INTEGRATED PROTECTION, CONTROL AND SCADA SYSTEM FOR

SUBSTATIONS
10 - 12 July, 2001

Modern Substation Automation


- Relevant Aspects compared to Conventional Requirements

Rajiv Krishnan/D Venkatesh


Asea Brown Boveri Limited

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 1 / 01/06/21
ABB
Todays Presentation

From substation control and protection to Substation Automation

From modern to intelligent Substation Automation

System Architectures

Functional Structures

Application examples

Features and Benefits

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 2 / 01/06/21
ABB
Executive Summary

IT based solution for protection and control offer cost effective


measures to counteract large area system disturbances
Effective fault location is mandatory for faster finding and fixing of
problems
Integrated numerical protection & control allows automated power
restoration and load shedding
On-line condition monitoring reduces maintenance costs and
enables
Substation Automation offers a cost effective infrastructure for
implementing on-line condition monitoring of assets
Voltage instability prediction is a new approach for early indication
voltage collapses and enables to work plants and systems harder
Integrated asset management improves overall utility performance
and productivity

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 3 / 01/06/21
ABB
General Principles of Substation Automation

The general principles of the substation operation have


not changed, since their developing days. Therefore the
control and protection tasks remain the same.

The objective of modern substation automation (SA) is to


solve these tasks in a more efficient and economical way
by using state of the art information technologies (IT) and
to provide more functionality to work plant and systems
harder

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 4 / 01/06/21
ABB
Conventional Control & Protection
Fault SCADA Event
Bay Control Bay Protection Busbar Protection
Recording ABB
RTU Recording
225kV LIGNE ABOBO 1 =D04+R01
ABB 225kV LIGNE ABOBO 1 =D04+R01
ABB 225kV LIGNE ABOBO 1 =D04+R01 ABB 225kV LIGNE ABOBO 1 =D04+R01 ABB 225kV LIGNE ABOBO 1 =D04+R01 ABB 225kV LIGNE ABOBO 1 =D04+R01

ABB ABB ABB

125VDC Distributuion Battery A 125VDC Distributuion Battery B


125VDC Distributuion Battery A 125VDC Distributuion Battery B 125VDC Distributuion Battery A 125VDC Distributuion Battery B 125VDC Distributuion Battery A 125VDC Distributuion Battery B 125VDC Distributuion Battery A 125VDC Distributuion Battery B
Station Level

ABB

32156784ABB 12REL316*4
Network Partner
RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT

1 913
10
11
14
15
16 Indactic
Indactic 650
650
ON/OFF

056 citcadnI 056 citcadnI 056 citcadnI

=W1 BAY CONTROL RELAY REC316*4

=W2 RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT

10=W1
16782345-Q1 =W2 4.2b
-Q1 -Q2

914
11
SEL SEL ON/OFF

12
13
c15
16
VeriosnFERMER
LOCAL CONTROL METERING
-Q0
SEL TESTE
LAMPE
ABB RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT

38 45678231ABB 92REL316*4
10
111
13
14
15
16 Network Partner Indactic
Indactic 650
650
ON/OFF

OUVRIRFERMER
LINE PROTECTION RELAY REL316*4
ABB
ABB

ABB REB500
Network Partner
ESC EXE

DISTANCE
LOC
BUSBAR PROTECTION REB500

ABB 225kV LIGNE ABOBO 1 =D04+R01

ABB ABB ABB


Bay Level

For each function a dedicated device -Q1


SEL
-Q2
SEL
=W1

=W2

and separate kiosks -Q0


SEL TESTE
LAMPE

Extensive station wide cabling Local


Control
OUVRIRFERMER

ABB

ESC EXE

DISTANCE
LOC
Process Level

-Q2 GIS or AIS


Extensive bay cabling
Switchgear
-Q0 -Q9 -Q8

-Q1

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 5 / 01/06/21
ABB
Substitution of Conventional Technology
Control/Protection Cubicles MicroSCADA
Fllanden =AD17-KB2
Steuerung / Schutz

220VDC SPANNUNG SYS 1 220VDC SPANNUNG SYS 2

Interbaybus
Fllanden =AD17-KB2
Steuerung / Schutz

Feldsteuergert REC216 mit Messung und Synchrocheck

0220V
LEISTUNGSSCHALTER
LS
ZU
24V LS
ANTRIEBSMODULE
ACHTUNG
HYDRAULIK
DC
HYDRAULIK
/ 230V
SCHUTZ-STEUERSPG.
SF
PUMPE
--FEDERSPANNUNG !(CO)
AUSGANGSRELAIS
GAS AC
SCHALTHANDLUNG
NACHFLLEN
STRUNG
STRUNG
SPANNUNG
VERRIEGELT
VIELE ANLUFE
(OCO)
LEISTUNGSSCHALTER
LEISTUNGSSCHALTER/
SPANNUNGSWANDLER
DC Star coupler
0

PROZESS
PUMPENLAUFZEIT
SPG.
LS EINSCHALTKREIS
TRENNER/ERDER
LSSICHERUNGSBERW.
INTERFACE
UNVOLLSTNDIG
BERSCHRITTEN
BLOCKIERT
POSITION
ANGESPROCHEN
STRUNGGESTRT
LEISTUNGSSCHALTER
LEISTUNGSSCHALTER
TRENNER/ERDER
AUSLSEKREIS-
AUSLSEKREIS-
BERWACHNUNG
BERWACHNUNG
AUSSCHALTKREIS
PHASEN-DISKREPANZ
MOTORSCHUTZ 432 (O)12
VERRIEGELUNG

ANGESPROCHEN
-JA1
ANGESPROCHEN
BLOCKIERT
AUSGELST
ANGESPROCHEN
LEITUNGS-
LEITUNGS-
LEITUNGS-
SAMMELSCHIENEN
SAMMELSCHIENEN-/
HAUPTSCHUTZ
HAUPTSCHUTZ
RESERVESCHUTZ
STRUNGSCHUTZGERT
SCHALTERVERSAGER
AUSGELST
AUSGELST
STRUNG
-SCHUTZ
SAMMELALARME
FELDSTEUERGERT
BETRIEBSZUSTAND
FERN AUSGELST
SIGNAL-/ALARMANLAGE
ALARM
HORN
LOKALLAMPEN
ZUSTAND
QUIT
QUIT
RELAISHAUSTEST
EIN NORMAL
/) DIREKT
=AD17 FLLANDEN

-JA2
SAMMELSCHIENENSPANNUNG
2a 0 100 200 30
0
1a 0 100 200 30
0
WIRKLEISTUNG
d gi ta l

(STELLEN
L2121
( L2122)
-480 +480

BLINDLEISTUNG
-240 +240

PUMPENRFEDER )) / SF
-JA4
STROM

RCK- S
((( REIN-BLOCKIERT
TL2111
TAUS-BLOCKIERT
R 0 500 10001500

KOMBIWANDLER
-JF1 S 0 500 10001500

SWANDLERALARM
L2151
GASSCHUTZ
ABB

L2141
T 0 500 10001500 Power Automation AG RER111
LEITUNGSHAUPTSCHUTZ REL316*4 PRFSTECKER
-JA5
SPANNUNG

( L2126-N ))
0 100 200 30
0 I I I
Reset
MESSANWAHL 0 0 0 500SCM 500SCM 500SCM 500SCM 500SCM

0LOKAL
AUS

R-S
R
STUFENVERL. WE-BLOCK SCHUTZ EIN/AUS 01 01 01 01 01 di gi tal

S-T
S-N
-JA6 Tx1 Tx1 Tx1 Tx1 Tx1

T-R
T-N
L2136
ANTRIEBSSTEUERUNG
RCK-
AUS-
EIN
AUS
Rx1 Rx1 Rx1 Rx1 Rx1

STELLEN
FHREN
NORMAL
FERN
DIREKT
Tx2 Tx2 Tx2 Tx2 Tx2

Rx2 Rx2 Rx2 Rx2 Rx2

-Q1 -Q2
Tx3 Tx3 Tx3 Tx3 Tx3

Rx3 Rx3 Rx3 Rx3 Rx3


SAMMELSCHIENENSCHUTZ REB500 RESERVESCHUTZ

I
-X1 0
AUS
SYNCHRONISIERUNG HAND SCHUTZ EIN/AUS

ABB Power Automation AG


COM581
2 x 220/24V DC/DC SPANNUNGSVERSORGUNG

Communication
Converter NCC / RCC

-Q0
Feeder Marshalling C

Control Cubicle
-Q9 Relays for control / logic Mimic control board
Transducers, Meters
Switches, Lamps

Marshalling
Annunciators, Terminals

-Q8
Protection Cubicle

SER / Fault Recorder NCC Interface

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 6 / 01/06/21
ABB
Modern Substation Automation (SA)
Control/Protection Cubicles MicroSCADA
Fllanden =AD17-KB2
Steuerung / Schutz

220VDC SPANNUNG SYS 1 220VDC SPANNUNG SYS 2

Interbaybus
Fllanden =AD17-KB2
Steuerung / Schutz

Feldsteuergert REC216 mit Messung und Synchrocheck

0220V
LEISTUNGSSCHALTER
LS
ZU
24V LS
ANTRIEBSMODULE
ACHTUNG
HYDRAULIK
DC
HYDRAULIK
/ 230V
SCHUTZ-STEUERSPG.
SF
PUMPE
--FEDERSPANNUNG !(CO)
AUSGANGSRELAIS
GAS AC
SCHALTHANDLUNG
NACHFLLEN
STRUNG
STRUNG
SPANNUNG
VERRIEGELT
VIELE ANLUFE
(OCO)
LEISTUNGSSCHALTER
LEISTUNGSSCHALTER/
SPANNUNGSWANDLER
DC Star coupler
0

PROZESS
PUMPENLAUFZEIT
SPG.
LS EINSCHALTKREIS
TRENNER/ERDER
LSSICHERUNGSBERW.
INTERFACE
UNVOLLSTNDIG
BERSCHRITTEN
BLOCKIERT
POSITION
ANGESPROCHEN
STRUNGGESTRT
LEISTUNGSSCHALTER
LEISTUNGSSCHALTER
TRENNER/ERDER
AUSLSEKREIS-
AUSLSEKREIS-
BERWACHNUNG
BERWACHNUNG
AUSSCHALTKREIS
PHASEN-DISKREPANZ
MOTORSCHUTZ 432 (O)12
VERRIEGELUNG

ANGESPROCHEN
-JA1
ANGESPROCHEN
BLOCKIERT
AUSGELST
ANGESPROCHEN
LEITUNGS-
LEITUNGS-
LEITUNGS-
SAMMELSCHIENEN
SAMMELSCHIENEN-/
HAUPTSCHUTZ
HAUPTSCHUTZ
RESERVESCHUTZ
STRUNGSCHUTZGERT
SCHALTERVERSAGER
AUSGELST
AUSGELST
STRUNG
-SCHUTZ
SAMMELALARME
FELDSTEUERGERT
BETRIEBSZUSTAND
FERN AUSGELST
SIGNAL-/ALARMANLAGE
ALARM
HORN
LOKALLAMPEN
ZUSTAND
QUIT
QUIT
RELAISHAUSTEST
EIN NORMAL
/) DIREKT
=AD17 FLLANDEN

-JA2
SAMMELSCHIENENSPANNUNG
2a 0 100 200 30
0
1a 0 100 200 30
0
WIRKLEISTUNG
d gi ta l

(STELLEN
L2121
( L2122)
-480 +480

BLINDLEISTUNG
-240 +240

PUMPENRFEDER )) / SF
-JA4
STROM

RCK- S
((( REIN-BLOCKIERT
TL2111
TAUS-BLOCKIERT
R 0 500 10001500

KOMBIWANDLER
-JF1 S 0 500 10001500

SWANDLERALARM
L2151
GASSCHUTZ
ABB

L2141
T 0 500 10001500 Power Automation AG RER111
LEITUNGSHAUPTSCHUTZ REL316*4 PRFSTECKER
-JA5
SPANNUNG

( L2126-N ))
0 100 200 30
0 I I I
Reset
MESSANWAHL 0 0 0 500SCM 500SCM 500SCM 500SCM 500SCM

0LOKAL
AUS

R-S
R
STUFENVERL. WE-BLOCK SCHUTZ EIN/AUS 01 01 01 01 01 di gi tal

S-T
S-N
-JA6 Tx1 Tx1 Tx1 Tx1 Tx1

T-R
T-N
L2136
ANTRIEBSSTEUERUNG
RCK-
AUS-
EIN
AUS
Rx1 Rx1 Rx1 Rx1 Rx1

STELLEN
FHREN
NORMAL
FERN
DIREKT
Tx2 Tx2 Tx2 Tx2 Tx2

Rx2 Rx2 Rx2 Rx2 Rx2

-Q1 -Q2
Tx3 Tx3 Tx3 Tx3 Tx3

Rx3 Rx3 Rx3 Rx3 Rx3


SAMMELSCHIENENSCHUTZ REB500 RESERVESCHUTZ

I
-X1 0
AUS
SYNCHRONISIERUNG HAND SCHUTZ EIN/AUS

ABB Power Automation AG


COM581
2 x 220/24V DC/DC SPANNUNGSVERSORGUNG

Communication
Converter NCC / RCC

-Q0
C

E
Feeder Marshalling

-Q9 Still extensive bay cabling

-Q8

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 7 / 01/06/21
ABB
Modern SA Architecture

Network Control
Station Level

Center NCC

ABB Network Partner AG COM581

C
E

Features and Benefits


Basic Functionality
Bay Level
Process Level

-Q2

-Q0 -Q9 -Q8

-Q1

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 8 / 01/06/21
ABB
Implementation of Intelligent Technology
Intelligent Primary Equipment MicroSCADA

Interbaybus
M M
Star coupler t
M
d gi ta l

LOCAL SET
? REMOTEOPERATION

ABB

-Q2
Power Automation AG RER111

-Q1
500SCM 500SCM 500SCM 500SCM 500SCM
01 01 01 01 01 di gi tal i it l
Tx1 Tx1 Tx1 Tx1 Tx1

PISA Rx1 Rx1 Rx1 Rx1 Rx1

Tx2 Tx2 Tx2 Tx2 Tx2

Rx2 Rx2 Rx2 Rx2 Rx2

-Q1 -Q2 Drive control & Tx3 Tx3 Tx3 Tx3 Tx3

Rx3 Rx3 Rx3 Rx3 Rx3

-Q51 monitoring
circuitry ABB Power Automation AG

Communication
COM581

Process bus Converter NCC / RCC


Star coupler
-Q0 ABB Power Automation AG RER111
C
Feeder Marshalling
500SCM 500SCM 500SCM 500SCM 500SCM
01 01 01 01 01
Tx1 Tx1 Tx1 Tx1 Tx1

Rx1 Rx1 Rx1 Rx1 Rx1

Tx2 Tx2 Tx2 Tx2 Tx2

Rx2 Rx2 Rx2 Rx2 Rx2

-Q0
Tx3 Tx3 Tx3 Tx3 Tx3

Rx3 Rx3 Rx3 Rx3 Rx3

PISA
A
Process
Bus
PISA
-T1-Q9 A
PISA
B

-Q8
Sampling
AD-Conversion
-Q9
Signal Processing
Signal Filtering
-Q8

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 9 / 01/06/21
ABB
Intelligent SA Architecture
Station Level

Network Control
Center NCC

ABB Network Partner AG COM581

FEATURES AND BENEFITS


C
E

Basic Functionality
Bay Level

M M

LOCAL SET
? REMOTEOPERATION
Process Level

PISA

PISA

PISA
A

B
PISA
A

-Q2
-Q0 -T1 -Q9 -Q8

-Q1 -Q51

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 10 / 01/06/21
ABB
Complete Range of Integrated Solutions

Business
Management Meter & Load
Network
Management Management

Substation Consulting
Automation & Services
& Protection

Power Plant Communications


Control

Panorama
Asea Brown Boveri Limited
INABB / AUTP, Rajiv Krishnan, 11 / 01/06/21
ABB
Functional Structure of Modern SA
Functions Allocation
Scalable System Extensions
Station Level

Network Control SCADA


Center NCC
Remote Communication
Automation
ABB Network Partner AG COM581
Fault evaluation
Monitoring
Events and alarms
C
E
Protection
Supervision & Control
Data Exchange
Bay Level

Monitoring
Protection
Interlocking
Control
Data Acquisition
Process Level

GIS or AIS Switchgear


Instrument Transformers
-Q2 Power Transformers
Surge Arresters
-Q0 -Q9 -Q8

-Q1

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 12 / 01/06/21
ABB
Design Principles of Modern SA

Features Benefits

Mainstream Hardware Less inventories and spare parts


Mainstream Software platforms Less training & Familiarisation
Integrated SA System Less Hardware and panels
Control Less operation and maintenance
Monitoring (protection)
Disturbance recording
costs
Metering More availability
etc. Minimising outage breaks
Open System Integration of third-party
Bus (serial) communication equipment
Using fibre optic media Less cabling and installation
for communication costs
Compact design Less testing and commissioning
Decentralised system structure costs
closer to process Less space and civil works
No conventional mimic board

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 13 / 01/06/21
ABB
Highlights of Modern SA

Features Benefits

Numerical protection Easy to use and to customise


Numerical control Efficient operation
Safe interlocking Avoiding errors
Less hazards and breaks
Self supervision Reduction of operation costs
Modern MMI
Increasing availability
Operator guidance
Reducing maintenance costs
Maintenance support
Higher power quality

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 14 / 01/06/21
ABB
Enhanced Functionality of Modern SA

Features Benefits

Process status information Better planning


more timely data
On-line Primary equipment
monitoring Efficient trouble shooting
SA System status information All information at one glance
Events and Alarms evaluation
Better monitoring
Disturbance records
Trends and calculations Supports operation decisions
Reports Efficient asset management

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 15 / 01/06/21
ABB
Intelligent Substation Automation
Functional Structure Functions Allocation
Network Control
Station Level

Center NCC
Remote communication
Advanced functions & Tools
ABB Network Partner AG COM581
Monitoring
Protection
Supervision & Control
C
E

Data exchange
Bay Level

M M

Monitoring
M

LOCAL SET
? REMOTEOPERATION

Protection
Control
Condition monitoring
Data exchange
Process Level

Intelligent or smart
AIS / GIS Switchgear
PISA

Data acquisition
PISA

PISA
A

B
PISA

Sensors & Actuators


A

-Q2
-Q8 Power Transformers
-Q0 -T1 -Q9
Surge Arrestors
-Q1 -Q51

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 16 / 01/06/21
ABB
Intelligent SA: Features and Benefits

Features Benefits

Bus (serial) communication Further reduction in yard


to primary equipment cabling and installation costs

Intelligent primary equipment More information from primary


equipment
Sampling and signal processing
locally in primary equipment Operation enhancements
Reducing operation and
maintenance costs

Less primary equipment costs


Less project execution time

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 17 / 01/06/21
ABB
Intelligent SA: Control, Protection and Sensors
ABB

Actuator for
isolator &
PISA PISA PISA earthing Abgangsschutz
Line Protection 1 I
switch
control
PISA
M M

Feldleitgert
Bay Controller
M

Star Coupler
Sternkoppler ? LOCAL

REMOTE
SET

OPERATION

Actuator for opt. opt.


circuit breaker PISA
el.
A
Abgangsschutz
Line Protection 2 II
control
PISA
A
PISA
B
Busbar Protection
Sensors for
current &
voltage
measurement

Process Bus Interbay bus 1


Phase L1 Interbay bus 2

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 18 / 01/06/21
ABB
Data acquisition for protection and control

Line bay Intelligent electronic device (IED) Interfaces


for protection and control

Status MMI
B. Input Interface

Command
B. Output Function
Function
Local MMI
Function
Library
Library
Library
CT/VT
A. Input
Communication
Status PCMCIA SA
B. Input
SMS
PCMCIA

Command
CPU
B. Output

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 19 / 01/06/21
ABB
Bay level control via built-in mimic

ABB Power Automation AG REC580

U=500kV
U=500kV

U=500kV
Q51
Q51 Q53
Q53 Q55
Q55 Q57
Q57 Q58
Q58 Q56Q56 Q54 Q54 Q52 Q52

Q1
Q1 Q01
Q01 Q61
Q61 Q63
Q63 Q03
Q03 Q64Q64 Q62 Q62 Q02 Q02 Q2 Q2

Q15 Q91 Q92 Q25


Q15 Q91 Q92 Q25

IL1=0A IL1=0A
Q81 IL1=0A BB1:UL1=500kV IL1=0A Q82
Q81 BB1:UL1=500kV Q82

One row with informations, etc..............................................


One row with informations, etc..............................................

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 20 / 01/06/21
ABB
Interlocking with CB Q0 in closed position

ABB Power Automation AG REC580

U=500kV
U=500kV

U=500kV
Q51
Q51 Q53
Q53 Q55
Q55 Q57
Q57 Q58
Q58 Q56Q56 Q54 Q54 Q52 Q52

Interlocked Q1
Q1 Q01
Q01 Q61
Q61 Q63
Q63 Q03
Q03 Q64Q64 Q62 Q62 Q02 Q02 Q2 Q2

Q15 Q91 Q92 Q25


Q15 Q91 Q92 Q25
CB Q0
IL1=0A IL1=0A
is closed IL1=0A
Q81
Q81
BB1:UL1=500kV
BB1:UL1=500kV
IL1=0A Q82
Q82

One row with informations, etc..............................................


One row with informations, etc..............................................

Select
IS Q1

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 21 / 01/06/21
ABB
Bay Level Protection Systems

ABB Network Partner AG REC 316*4

1 9
2 10
3 11
4 12
5 13
6 14
7 15
8 16

Line Protection
ABB Network Partner AG REC 316*4
ABB Network Partner AG REC 316*4

1 9
1 9
2 10
3 11 2 10
4 12 3 11
5 13 4 12
6 14 5 13
6 14
7 15
8 16 7 15
8 16

C
C

E
E

Transformer Protection Generator Protection

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 22 / 01/06/21
ABB
Monitoring via IEDs for Protection

Automatic printing
Advanced analysis
Summary report GPS
tools

User friendly
visualization
Universal Time
CONCISE / FAST synchronization
Alarm Classes
Distance to Fault
Mo 12. 11. 96 GMT 17:02.43.305

Ayer Rajah & Labrador Feeder One

Sequence of Events

# Of trips
ABB Network Partner AG

IED Parameter
ABB Network Partner AG REL 316*4

1 9

2 10

3 11

4 12

5 13

6 14

7 15

8 16
Bay
C
E

I
C
O
E

R
F
C
E

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 23 / 01/06/21
ABB
Data exchange concept

Communication Level Requirement for data PYRAMID Bus Features


transmission and functionality Solution
Limited amount of data RP570/571 Master - Slave, multidrop
Binary signals, Commands, Typically Response deterministic
Network Control Link Measurands 1200 Bit/s (order of seconds)
Future links with Throughput 600 Bit/s
>64 kBit/s
High data traffic for MMI TCP/IP No master, event driven
Binary signals, Commands, 10 Mbit/s Response times 1 ? s
Station Bus Measurands (de facto Throughput 800 kBit/s
standard)
Soft real-time requirement LON No master, event driven
Station-wide interlocking, 1.25 MBit/s High priority slots (HPS)
Switching sequences Load prediction
Interbay Bus Time synchronisation 1 ms Response times 8..20 ms/HPS
Binary signals, commands, others <800 ms
Measurand Throughput 30 kBit/s
Hard real-time requirement MVB No master, cyclic slots
Process Bus High amount of real time 1.5 Mbit/s Response times 11000 ms
analogs as phasors, used for (adaptable)
Time synchronisation 50 s REB500 900 kBit/s
Binary signals, commands

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 24 / 01/06/21
ABB
Station level supervision

Single line diagram


U, I =>fast
P, Q, E => slow
Overview pictures
P, Q, => slow
Customised measurements
P,Q, E
Summation
Minimum / maximum
Average values
Lists
Bar charts
etc. upon request

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 25 / 01/06/21
ABB
Station Level Protection

ABB Network Partner AG REB500

REB 500
C

Central Unit

MVB Bus

ABB Network Partner AG REB500 ABB Network Partner AG REB500 ABB Network Partner AG REB500 ABB Network Partner AG REB500

C C C C

E E E E

Bay Unit Bay Unit Bay Unit Bay Unit

Busbar / Breaker Failure Protection

Busbar Protection

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 26 / 01/06/21
ABB
Event Processing

Recording and time stamping of events

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 27 / 01/06/21
ABB
Alarm Processing

Recording and time stamping of alarms

Persisting
and
fleeting
alarms

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 28 / 01/06/21
ABB
Recording of Trends and Alarm Generation

Upper Alarm (A)


hysteresis
Upper warning (W)
Lower warning

Lower alarm

A W
Asea Brown Boveri Limited
INABB / AUTP, Rajiv Krishnan, 29 / 01/06/21
ABB
Diagnostic: Fault Recording and Evaluation

Automatic
fault location
printout

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 30 / 01/06/21
ABB
Automation Examples

Situation Objective Method


Short circuit or overload Selective fault clearance Numerical protection

Power shortage Power supply maintained Load shedding

Power restored Power supply restored Reconnect consumers

Load variations Power quality maintained Control transformers

Operation under stress Safe switching Automatic switching


sequences

Transient earth faults Short power interrupts Auto-reclosures

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 31 / 01/06/21
ABB
Integration into Communication Networks

Protection / Operation / Planning / Asset


EMS / SCADA Engineering Centre Maintenance Centre Management Centre
Centre 1

EMS / SCADA
Centre 2 Corporate
Real time
System wide Communication Backbone
Master Clock Network Network

Inter-substation
Substation 1 Substation 2 Substation 3 Substation n
real time
communication

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 32 / 01/06/21
ABB
Remote Control via Network Control Centre (NCC)

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 33 / 01/06/21
ABB
Scalability: From basic up to fully redundant SA
Option:Option:
Link
Option:
Option:
to GPS
Network
Option:Hardcopy
Alarm
ABB
real Basic
Control
unit
service
time SA
printer
for System
Centre
for
system
receiver
modem print
forfor
for alarms
out
remote
systemof colour
remote indication
supervision
pictures
synchronisation
diagnostics & control
Option:
Option:
Option:
Second
Additional
Auxiliary
Alarm
Baseunit
workplace
System
alarm
for the
unit
as
for
second
hot
for
operation
alarms
standby
Baseindication
or
System
system
engineering
Starting with Basic System and growing by options to fit optimally in customers requirements
Hardcopy
Printer
ABB
Service Alarm/Event
Control Centre Modem Printer
Interfaces
Base System Base System Additional
Workplace GPS
Alarm Alarm Meinberg
ABB Network Partner AG COM581
Unit Unit Mo 12. 11. 96 GMT 17:02.43.305

Printer Server POWER

V1

OVP
ACQR LOCK

NORMAL OPERATION
WED 11.12.1996
GPS 166
SATELLITE CONTROLLED CLOCK

MEZ 11.42.25
SV 24 > SYN

CLR
MENU NEXT INC
ACK

C MEINBERG

Ayer Rajah & Labrador Feeder One

Protocol Converter
COM581

Ethernet (TCP/IP)

Network Partner
SSLTA 88 SRS485M SRS485M SREDU/M

SERVICE
RS232 RS485 RS485
RER 111 Star Coupler (LON Bus) Network Partner
SSLTA 88 SRS485M SRS485M SREDU/M

SERVICE
RS232 RS485 RS485

1MRSC60029
1MRSC60028
1MRSC60028
1MRSC60028
1MRSC60028
1MRSC60028
1MRSC60028

For Control and Protection Relays 1MRSC60029


1MRSC60028
1MRSC60028
1MRSC60028
1MRSC60028
1MRSC60028
1MRSC60028

ABB Network Partner AG REB500

C
REB 500
E

Central Unit
Auxiliary
MVB Bus REC 316 REG 316 RET 316 REL 316 REL 521 REL 531 REL 511 Alarm
ABB Network Partner AG REL521 ABB Network Partner AG REL531 ABB Network Partner AG REL511
ABB Network Partner AG
REC 316*4 ABB Network Partner AG
REC 316*4 ABB Network Partner AG
REC 316*4 ABB Network Partner AG
REC 316*4

ABB Network Partner AG REB500 ABB Network Partner AG REB500 ABB Network Partner AG REB500 ABB Network Partner AG REB500

1
2
9
10
1
2
9
10
1
2
9
10
1
2
9
10
Annunciation
3 11 3 11 3 11 3 11
4 12 4 12 4 12 4 12
5 13 5 13 5 13 5 13
6 14 6 14 6 14 6 14
7 15 7 15 7 15 7 15
8 16 8 16 8 16 8 16

C C C C C C
C C C C c c

E E E E E E
E E E E
Bay Unit Bay Unit Bay Unit Bay Unit

Busbar / Breaker Failure Protection Bay Control and Protection Units Bay Control and Protection Units

Asea Brown Boveri Limited


INABB / AUTP, Rajiv Krishnan, 34 / 01/06/21