Professional Documents
Culture Documents
PROTECTION
S.S.A.RAJAPAKSA MIET,MIEEE
Senior electrical engineer
Miniature circuit breaker
MCB standards
• IEC 60898
• 4,6, 10, 16, 20, 25, 32, 40, 50, 63,80, 100, 125
amperes
1 pole
2 pole
3 pole
4 pole
MCB tripping characteristics
“a mechanical switching
device, capable of making,
carrying and breaking
currents under normal
circuit conditions and also
making , carrying for a
specified time and breaking
currents under specified
abnormal circuit condition
such as those of short
circuits.”
Where are MCCBs used?
ACB ACB
MCB MCB
What are the standards?
• BS EN 60 947-1 General Rules
• BS EN 60 947-2 Circuit Breakers
• BS EN 60 947-3 Switch Disconnecters
• BS EN 60204-1
Safety of machinery
• BS 7671 :2008
IEE Wiring Regulations 17th Edition
Short circuit breaking capacity
• short circuit breaking capacity or short circuit breaking
current of circuit breaker is defined as maximum
current can flow through the breaker from time of
occurring short circuit to the time of clearing the short
circuit without any permanent damage in the CB. The
value of short circuit breaking current is expressed in
RMS. During short circuit, the CB is not only subjected
to thermal stress, it also suffers seriously from
mechanical stresses. So during determining short
circuit capacity, the mechanical strength of the CB is
also considered. So for choosing suitable circuit
breaker it is obvious to determine the fault level at that
point of the system where CB to be installed.
factors to be considered for calculation of
breaking capacity
• Distribution transformer KVA rating (higher the
transformer rating breaking capacity increases -
eg:100 KVA- 3 KA , 1000 KVA- 33 KA)
• Distribution voltage (higher the voltage breaking
capacity specified in kA: decreases)
• Cross sectional area of the cables ( higher the
cross sectional area breaking capacity will not
reduce)
• Length of the cables (higher the length breaking
capacity reduces rapidly )
Breaking Capacity (Ics)
• In order to define this value, the circuit breakers
under test must be subjected to a test sequence
of:
1 6 12
Magnetic (Im) Ir (x ln) Im (x ln)
I
600%In
Abnormal conditions faced by circuit
breakers
• Over current -sensed by the bimetallic
thermal overload device or electronic
overload trip unit
• Short circuit - sensed by the electromagnetic
short circuit trip or electronic short circuit
trip unit
Vocabulary of terms associated with
circuit breakers
• Rated current (In)-The maximum permissible continuous
current rating specified with in the given temperature
limits.
• Breaking capacity -a value of abnormal breaking current
that a circuit breaker is capable of breaking at a stated
voltage.
• Rated ultimate short circuit breaking capacity(Icu)- the
maximum short circuit current can withstand by the circuit
breaker under specified conditions of the manufacturer
• Eg; a short circuit close to the breaker terminals may
cause such maximum currents. After such short circuit the
breaker cannot handle its full rated current.
Suitability for isolation
• In open contact position the same must
withstand the impulse voltage without
flashover. Contact position shall be indicated
using following method
• Position of the opening handle
• Separate mechanical indicator
• Visible breaking of contacts
Switching devices
Average trip
time=20
seconds
400%
Tripping a MCCB
• Electromagnetic trip unit
• Inverse time characteristics
• Time delay (utilization category B) not
available
• bimetallic Over current tripping
• Electromagnetic short circuit tripping
Tripping a MCCB(electronic trip unit)
• Electronic trip unit
• True RMS sensing for long time delay
• Peak sensing for short circuit/instantaneous
• Time delay for tripping (utilization category B )
available
• Communication capability
• L/S/I curves
• Integral ground fault
• History of last trip
Tripping curve of an electronic MCCB
( TERASAKI -TEMBREAK 1 )
Electronic trip unit
BRIDGE CONSTANT
RECTIFIER VOLTAGE
BUILT IN CURRENT CIRCUIT TO CIRCUIT
TRANSFORMERS CONVERT AC/DC Magnet hold
FOR 3 PHASES
trigger
ANALOGUE
TO DIGITAL CENTRAL
SIGNAL PROCESSING
CONVERTER UNIT
User interface
USER INTERFACE
Auxiliary Alarm
Auxiliary Alarm
Shunt UVT
Internal accessories
Link interlock
Wire interlock
- front mounting ensures
- for form 4 application compact change over-unit
Specifications …
• Sensitivity 30/100/300 mA
• Specifications …..
• Rated tripping (residual) current -10,30,100,300,500 Ma
• Personal shock protection max; value
• 30mA
• Fire protection max; value 300 Ma
• max; tripping time at rated tripping current – 300 mille
seconds
RCCB
Earth leakage
protection by
RCD
Circuit
ELR + breaker
RCCB vs ELR
RCCB ELR
• Fixed sensitivity setting. • Programmable
• Instantaneous tripping. sensitivity setting.
• Usually for domestic • Programmable time
applications or delay.
applications with less • Usually for industrial
than 100A load current. applications or
applications above
100A load current.
Earth Leakage Protection
• Residual current circuit breaker (RCCB)
– Mainly for human protection & residential use.
• Tripping time
– Instantaneous
– Delay time
– (preferred setting 500 Milli sec)
Application of shunt trip for (ELR)
Application of ELR in LV system
• Usually use Earth leakage relays (ELR) for load
current larger than 100A but less than 300A
• Usually for load current less than 100A, use
RCCB/ELCB
• Usually for load current larger than 300A, use
Earth-Fault relay
Installation & Wiring 1
ZCT
Cable
ZCT
Specifications …