EHS SISTEMI I NAČIN RADA

Flux Pro
Dragan Vučinović
23.05.2015
EHS (ECO HEATING SYSTEM)

- Mono
- Split
- TDM (TIME DIVISION MULTI)
MONO
EHS Mono system

• EHS Mono System


 No refrigerant pipe works
 Easy installation by cylinder unit

Pre-plumbed Cylinder Unit


“Integrated
Outdoor Unit”

Control
Kit
Water
Under Floor Radiator
Water Piping

Hot Water

Outdoor Indoor
Cycle Diagram - Outdoor
Outdoor Units – 9/12/14/16 kW

Pločasti Kondenzator
izmenjivač
Product Structure • Control kit

Components for Control Kit


- Control kit (1EA)
- Flow switch (1EA, Set point 16lpm)
- Wired remote controller (1EA)
- Temp sensor (DHW Tank 1EA, Backup Heater 1EA)
- Remote controller (1EA)
- Smart grid wire (1EA)

Samsung Kit Feature : ELCB integrated (30A)


T

Prikaz povezivanja- Monoblok


Outdoor Mechanical room indoor
T
Wired Remote Controller

DHW sensor input


& Booster Heater output

Solar pump Zone


Air controller #2
booster heater Vent
Solar signal input T
E 50~55℃ 45℃
Supply Header

Return Header
back up boiler
operation output
DHW tank
Radiators or Convectors

2
Zone
controller #1

Control Kit
Shut-off &
Drain Valve
Secondary 40℃
2
pump Supply Header
3 3
Primary
strainer pump 3-way Return Header
valve Air
R PrimaryE Vent Under-Floor Heating Coils
pump Expansion
Pressure tank Mixing tank
relief valve

Y 3.0 bar
Drain

Mono Outdoor Unit


Split
Optimized Solution EHS SPLIT

for residential use


EHS Split System EHS Split System
Consists of an outdoor unit and an hydro unit

Outdoor Unit Hydro Unit


 Compatible with all low temp.
radiator and UFHs
 More efficient
 Up to 55℃ water supply
 Easy to install
Hot Water (up to 55℃)  Easy to control
 Floor Heating
Enhance Radiator
an available capacity and
Ref’ Piping Water Piping
COP at a low ambient temperature.

Hot Water

Hydro Unit
Outdoor Indoor
Water Tank
DHW tank Outdoor Unit
EHS SPLIT

02 Features (EHS Split System)


Reliability
Since Samsung EHS system is designed to meet your up to date demands, can provide an outstanding
Satisfaction with both you and your customers.

• Low Noise Fan


• Anti-snowing mode -20℃
Operating Range
• Silent mode

Capacity at -10℃ 90%

Seasonal COP 3.66 (TBD)

COP at A2W35 3.50

• Base Plate Heater (Optional)

* 16kW, both EHS Split & Mono models


EHS SPLIT

02 Features (EHS Split System)


Easy to Control
Samsung EHS can be implemented with other optional products: Domestic Hot Water Tank,
Thermostat, Pump, Solar Panel or Back-Up Boiler, making it more versatile than ever.
Field Scope

Solar pump Application SAMSUNG

Solar
Backup Boiler

Boiler

2way valve
2way Valve
for UFH

Hydro Unit 3way valve 3way Valve


for UFH

Room
230V AC
Room Thermostat Thermostat
EHS SPLIT

03 Line-up (EHS Split System)


Line-up Key Specifications
Capacity SAMSUNG DAIKIN 11kW
CAPACITY (kW)
SPLIT 12.5kW
5.2 10.0 12.5 14.0 16.0
Air-to-Water
Function Air-to-Water
1 + Air-to-Air
Phase
AEX052EDEHA AEX100EDEHA AEX125EDEHA AEX140EDEHA AEX160EDEHA

3 COP / EER
Phase (Air-to-Water)
4.70 / 3.45 4.60 / 3.32
Model AEX125EDGHA Capacity
AEX140EDGHA AEX160EDGHA

HYDR CAPACITY (kW)


O 8 kW 16 kW Performance
at -10℃
90 % 65 %
1
Phase
AEN080YDEHA AEN160YDEHA

3
Phase
AEN160YDGHA
Split
 Outdoor  Mech. Room  Indoor
T

Solar thermal Panel


E
Solar Pump

Room Controller
1) Solar Control Back-up Boiler
2) Back up Boiler 4) Zone Control
Booster Heater & Protector Operation
45℃
Supply Header
Thermistor Return Header
50~55℃

3-way Valve
T

Radiators or Convectors
[Application #3]
Room Thermostat
3) DHW Control [Application #2] & Actuators
[ Supply Scope ] DHW Tank Load Thermostatic T
Pump #1 & Balancing Valves

Load
E T B T
Pump #2 40℃
2
Supply Header
3

Return Header
E Under-Floor Heating Coils
Mixing Tank
[Application #1] [Application #4]
Zone Thermostat Differential Pressure
& 2-way Valve bypass valve
Outdoor unit Hydro-unit
Cycle Diagram – Hydro Unit

Hydro Unit - 16kW

7) Pressure Relief Valve


[working at 3bar]

6) Air vent valve


5) Heater Vessel
[2+4 kW, Incoloy 800]
Tw3 Tw2

4) EEV
Tr1
10) Expansion Vessel Ref' In
8) Flow Switch [8L, Pre-charge 1bar]
[최소유량 16LPM↑] 3) Heat exchanger
[Plate type]
Ref' Out
Tr2
Tw1

9) Water Pump
[46LPM x 54kPa]

11) Manometer 2) Strainer


[STS304, Mesh #30]
[0~4bar]

1) Service Valve
[1 ¼” BSPP male]

Wat Water
in
er
out
Glavna razlika u odnosu na EHS MONO
- Freonska instalacija izmedju spoljašnje i unutrašnje jedinice
- Pored izmenjivača unutrašnja jedinica sadrzi:
- Grejače (backup)
- Prekidač protoka (dobija se i uz MONO)
- Pumpu
- Manometar
- Temp. Senzore
TDM
System Overview – A2W+A2A
How does it operates?
 Air to Air unit : Space cooling & Space heating
 Air to Water unit : Water heating & Space heating/cooling

EEV
Kit Cooling

RAC
DUCT

Heating
3

Supply Header

Return Header

Hydro-unit Cooling
Outdoor unit
Radiators or FCU

Room Controller Heating


Warm Water

DHW Tank
TDM Operation ②
A2A=ODU Capacity 100%
- Alternative operation with A2A priority
Quick heating available by using TDM technology Alternating between A2A and A2W : By
default, after 30 min. A2A operation, then 5
Quick heating Normal heating min. A2W operation takes over. (FSV option)

A2A < ODU Capacity 100%


- A2W and A2A operate simultaneously when
they are in the same operation mode. (Sum
of A2W and A2A loads is smaller than outdoor
unit capacity)
A smart alternating by TDM
Target Temp.
Samsung EHS
TDM is applied when A2A & A2W (or DHW)
Room are in the same operation mode.
Temp. Normal Heat Pumps (Floor Heating)
- A2W or DHW request heating when A2A is
in the cooling mode BUH or BSH turns of
instead of TDM operation
Initial Temp.
Time
Normally 5~20 minutes

Installation Guide
[The capacity of the outdoor unit] = [the larger one of the total cooling load] or [the total heating load of the house]

Room # Room1 Room 2 Room3 Room # Room1 Room 2 Room3


Heating or Heating or
5kW 3kW 3kW 5kW 3kW 3kW
Cooling Load Cooling Load

Air to Air Air to Air

Air to Water Air to Water


Outdoor unit
Installation 11kW Installation
example 1 example 2
KONTROLA
Heat Pump

46 35

Outdoor Temp. (℃DB)


Outdoor Temp. (℃DB)

Heating Mode
Cooling Mode

No heatpump
operation, Back up
heater only

10
-20

5 25 15 25 40 55

Leaving water temp. (℃) Leaving water temp. (℃)

Water Temp. (℃) Water Flow rates (LPM) Air Temp. (℃, DB/WB)
-
Min Std Max Min Std Max Min Std Max

Cooling 5 - 25
Controller
Heating 15 - 55

Inlet - 23 (12*2) 30
Cooling 10/- 35/24 46/28
Outlet 5 18 (7*2) 25
16 (12*1) Δ 5℃ 58 (48*1)
Inlet 10 30 (40*2) -
Heating -20/- 7/6 35/24
Outlet 25(15*4) 35 (45*2) 55

*1 : 11~16kW. (6~8kW)
Min. water in system 20L *2 : Eurovent Test Condition #2
*3 : NF PAC low temp. heating
4 : Back up heater only
Operation Range

DHW(Domestic Hot Water) Tank

43

35

Outdoor Temp. (℃DB)


Sanitary Mode
Booster heater
operation only

-20

30 40 55 70
Leaving water temp. (℃)

Water Temp. (℃) Water Flow rates (LPM) Air Temp. (℃, DB/WB)
-
Min Std Max Min Std Max Min Std Max
Controller DHW 30 - 70
Sanitary Outlet 30 - 70 -20/- - 43/26

both Hydro unit and DHW tank should be installed in a mechanical room with ambient temperature 0~40℃
Wired Remote Controller

Button and function

OUTING

22
Operation Mode Display
Available operation mode
Heating mode and cooling mode can not operate at the same time.

Heating Cooling
DHW modovi
- Eko mod
Water law Heating + DHW - Standard mod
- Power mod
Cooling + DHW Water law + DHW
DHW urgent dugme

DHW Urgent DHW Outing mod

Outing (heating) Outing (heating + DHW)


Prioriteti:
A2A > DHW > ZONE2 > ZONE1

Outing (heating + urgent DHW)

23
Operation Mode ③

Water law Operation


In this mode, the heat pump operates according to the parameters for the weather dependent.
 The set point can be set manually
 or set weather dependant
Ts
Heating Water Law Ts • All the Field Setting Values
Cooling Water Law needed to re-design
•the water law for floor or
FCU(radiator) can be
Max. Max. •changed by using Wired
Remote Controller’s
↑ +5°C ↑ +5°C •Field Setting Mode.
Shift Shift
Min. ↓ -5°C Min. ↓ -5°C
• There are 2 types of water
law for each mode, one for
floor application, the other for
FCU(radiator). One of them
#2011 #2012 Ta #2051 #2052
can be selected by using
Wired Remote Controller’s
Field Setting Mode.
Min Max Min Max

#2022 #2021 #2062 #2061


• The target water
Floor Floor temperatures exceeding the
(default:25°C) (default:40°C) (default:18°C) (default:25°C)
operation limit of heat
#2032 #2031 #2072 #2071
FCU
(default:35°C) (default:50°C)
FCU
(default:5°C) (default:18°C) pump(5 ~ 55 ℃) after
reflecting user’s arbitrary
input(temperature shift) will
Ta : Outdoor Temperature be neglected, and be kept
Ts : Setting Temperature (Target Water Temperature by Water Law) maximum or minimum
FCU: Fancoil unit respectively.
PITANJA?