13.2/7.62kV
69kV
13.8kV
13.8kV
230kV
13.2/7.62kV
Generation
115kV 13.8kV 4.16/2.4kV
4.8kV
Transmission
34.5/20kV 6.24/3.6kV
13.2/7.62kV
Sub-Transmission
13.8kV
Distribution
OUTLINE
Transformer Nomenclature (Nameplate,
Company Number)
Workshop
Transformer Taps
Transformer Polarity
Transformer Connections (Standards,
Common Errors & Troubles)
Workshop
Connection for L-G Secondary System
Reminders on DT Installations
Typical MERALCO DT
Primary H2
Primary H1 Bushing
Bushing (At the Back)
Secondary
(X1, X3, X2, X4)
KVA Bushings
Rating
Company Nameplate
Number
DT Nameplate Sample
Polarity
KVA Rating (Subtractive)
Primary
Voltage
Secondary Rating
Voltage
Rating
(Dual
Voltage)
Voltage
Rating
per tap
Schematic
position
Diagrams
DT Nameplate Sample
Primary
Voltage Rating KVA Rating
Secondary
Voltage
Rating Polarity
(Additive)
Voltage
Rating
per tap Schematic
position Diagrams
DT Nameplate Sample
Company Number
KVA
Rating
Secondary
Voltage
Rating
Primary
Voltage
Rating
Voltage
Rating
per tap
position Schematic Diagrams
DT Nameplate Sample
Primary Secondary
KVA Rating Voltage Rating Voltage Rating
Polarity (Additive)
Symbols Used in Transformer Voltage Ratings
To designate separate
voltages which can be
obtained by reconnecting 34500GRDY / 19920 V -
Cross X the coils of a winding in 120/240 X 139/277 V
series or multiple
combinations
Primary Voltage Ratings of DTs Used by MERALCO
W W 20
Z T 13.2, 13.8
Z Z 7.62
X X 3.6
Y Y 4.8
MY M 2.4
DT Company Number Coding System of
MERALCO
II. SUFFIXES (Secondary Winding Rating)
CODE LETTER VOLTAGE RATING
A 120/240 or 240/120
B 139/277
C 240/480
D (or Y) 139/277x120/240
E 240/139*
F 480/277*
* Three-
G 240 phase
DTs
N 125/216*
Difference Between
120/240- & 240/120-Volt Ratings
B-
139/277 V
Secondary
W-
19.92 kV
Primary
DT Company Number Sample
A-
120/240 V
Secondary
M-
2.4 kV
Primary
DT Company Number Sample
D-
Dual Voltage
120/240 X
139/277 V
Secondary
Z-
7.62 kV
Primary
External Tap-Changers
Operation
1. De-energize the DT
2. Loosen lock screw
3. Rotate switch to
desired position
4. Tighten lock screw
5. Energize the DT
Lock Screw
Other Types of External Tap-Changers
Internal View of a DT With an
External Tap-Changer
Tap-
Changer
Internal Tap-Changers
Rotary Tap-Changers
Schematic Diagram of a Dual Voltage
Transformer
H1 H2
TAP
5 4 3 2 1 CHANGER
DUAL
VOLTAGE PRIMARY
TAP
WINDING
(SET AT
INNER
TAP)
139V 139V
X1 X3 X2 X4
139/277 V
Schematic Diagram of a Dual Voltage
Transformer
H1 H2
TAP
5 4 3 2 1 CHANGER
DUAL
VOLTAGE PRIMARY
TAP
WINDING
(SET AT
OUTER
TAP)
120V 120V
X1 X3 X2 X4
120/240 V
Samples of DTs With Dual Voltage Tap
Dual
Voltage
Taps
Always
refer to
nameplate
for actual
ratings.
Samples of DTs With Dual Voltage Tap
Tap changer Dual Voltage Taps
Dual
Voltage
Taps
Transformer Polarity Convention
Single-phase
transformers that
do not meet either Subtractive
one or both criteria
Terminal Markings of DTs
I. ADDITIVE POLARITY
H1 H2 H1 H2 H1 H2
X3 X1 X3 X1 X4 X1
X2 X2 X2 X3
H1 H2 H1 H2 H1 H2
X1 X3 X1 X3 X1 X4
X2 X2 X3 X2
EXAMPLES:
1) 100 kVA, 3.6 kV-240/120 V Additive
HV SIDE
Temporary
Shorting Vm Voltmeter
Wire (Jumper)
LV SIDE
Subtractive
Polarity:
333 kVA,
3600/6240Y V -
120/240 V
Polarity of DTs
X2
X1
X4
X3
Subtractive
Polarity:
250 kVA,
34500Grd.Y/
19920 V -
139/277 V
Polarity of DTs
X3 X2 X1
Additive
Polarity:
25 kVA,
2400/4160Y V -
120/240 V
DT Connections Used By MERALCO
System 1-Phase 1-Phase Open-Wye, Ungrd. Wye- Grd. Wye- Open-Delta- Delta-
L-to-N L-to-L Open-Delta Delta Grd. Wye Open-Delta Delta
34.5 / 20 kV Wye Yes Yes Yes
13.2 / 7.62 kV Wye Yes Yes Yes Yes Yes Yes Yes
Note: The voltage on he leftmost column refer to the system voltage of the circuit & not on
the voltage rating of the DT.
Single-phase Connection
Line-to-Neutral Primary (Subtractive Polarity)
A
N
H1 H2
X1 X3
X2
n
a
b
A
N
H1 H2
X3 X1
X2
n
a
b
H1 H2
X3
X1
X2
n
a
b
C Van = 120V
PRIMARY SECONDARY
Single-phase Connection
Line-to-Line Primary (Additive Polarity)
A
B
H1 H2
X1
X3
X2
n
a
b
C Van = 120V
PRIMARY SECONDARY
Open-Wye, Open-Delta Connection
2 Subtractive Polarity DTs
A
B
C
N
H1 H2 H1 H2
X3 X3
X1 X1
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b
n Vab = 240V Van = 120V
N a
Vbc = 240V Vbn = 120V
A C c
Vca = 240V Vcn = 208V - Bastard
PRIMARY SECONDARY
Voltage
Open-Wye, Open-Delta Connection
2 Additive Polarity DTs
A
B
C
N
H1 H2 H1 H2
X1 X1
X3 X3
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b
Vab = 240V Van = 120V
n
N c
Vbc = 240V Vbn = 120V
A C a
PRIMARY SECONDARY Vca = 240V Vcn = 208V
Common Error in Open-Wye, Open-Delta Connections
A
B
C
N
H1 H2 H1 H2
X3 X1 X3 X1
X2
X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B c
b Vab = 240V Van = 120V
N n
Vbc = 240V Vbn = 120V
A C a
PRIMARY SECONDARY Vca = 416V Vcn = 317V
Common Error in Open-Wye, Open-Delta Connections
A
B
C
N
H1 H2 H1 H2
X3 X1 X3 X1
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B
b
Vab = 240 V Van = 120V
N n
a Vbc = 416 V Vbn = 120V
A C c
PRIMARY SECONDARY Vca = 240 V Vcn = 317V
Common Trouble in Open-Wye, Open-Delta Connections
Detached jumper
A
To B
Source C
N
H1 H2 H1 H2
X3 X1 X3 X1
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b
n Vab = 240 V Van = 120V
N a
Vbc = 480 V Vbn = 120V
A C c
PRIMARY SECONDARY Vca = 240 V Vcn = 360V
Wye-Delta Connection
3 Additive Polarity DTs
A
B
C
N
Floating Neutral
H1 H2 H1 H2 H1 H2
X1 X3 X1 X1
X3 X3
X2 X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b Vab = 240V Van = 120V
n
N c Vbc = 240V Vbn = 120V
A C a
Vca = 240V Vcn = 208V - Bastard
PRIMARY SECONDARY Voltage
Common Error in Wye-Delta Connections
(Ex. 1 Subtractive & 2 additive DTs)
ERROR: X1 of Wing 1 was connected to X1 of Main while X3
of Main was connected to X3 of Wing 2
A
B
C
Floating Neutral
H1 Wing 1 H2 H1
Main H2 H1 Wing 2 H2
X1 X1 X3 X1
X3 X3
C X2 X2 X2
C’
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
c
B a Vab = 240V Vc’a = 416V Van = 120V
n
N Vbc = 416V Vbc’ = 240V Vbn = 120V
b
A C c’ Vca = 240V Vcc’ = 480V Vcn/Vc’n = 317V
PRIMARY SECONDARY
Corrected Error in Wye-Delta Connection
(Subtractive & 2 additive DTs)
CORRECTION: H2 instead H1 of Main DT was tapped to the phase
conductor. This results in the imaginary swapping of the X1 & X3 leads.
A
B
C
Floating Neutral
H1 Wing 1 H2 H1
Main H2 H1 Wing 2 H2
H2 H1
X1 X1 X3 X1
X3 X3
X3 X1
X2 X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b Vab = 240V Van = 120V
n
N c Vbc = 240V Vbn = 120V
A C a
Vca = 240V Vcn = 208V - Bastard
PRIMARY SECONDARY Voltage
Wye-Wye Connection for 240-volt Service
3 Subtractive Polarity DTs
A
B
C
N
H1 H2 H1 H2 H1 H2
X1 X4 139V 139V X4 X1 X4
X1
X3 X2 X3 X2 X3 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b Vab = 240V Van = 139V
X1 X4 139V 139V X4 X1 X4
X1
X3 X2 X3 X2 X3 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b Vab = 480V Van = 277V
X4 X1 X1 X4 X1
X4
X2 X3 X2 X3 X2 X3
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b Vab = 240V Van = 139V
X4 X1 X1 X4 X1
X4
X2 X3 X2 X3 X2 X3
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b Vab = 480V Van = 277V
H1 H2 H1 H2
X3 X1 X3
X1
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B n b Vab = 240V Van = 120V
A a 0º angular
displacement Vbc = 240V Vbn = 120V
H1 H2 H1 H2
X1 X3 X1
X3
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
c 180º angular
B displacement Vab = 240V Van = 120V
H1 H2 H1 H2
X1 X3 X1
X3
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B n b Vab = 240V Van = 120V
A a 0º angular
displacement Vbc = 240V Vbn = 120V
H1 H2 H1 H2
X1 X3 X1
X3
X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
c
B Vab = 240V Van = 120V
X3 X1 X3 X3
X1 X1
X2 X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b
n Vab = 240V Van = 120V
X1 X3 X1 X1
X3 X3
X2 X2 X2
n
a
b
c
VOLTAGE VECTORS SECONDARY VOLTAGES
B b Vab = 240V Van = 120V
A n
c Vbc = 240V Vbn = 120V
C a
Vca = 240V Vcn = 208V
PRIMARY SECONDARY
SINGLE-PHASE 240V, LINE-TO-GROUND
SECONDARY SYSTEM
A
B
C
N
H1 H2
X3 X1
X2
a
b
A
B
C
N
H1 H2 H1 H2
X1 X1
X3 X3
X2 X2
a
b
c
INSULATED PHASE BARE GROUNDED
CONDUCTORS PHASE CONDUCTOR
B b
SECONDARY VOLTAGES
N c Vab = 240V
a Vbc = 240V
A C
Vca = 240V
PRIMARY VECTORS SECONDARY VECTORS
WYE-DELTA CONNECTION FOR 3-PHASE,
CORNER-GROUNDED DELTA SECONDARY
A
B
C
N
H1 H2 H1 H2 H1 H2
X1 X3 X1 X1
X3 X3
X2 X2 X2
a
b
c
INSULATED PHASE BARE GROUNDED
CONDUCTORS PHASE CONDUCTOR
B b
SECONDARY VOLTAGES
N c Vab = 240V
a Vbc = 240V
A C
Vca = 240V
PRIMARY VECTORS SECONDARY VECTORS
Reminders on DT Installation
A. New Installation
Inspect DT for any physical defects
Before re-energizing:
Remove all temporary grounding wires
Check DT connection against sketch/drawing/phase markings
Release pressure by operating the pressure relief device
Energize DT
Check voltage & phase sequence at CMS (verify with customer)
Accomplish Transformer Report (TR)
A Transformer Rated 13200 V
A Transformer Rated 13200 Grd.Y/7620 V
A Transformer Rated 7620/13200Y V
Available DT Banks at the Training Grounds