ZXM10 EISU Training

Unitrans D&T Group


Overview
 The ZXM10 EISU is an imbedded microprocessor system.
 It can monitor supervision signals of various base station
power equipment and environments in real time, generate
alarms, and make corresponding control as required.
 it is capable of networking downlink base stations, and
networking by making effective use of base station
communication resources.

2
Description of EISU Models
 The ZXM10 EISU (V1.0) is a series product.

ZXM10 EISU ( - - - )
48 -48 VDC power
24 +24 VDC power

Null Basic functions


BT Battery capacity analysis function added

Null Basic configurations


SS Extended configuration

Null Basic mode, network interface (master comm port) and serial port
for master communication
1E One E1 interface (master comm port) and timeslot back board for
master communication
2E Two E1 interfaces (master comm port), 2M ring and timeslot front
board for master communication
4E Four E1 interfaces (master comm port), 2M ring + chain networking

3
Description of Common Models of the EISU
No. Model Description

1 ZXM10 EISU Serial port and network interface for master


(48) communication, basic configuration for supervision
factor, -48 V
2 ZXM10 EISU 2M ring and front board for master communication,
(2E-48) basic configuration for supervision factor, -48 V
3 ZXM10 EISU Back board for master communication, basic
(1E-48) configuration for supervision factor, -48 V
4 ZXM10 EISU Back board for master communication, extended
(1E-SS-48) configuration for supervision factor, -48 V
5 ZXM10 EISU Back board for master communication, extended
(1E-SS-BT-48) configuration for supervision factor, battery
capacity analysis function being integrated, -48 V

4
Functions
 In the basic configuration, the ZXM10 EISU provides 12
general AI/DI measurement channels, two general DI
measurement channels and four DO channels to implement
data collection and control of the unintelligent equipment. If an
extended supervision unit is configured, eight general AI/DI
measurement channels, two general DI measurement
channels and four DO interfaces are added.
 The ZXM10 EISU has the dedicated sensor interface, where
one digital temperature sensor, two battery channels for total
voltage and one smog detector can be connected.
 The ZXM10 EISU provides multiple intelligent equipment
protocol resolution interfaces to implement data collection and
control of the intelligent equipment. (There are four to six
interfaces and 20 intelligent devices can be connected.)
 The ZXM10 EISU has the picture supervision function. It
provides two USB camera interfaces to process, store and
forward picture data. The picture resolution is up to 640  480.

5
Functions
 The ZXM10 EISU provides multiple communication interfaces
and networking modes. These transmission interfaces contain
asynchronous serial ports, Ethernet interfaces and E1
interfaces. They provide the following networking modes: order
wire channel, network, 2M protection ring, 2M chain, separate
2M and 2M extracted timeslot.
 The ZXM10 EISU provides the local storage function. The data
within 15 days can be stored locally after the master
communication is interrupted.
 The ZXM10 EISU provides the function of remotely or locally
downloading the running program and intelligent equipment
communication protocol program.
 The ZXM10 EISU has the functions of equipment self-
diagnosis and fault self-location.
 The ZXM10 EISU provides the management function of real-
time clocks.

6
Functions

 The ZXM10 EISU configured with the extended transmission


board provides transparent Ethernet interfaces.

 The ZXM10 EISU provides the Web browsing function.

 The ZXM10 EISU supports the intelligent equipment center


resolution function.

 The ZXM10 EISU supports energy saving for air conditioners.

7
Panel Indicators
 There are nine indicators on the EISU panel,

8
Jumper and DIP Settings of EISU
 Basic configuration of EISU includes configuration to EISUP
board, EISUM board, ETNM board, and EISUL board.

EISUL board

EISUP board EISUM board

ETNM board EISUS board

9
Jumper and DIP Settings on EISUP Board
 Key components on EISUP board are as follow. In engineering
practice,

X5

EISUP
S2

X4 X7

S1

10
Jumper and DIP Settings on EISUP Board
 the jumper X7 on EISUP board must be at pin 2 and 3. DIP
switch S2 use default setting.

11
Jumper and DIP Settings on EISUM Board
 here are two DIP switches on EISUM

EISUM

S2

S1

12
Jumper and DIP Settings on EISUM Board
 boardS1.1~S1.8 and S2.1~S2.4 are AI type switches, ON
means current type, OFF means voltage type.

13
Description of External Interfaces-EISUM
 External interfaces of the EISU can be viewed when the cable
cover is removed. The external interfaces are provided by the
EISUM, EISUS and ETNM. The interfaces in the lower row are
provided by the EISUM, and the interfaces in the upper row by
the EISUS and the ETNM. The EISUS can change its location
with the ETNM .

Switch

14
Configuration EISUconfig
 Log in EISUconfig

15
Basic Configuration
 EISU network parameters and security console connection
parameters.

16
Board Management
 On Channel Configuration subpage, sensor type, channel
type, upper and lower limits of alarm, and return difference,
and so on,

17
Serial Port/Intelligent Port Management
 EISU has 7 serial ports in total.

18
Intelligent Analysis Settings
 the red numbers are the order of the steps in setting intelligent
analysis function.

19
USB Video Management
 If USB device is closed, then all management and operation
related to this USB device are unavailable. If USB device is
available, relevant operation may be done.

20
Access Control Communication Settings

21
External access control mode
 Connect external access controller with EISU applied in
dynamic IP networking.
For example, connect CHD805AE in wireless dynamic IP
networking or dynamic IP networking.
1. Set the serial port connecting the device as soft transparent;
2. Set up serial port parameters: baud rate, receive mode.

22
EISU built-in access control mode

23
Operation steps
 1.Select the serial port that is specified on engineering drawing in
Serial Port box, and select Access Control in the Function box;
 2.Click Modify button to set serial port parameters.
 If Baud Rate is 9600, then the Waiting Time after Sending should
be set as 2083;
 If Baud Rate is a value other than 9600, then the Waiting Time after
Sending will be automatically set to appropriate value. EISU
configuration program above V1.10 supports this function.
 3.For receive mode, you must select [Header (7E) +Tail (0D)];
 4.Set Function Parameters of Access Control Port:
 Server IP and Port No. do not need to be set.
 5.Door Magnetic Channel must be set as the exact channel that is
connected in construction practice.

24
Update of Application Program and Driver
 EISU supports remote downloading application program and
driver.

25
Faults and Alarm Handling

26
Faults and Alarm Handling

27