacturers Name or Trademarks.
Designation of Steel should also be similarly
marked on the product or tag. Each end of rolled
product shall be painted with Green Colour as per
specified for Grad A in IS : 2062 / 1992.
Sample criteria

The Nos. of sample randomly selected from the lot shall
be in accordance with and acceptance
criteria shall as per IS : 2062 / 1992.
STRUCTURAL STEEL ITEMS
Acceptance test [a] Verification of Dimension.
[b] Yield Strength Test.
[c] Elongation Test.
[d] Bend Test.
[e] Chemical Composition.
PVC PIPE
Applicable IS IS-9537 (Part-I & II) 1983
Marking NAME OF DISCOM , trade mark of supplier and
Nominal size of conduits should be screen print &
embossed on the pipe at every half meter length
preferably at 50 MM from one end
Sample criteria

Appendix-A
(A-2,1)of IS-9537 Part-III/1983
Acceptance test A. Visual inspection.
B. Verification of dimension as per Companys
requirement.
C. Compression test (Clause No. 9.3)
D. Resistance of burning (Clause No. 11).
E. Electrical characteristics ( Clause No. 12).

G.I. WIRE
Applicable IS IS : 280/1978
Packing The G. I. Wire shall be supplied in coils. The weight of
the coil shall be 50 Kg. to 80 Kg. Each coil shall be
wrapped in
hession
Marking (1) Name of Manufacturer.
(2) Size of Wire.
(3) Weight of Coil (approx.) Kg.
(4) Coil Serial No.
(5) A/T No. & Date,.
(6) ISI Mark if any.
(7) Property of MGVCL.
Sample criteria

The sampling for Acceptance Test shall be carried out as
per Appendix -'A' of IS : 280/1978 (Third revision)
G.I. WIRE
Acceptance test a) Visual examination.
b) Checking of diameters of wires.
c) Tensile Strength. As per relevant ISS specified
d) Wrapping test. para -2 hereof.
e) Mass of zinc coating.
f) Uniformity of zinc coating.
g) Adhesion of zinc coating.
G.I. STAY WIRE
Applicable IS IS-2141/1992, IS-4826/1979
Packing The G. I. Stay wire shall be supplied in coils. Each coil
should be weighing 50 to 70 Kgs. Each coil shall be
wrapped in hession
Marking 1) Name of Manufacturer.,
2) Size of G. I. Stay wire.
3) Coil Serial No.
4) Weight of Coil (approx.)
5) Tensile designation.
6) Coating.
7) A/T No. & Date.
8) ISI Mark if any.
9) Property of PGVCL/DGVCL/UGVCL/MGVCL.
Sample criteria

The sampling for Acceptance Test shall be carried out as
per of IS : 2141
G.I. STAY WIRE
Acceptance test a) Tensile and Elongation test.
The percentage elongation of the stranded wire
shall not be less than 6 % (Grade-4D)
b) Chemical Analysis :
The manufacturer shall have to submit test
certificate with every lot for the chemical
composition of
the steel rods from which the wires are drawn.
c) Galvanizing test.
The zinc coating shall confirm to "heavy
coating" as laid down in IS 4826/1979.
12.





9KV/18KV METAL OXIDE LIGHTNING ARRESTORS
WITHOUT GAP
Applicable IS 1. IS: 3070(Part-3)-1993 Metal Oxide Lightening
Arrestors without Gaps.
2. IEC-99-4 1991-II Metal Oxide surge arrestor
(Part-4) without gap for AC system
Packing The lightening arrestor fully assembled with fittings
shall be carefully covered with
shock absorbing protective material and should be
packed in either wooden crates or
corrugated box
Marking Each lightening arrestor shall be provided with a name-
plate or plates legibly marked
with following details (Details on sticker not acceptable)
a) Gapless lightening arrestor
b) Continuous operating voltage
c) Rated voltage & current
d) Rated frequency





9KV/18KV METAL OXIDE LIGHTNING ARRESTORS
WITHOUT GAP
Marking e) Nominal discharge current
f) The manufacturer's name or trace mark with
type & identification
g) The year & month of manufacturer
h) Serial Number of arrestors
i) Property of PGVCL
j) A/T No. with date & reference
Sample criteria

The sample criteria for acceptance tests shall be nearest
lower whole number to the
cube root of the number of arresters in the lot available
for inspection in accordance with the
clause No.7.2 of
IS: 3070 (part-3) -1993





9KV/18KV METAL OXIDE LIGHTNING ARRESTORS
WITHOUT GAP
Acceptance test (a) Measurement of Power frequency voltage on
the complete Arrestors at the reference current.
(All samples)
(b) Lightening impulse residual voltage test.(All
samples)
(c) Partial discharge test.( All samples)
(d) Visual examination and dimensional
verification test.(All samples)
(e) Porosity test of porcelain housing ( on two
samples)
(f) Galvanizing test on exposed ferrous metal
parts for uniformity of zinc
coating test and weight of zinc coating test. (on
two samples)
11 KV D.O FUSE
Applicable IS IS: 9385
(Part-I to III)
Packing 3 nos of D.O. Fuse are to be packed in a
Wooden/Corrugated Box.
Marking

Aluminum anodized name plate shall be fixed at base of
D.O. fuse. The following
information shall be duly punched or engraved on it. (1)
Manufacturers name (2)A/T No. and date (3) Rated
voltage (4) Rated normal current (5) Frequency (6) Sr.
No. of D. O. fuse (7) Property of PGVCL etc.
Sample criteria

One sample from each 100 Nos. or part of it to be
selected at Random from offered
lot for carrying out all acceptance tests mentioned above
at Clause No. 23 except for
temperature rise test, which shall be carried out on only
one (1) sample from offered
lot.
11 K.V. D.O FUSE
Acceptance
test

i) Visual inspection.
ii) Verification of dimensions
(iii) Power frequency voltage dry test
Iv ) insulation resistance
v) Mechanical operation
v i) Physical operation test ON-OFF
operation (10
vii) Temperature-rise test.

DIST BOX.
Applicable
standarad
IS no 2086 and 13947.
Marking

L.T. Dist. Box and also outside on front side name of the
firm as well as MGVCL
should be Embossed with manufacturing year.
1) Companys Name with full address
2) Capacity of Box
3) Serial No. of Box
4) A/T No. with date
5) Property of UGVCL
6) Date of supply of L.T. Dist. Box

Sample criteria

2 % of offered lot
DIST. BOX
Acceptance test (a) Visual Examination :
The L.T. Dist. Box will be inspected visually
externally and internally for proper Powder
coating layer, fittings of all the components in
accordance with MGVCL Specification and
relevant IS.
(b) Verification of dimensions :
Verification of dimensions, external/internal
clearances, will be carried out as per technical
specifications and approved drawing.
(c) Verification of fittings :
Components like Porcelain Fuse Units, bus bars,
neutral links and other fittings will be verified
as per technical specification and approved
drawings.
(d) High Volatage Withstand Test at 2.5 KV:
The Voltage of A.C. 2.5 KV RMS, 50 Hz. Shall be
applied for one minute as follows :
1) For Porcelain Fuse Units and bus bars :
(A) With all the Contacts closed.
TENDER NO. UGVCL/SP/450/25-63-100KVA
LTDB
Date Place Companys Round Seal Signature &
Seal of tenderer
- 13 -
(i) Between each pole and all other poles.
(ii) Between all live parts of the poles connected
together and earth.
(B) With all the contacts open :-
(i) Between incoming terminals and outgoing
terminals of Porcelain Fuse Units .
There shall not be any puncture or flasher during
this test. Following this test, the IR
test shall be taken and values observed shall not
be less than 10 Meg.Ohm.
(e) Insulation Resistance Test :
T
C.I EARTHING PLATE
Applicable IS As per specification
marking Word ' PGVCL' and manufacturer's name ' trade
name shall be casted on one
side of the Plate.
sample 20 no up to 2000 no
30 no up to 3000 no
40 no above 3000 no
Acceptance test Visual inspection
Verification of dimension
Verification of weight
ENERGY METER
Acceptable standarad

IS 13779 (1999) A.C. Static Watt
hour meter class 1.0 and Class 2.0
IS 12346 (1988)Specification for
testing equipment for
A.C.Electrical energy meter.
IEC 62053-21 (2003) General
Requirements, Tests and Test
conditions for A.C.Static Watt
hour meter for active energy
Class 1.0 and 2.0.
IEC 62053-21 (2003) A.C.Static
Watt hour meter for active energy
class 1.0 and 2.0

ENERGY METER
NAME PLATE
The Name Plate must be metallic. Sr.no.of
meter, MADHYA GUJARAT VIJ CO LTD.,
supplied order no. and year of supply,
GUARANTEE PERIOD 5 YEARS,
PROPERTY of MADHYA GUJARAT VIJ CO
LTD. I.S.I. certificate symbol given by
B.I.S. shall be marked. Adequate space shall
also be provided for pasting private sr .no
.of MADHYA GUJARAT VIJ CO LTD.,Sr. No.
of meter as given by MGVCL shall be
provided on name plate . The name plate
shall be provided with BAR CODE
containing details of Meter Serial Number
and Identification etc.

ENERGY METER
PACKING Each meter shall be packed in suitable mode to
ensure safe and eco environmental friendly use.
The meter shall have in plastic paper cover. 20 to
25 such single phase meter cases shall be again
packed in box having holding hooks of Nylon or
any other arrangement.

Acceptance test Insulation resistance measurement
No load condition
Starting current test
Accuracy requirement
Power consumption
Repeatability of error
Transportation test as per MGVCL
specification
Tamper conditions -- as per MGVCL
specification.


Thank you