Here we are concerned with safe grounding practices and design for
outdoor ac substations (distribution and transmission) for power
frequencies in the range of 50 to 60 Hz.
An effective substation grounding system typically consists of driven
ground rods, buried interconnecting grounding cables or grid, equipment
ground mats, connecting cables from the buried grounding grid to
metallic parts of structures and equipment, connections to grounded
system neutrals, and the ground surface insulating covering material.
Currents flowing into the grounding grid from lightning arrester
operations, impulse or switching surge flashover of insulators, and lineto-ground fault currents from the bus or connected transmission lines all
cause potential differences between grounded points in the substation
and remote earth. Without a properly designed grounding system, large
potential differences can exist between different points within the
substation itself. Under normal circumstances, it is the current flow
through the grounding grid from line-to-ground faults that constitutes the
main threat to personnel.
For reference material, IEEE Std. 80, Guide for Safety in Substation Grounding, is generally recognized
as one of the most authoritative guides available. It is recommended for any person concerned with the
design of substation grounding systems. A bibliography in the IEEE guide lists important additional
references, including abstracts of many of them.
The design procedures presented in this slide are based on IEEE Std. 80, Guide for Safety in
Substation Grounding. IEEE Std. 80 presents a simplified design procedure for substation grounding that
meets the required safety criteria without the use of an expensive computer software program.
The first aspect of substation grounding is how to take and analyze soil resistivity measurements. Next,
we look at the importance of the area of the ground grid. We shall also discusses and illustrates some of
the cases governing fault current flow. We will then use the split factor to take into account that not all of
the fault current uses the earth as a return path. The split factor can be calculated from graphs instead of
formulas; these graphs are one of the major improvements to grounding design from previous grounding
design manuals.
Once the maximum grid current is determined, we will then use the maximum grid current to choose
the type and size of the ground grid conductors needed. We shall also examines how to connect
substation equipment to the ground grid and the type of connector to use.
We will also show the importance of high-speed relays by calculating the tolerable limits of current to
the body, and the typical shocks situations. Tolerable touch and step voltages are discussed, which are
the design criteria of a safe grounding design. Also the benefits of protective surface materials, such as
gravel, in improving the tolerable touch and step voltages will be discussed.
Finally, all these information are pulled together in a step-by-step approach to designing a substation
grounding system. Once a safe ground grid has been designed, the proper grounding of the substation
fence and the operating handles on switches, cable sheaths, and surge arresters is discussed.
1.2 DEFINITIONS
1. DC Offset
Difference between the symmetrical current wave and the actual current wave during a
power system transient condition. Mathematically, the actual fault current can be broken into
two parts: a symmetrical alternating component and a unidirectional (dc) component. The
unidirectional component can be of either polarity, but will not change polarity and will
decrease at some predetermined rate.
2. Earth Current
The current that circulates between the grounding system and the ground fault current
source that uses the earth as the return path.
3. Ground Fault Current
A current flowing into or out of the earth or an equivalent conductive path during a fault
condition involving ground.
4. Ground Potential Rise (GPR)
The maximum voltage that a ground grid may attain relative to a distant grounding point
assumed to be at the potential of remote earth. The GPR is equal to the product of the earth
current and the equivalent impedance of the grounding system.
5. Mesh Voltage
The maximum touch voltage within a mesh of a ground grid.
DEFINITIONS contd.
6. Soil Resistivity
The electrical characteristic of the soil with respect to conductivity. The value is
typically given in ohmmeters.
7. Step Voltage
The difference in surface potential experienced by a person bridging a distance of
1 meter with his feet without contacting any other grounded object.
8. Touch Voltage
The potential difference between the ground potential rise and the surface
potential at the point where a person is standing while at the same time having
his hands in contact with a grounded structure.
9. Transferred Voltage
A special case of the touch voltage where a voltage is transferred into or out of
the substation from or to a remote point external to the substation site.
The current tends to flow near the surface for the small probe spacing, whereas more of the
current penetrates deeper soils for large spacing. Thus, it is usually a reasonable
approximation to assume that
the resistivity measured for a given probe spacing a represents the apparent resistivity of the
soil to a depth of a when soil layer resistivity contrasts are not excessive. Both equations can
be used to determine the apparent resistivity at a depth a.
There are a number of reasons for the popularity of the Wenner four-pin method. The
four-pin method obtains the soil resistivity data for deeper layers without driving the test pins
to those layers. No heavy equipment is needed to perform the four-pin test. The results are
not greatly affected by the resistance of the test pins or the holes created in driving the test
pins into the soil.
Resistivity measurement records should include temperature data and information on
the moisture content of the soil at the time of measurement. Also record all data available on
known buried conductive objects in the area studied. Buried conductive objects in contact
with the soil can invalidate resistivity measurements if they are close enough to alter the test
current flow pattern. This is particularly true for large or long objects.
1.4
The area of the ground grid should be as large as possible, preferably covering the
entire substation site. All of the available area should be used since this variable has the
greatest effect in lowering the grid resistance. Measures such as adding additional grid
conductor are expensive and do not reduce the grid resistance to the extent that increasing
the area does.
In general, the outer grid conductors should be placed on the boundary of the substation
site with the substation fence placed a minimum of 3 feet inside the outer conductors. This
results in the lowest possible grid resistance and protects persons outside the fence from
possibly hazardous touch voltages. It is therefore imperative that the fence and the ground
grid layout be coordinated early in the design process.
The simplified design equations require square, rectangular, triangular, T-shaped, or Lshaped grids. For preliminary design purposes, on a layout drawing of the substation site,
draw in the largest square, rectangular, triangular, T-shaped, or L-shaped grids that will fit
within the site. These represent the outer grid conductors and will define the area of the grid
to be used in the calculations. A square, rectangular, triangular, T-shaped, or L-shaped grid
site generally requires no additional conductors once the design is complete. For irregular
sites, once the design has been completed, additional conductors will be run along the
perimeter of the site that were not included in the original grid design and connected to the
grid. This will take advantage of the entire site area available and will result in a more
conservative design.
1.5
Fault in Substation; System Grounded at Local Station and also at Other Points. Ref. IEEE
Std. 80, Draft 13, June 19, 1998, Figure 15-3. Copyright 1998. IEEE. All rights reserved.
Typical Current Division for a Fault on High Side of Distribution Substation. Ref. IEEE Std.
80, Draft 13, June 19, 1998, Figure 15-4. Copyright 1998. IEEE. All rights reserved.