Professional Documents
Culture Documents
AIR
DISTRIBUTION
AIR DISTRIBUTION
AIR DISTRIBUTION
AIR DISTRIBUTION
HEAT LOAD CALCULATIONS DETERMINE
AIR DISTRIBUTION
AIR DISTRIBUTION SYSTEM CAN BE COMPARED TO
CIRCULATION OF BLOOD IN A HUMAN BODY. IT IS
THE HEART OF THE SYSTEM.
AIR DISTRIBUTION
THE VEINS RETURN THE BLOOD AFTER IT HAS GIVEN UP
ITS OXYGEN; ALMOST THE SAME AS RETURN AIR DUCT
CARRY BACK THE AIR AFTER IT HAS DONE ITS COOLING /
HEATING JOB.
AIR DISTRIBUTION
ROOM
A/C SPACE
AIR DISTRIBUTION
AIR DISTRIBUTION SYSTEM
IS THE MEANS TO ACHIEVE THE GOAL
AIR DISTRIBUTION
ELEMENTS OF AN AIR DISTRIBUTION
SYSTEM
OVERALL AIR SYSTEM COMPRISES OF
FOLLOWING IN VARYING CONFIGURATIONS
1. COOLING / HEATING COILS.
2. SPRAY / HUMIDIFIER
3. AIR FILTERS ( PRE, FINE, HEPA )
4. SUPPLY / RETURN/ EXHAUST AIR FANS – WHICH PROVIDES
ENERGY TO MOVE THE AIR
5. CASING - HOUSING THE ABOVE COMPONENTS
6. DUCT THROUGH WHICH AIR IS DISTRIBUTED TO THE SPACE
7. SPLITTER & DAMPERS - TO CONTROL / ISOLATION
8. INLET/ OUT LET/EXHAUST AIR TERMINALS
9. HEAT RECOVERY WHEEL
AIR DISTRIBUTION
ELEMENTS OF AN AIR DISTRIBUTION
SYSTEM
LEAKAGE
FA DAMPER FILTER COILS SA. FAN VCD
SUPPLY AIR DUCT
SAG
FIRE DAMPER
(+) (-)
VCD ( RA )
SPACE
FIRE DAMPER ( RA )
RAG
AIR DISTRIBUTION
ALL AIR SYSTEM
SINGLE DUCT DUAL DUCT
IN WHICH HEATING / COOLING
SOURCES ARE IN SERIES
AIR DISTRIBUTION
ALL AIR SYSTEM - MERITS
ALL AIR SYSTEM CAN BE USED FOR COMFORT OR
PROCESS WORK.
USED EXCLUSIVELY FOR SPECIAL APPLICATIONS WHERE
CLOSE CONTROL OF TEMPERATURE, HUMIDITY, HIGH
LEVEL OF FILTRATION, FRESH AIR & PRESSURIZATION
ARE REQUIRED
( CLEAN ROOM; HOSPITAL; PHARMA; COMPUTER )
GREATEST POTENTIAL FOR USE OF ALL OUT SIDE AIR
FOR ECONOMISER COOLING INSTEAD OF MECHANICAL
REF.
ADAPTS WELL TO WINTER HUMIDIFICATION.
HEAT RECOVERY DEVICES.
HIGH LEVEL OF FILTRATION.
AIR DISTRIBUTION
CONSTRAINTS
• REQUIRE ADDITIONAL DUCT CLEARANCE
ABOVE FALSE CEILING, WHICH REDUCES
USABLE FLOOR SPACE OR INCREASES
HEIGHT OF BUILDING.
AIR DISTRIBUTION
ALL AIR SYSTEM
PRE COOLING
FILTER COIL S A FAN
OUT DOOR
AIR
(-)
ZONE - 1 R1
HUMIDIFIER
AIR DISTRIBUTION
ZONE : IS AN AREA THAT REQUIRES
SEPARATE CONTROL OF CONDITIONS
AIR DISTRIBUTION
T1
REHEAT COIL
ZONE - 1
COOLING T2
OUT DOOR COIL SA. FAN
AIR
REHEAT COIL
ZONE - 2
AIR DISTRIBUTION
HVAC DUCT SYSTEM
IT IS A STRUCTURAL ASSEMBLY WHOSE PRIMARY
FUNCTION IS TO CONVEY AIR BETWEEN TWO SPECIFIC
POINTS.
EXHAUST AIR DUCT
4
AIR HANDLING
UNIT
COIL 1
SUPPLY AIR
DUCT
FILTER
3 SA RA
A/C
SPACE
FRESH AIR
DUCT
AIR DISTRIBUTION
ELEMENTS OF DUCT ASSEMBLY
INCLUDE
AIR DISTRIBUTION
FALSE CEILING PLENUM AS
RETURN AIR SPACE
• SUSPENDED CEILING SPACE ABOVE A ROOM, RAISED
FLOOR SPACE / CAVITY AND SHAPE WALL CAN ALL BE
USED AS A RETURN DUCT.
AIR DISTRIBUTION
SUSPENDED CEILING
SPACE ABOVE
FALSE CEILING IS
SUPPLY USED AS RETURN
SLAB AIR DUCT AIR PLENIUM
FALSE
CEILING
2400
FFL
AIR DISTRIBUTION
RAISED FLOOR
SLAB SUPPLY AIR DUCT
FALSE CEILING
AIR DISTRIBUTION
CAVITY WALL
SUPPLY DROP DOWN
SLAB AIR DUCT CEILING
AIR DISTRIBUTION
THE FLOW SYSTEM - WHAT CAUSES
AIR FLOW ?
THE FLOW OF AIR BETWEEN TWO ZONE ( OR SPACES)
IS DUE TO PRESSURE DIFFERENCE BETWEEN THE TWO
ZONES. THIS PRESSURE DIFFERENCES FORCES THE AIR
TO FLOW FROM HIGH PRESSURE TO LOW PRESSURE
ZONE
CONTINUITY EQUATION
QUANTITY OF AIR Q ( M3/SEC CR CFM ) THAT WILL
FLOW IS EQUAL TO CROSS SECTON AREA. A OF DUCT
( M2/FT ) TIMES AIR VELOCITY (U, FPM OR M/SEC)
AIR DISTRIBUTION
THE AIR VELOCITY WILL CREATE A VELOCITY
PRESSURE ( INCH WG ). IT IS A MEASURE OF
KINETIC ENERGY
AIR DISTRIBUTION
VELOCITY, V
AIR FLOW
VE
LO
PR CI
ES TY
SU
RE
CROSS
SECTIONAL
AREA, A
Q GRAVITY
( AIR FLOW ) DAMPER
Q = A*V
AIR DISTRIBUTION
WHEN AIR FLOWS THROUGH A DUCT OF
CONSTANT CROSS SECTION, THE AVERAGE
VELOCITY REMAINS CONSTANT AND
PARALLEL TO CENTRE LINE OF THE DUCT
AIR DISTRIBUTION
DUCT AIR VELOCITY PROFILE
MAX. AT CENTRE
AIR FLOW
MIN. AT SURFACE
ELBOW
10 H
24" W
1 H=18"
2
3
4
VELOCITY TRANSVERSE
5H ( MEASUREMENT )
AIR DISTRIBUTION
STATIC PRESSURE
ST
AT
IC U CT
PR D
ES
SU
RE
AIR DISTRIBUTION
STATIC PRESSURE MEASUREMENT
FAN BLOWING FAN EXHAUSTING
AIR DISTRIBUTION
IN PRACTICE, THERE IS ALWAYS A FRICTION
LOSS AS AIR FLOWS THROUGH IT. STATIC
PRESSURE IS USED TO OVER COME THESE
FRICTIONAL LOSSES THROUGH COIL,
ELBOWS, FILTERS, FITTINGS, DUCT WALL.
AIR DISTRIBUTION
AIR AT REST & AIR IN MOTION
STATIC TOTAL
PRESSURE PRESSURE
345 PA 345 PA
THROTTLING
AIR AT REST DEVICE
FAN DUCT
345 PA
97 PA
THROTTLING
AIR IN 4005 FPM DEVICE
MOTION
50% OPENED
FAN DUCT
AIR DISTRIBUTION
FRICTION LESS - DUCT
FOR ALL CONSTANT AREA SECTIONS, THE TOTAL AND STATIC
PRESSURE LOSSES AND SAME.
INCREASE IN REDUCTION IN REDUCTION IN
DUCT SIZE => AIR VELOCITY => VELOCITY PR.
& STATIC PR.
INCREASES.
OR VICE VERSA
TOTAL PRESSURE ALWAYS DECREASES ALGEBRICALLY IN THE
DIRECTION OF AIR FLOW. (NEGATIVE VALUES OF RETURN OR
EXHAUST SYSTEM INCREASES IN DIRECTION OF AIR FLOW.
POSITIVE VALUE OF SUPPLY AIR SYSTEM REDUCES.
AIR DISTRIBUTION
FRICTION LESS DUCT
AIR FLOOR OPEN END
TOTAL PRESSURE
( INCHES WG )
STATIC
PRESSURE
TOTAL
PRESSURE
VELOCITY ATMOSPHERIC
PRESSURE PRESSURE
FRICTIONAL
LOSS
TOTAL
PRESSURE
STATIC
VELOCITY
PRESSURE
PRESSURE
VELOCITY ATMOSPHERE
PRESSURE
PRESSURE
AIR DISTRIBUTION
SYSTEM STATIC PRESSURE
INTERNAL STATIC
OUTDOOR AIR PRESSURE
LOUVER
SUPPLY AIR
OUT LET
SUPPLY AIR
DUCT A/C SPACE
FILTER COIL FAN
RETURN AIR
OUT LET
AIR DISTRIBUTION
SYSTEM STATIC PRESSURE
= INTERNAL STATIC PRESSURE + EXTERNAL
( WITH IN THE EQUIPMENT ) STATIC PRESSURE
(EXTERNAL TO UNIT)
AIR DISTRIBUTION
SYSTEMS STATIC PRESSURE
PRESSURE
INCREASE DUCT COIL DUCT
DUCT FILTER
+ 0.58 ( - ) 0.01 ( - ) 0.22 ( - ) 0.08
( - ) 0.08 ( - ) 0.08
AIR FLOW
SUPPLY AIR
RETURN AIR GRILLE
GRILL - ( - ) 0.03 (-) 0.08
NEGATIVE PRESSURE POSITIVE PRESSURE
AIR DISTRIBUTION
A. TOTAL FRICTIONAL RESISTANCE
1. RETURN AIR GRILL - 0.03” WG
2. DUCT - 0.08
3. FILTER - 0.08
4. DUCT - 0.01
5. COIL - 0.22
6. DUCT - 0.08
7. SUPPLY AIR GRILL - 0.08
TOTAL - 0.58” WG
AIR DISTRIBUTION
CLASSIFICATION OF DUCTS
BASED ON AIR VELOCITY
LOW VELOCITY
UP TO 2500 FPM & 2 INCH STATIC PRESSURE -
NORMALLY BETWEEN 1200 - 2200 FPM - USED FOR
COMFORT JOBS.
HIGH VELOCITY
SYSTEM - ABOVE 6” STATIC PRESSURE 6” - 10” HIGH
PRESSURE.
ABOVE 2500 FPM - MOSTLY INDUSTRIAL. HOWEVER
VELOCITY & PRESSURE RATING ARE INTER RELATED
HIGHER THE VELOCITY HIGHER FRICTION LOSS
REQUIREMENT OF HIGH
PRESSURE DUCT WORK
AIR DISTRIBUTION
RECTANGULAR VS ROUND DUCT
FOR A SPECIFIED CROSS SECTIONAL AREA AND MEAN
AIR VELOCITY, ROUND DUCTS HAVE LESS FLUID
RESISTANCE AGAINST AIR FLOW THAN RECTANGULAR
DUCTS AND ARE EFFICIENT AND ECONOMIC.
TRANSVERSE JOINT
CROSS BREAKING
CROSS BREAKING OR
A * BEADING ARE EFFECTIVE
H
AIR DISTRIBUTION
DUCT TRANSVERSE JOINTS
SEALANT
DRIVE SLIP
DETAIL - A
H=25MM
SEALANT
SEALANT
STANDING - S SEAM
DETAIL - B
AIR DISTRIBUTION
DUCT LONGITUDINAL JOINTS
PITTS BURGH LOCK BUTTON BURGH
SNAP LOCK
SEAL THIS
POCKET WITH
SEALING
AIR DISTRIBUTION
SEAM LOCATIONS
SEAM LOCATIONS
NUMBER OF SEAMS AND LOCATION VARIES WITH JOINT TYPE, SHEET STOCK
AIR DISTRIBUTION
BREATHING OF DUCTS
RECTANGULAR METAL DUCTS ARE PRONE TO
RUMBLE FROM FLEXURE IN THE DUCT WALLS
DURING AHU START UP AND SHUT DOWN.
DUCT WALL SHOULD BE ADEQUATELY
STIFFENED / REIN-FORCED OR CROSS -
BRACED.
ROUND DUCTS CAN HAVE SPIRAL OR
LONGITUDINAL SEAMS. WITH SPIRAL SEAMS
THINNER MATERIAL CAN BE USED.
AIR DISTRIBUTION
WHAT ARE FLEXIBLE DUCTS?
WHERE ARE THEY USED?
ARE USED TO CONNECT THE MAIN DUCT WITH
TERMINAL BOXES OR DIFFUSERS.
THEIR FLEXIBILITY AND EASE OF REMOVAL ALLOW
RELOCATION OF TERMINAL DEVICE.
FLEXIBLE DUCTS SHOULD BE AS SHORT AS POSSIBLE
AND ITS LENGTH FULLY EXTENDED TO MINIMIZE FLOW
RESISTANCE.
SIZES ARE FROM 2 TO 20 INCHES.
FLEXIBLE DUCT USED SHOULD BE UL LISTED.
LOW INSTALLATION TIME
AIR DISTRIBUTION
FLEXIBLE DUCTS
AIR DISTRIBUTION
WHICH ARE THE STANDARDS FOR HVAC
DUCT WORK NORMALLY FOLLOWED?
AIR DISTRIBUTION
LET US RECAPTULATE
FOUR IMPORTANT CONSIDERATIONS ONE
SHOULD KEEP DURING DUCT SIZING & ROUTING.
MAJOR DISADVANTAGE
A) THERE IS NO NATURAL PROVISION FOR EQUALISING
PRESSURE DROP IN BRANCHES WHEN LAYOUT IS NOT
SYMMETRICAL.
B) THERE IS NO PROVISION FOR PROVIDING THE SAME
STATIC PRESSURE BEHIND EACH SUPPLY OR RETURN
TERMINAL DEVICE. CONSEQUENTLY BALANCING CAN
BE DIFFICULT.
AIR DISTRIBUTION
MODIFIED EQUAL FRICTION
METHOD
IS RECOMMENDED TO BE USED FOR NON -
SYMMETRICAL DUCT IS LAYOUTS WITH BOTH
LONG AND SHORT DUCT RUNS.
AIR DISTRIBUTION
MODIFIED EQUAL FRICTION METHOD
BRANCH - 1 D
C
VCD
EQ. LENGTH = L1
A B
BRANCH - 2 F
E
VCD
EQ. LENGTH = L2
CENT. FAN BRANCH - 3
G H
EQ. LENGTH = L3
AIR DISTRIBUTION
A. L3>L2>L1
AIR DISTRIBUTION
D. FAN STATIC PRESSURE IS SELECTED BASED ON
HIGHEST PRESSURE REQUIREMENT.
E. SINCE PA-H > PA-F > PA-D : AIR BALANCING
WILL BE A PROBLEM
SOLUTION
a) PROVIDE VOLUME CONTROL DAMPERS ( VCD ) ON
SHORTER BRANCHES I.e BRANCH-1 & BRANCH - 2
b) A HIGHER FRICTION RATE CAN BE SELECTED FOR
SHORTER BRANCHES, NAMELY BRANCH 1 &2.
HOWEVER TAKE CARE VELOCITY IS NOT TOO
HIGH.
AIR DISTRIBUTION
ROLASTAR COMPUTERISED
DUCTING SYSTEMS
• SUPERIOR
QUALITY
• TIME SAVING
• MONEY SAVING
• STATE-OF-ART
CAD/CAM
AIR DISTRIBUTION
SPECIAL FEATURES OF
ROLASTAR
AIR DISTRIBUTION
PROVISION FOR AIR BALANCING
FOR SATISFACTORY PERFORMANCE, AIR
SHOULD BE SUPPLIED BASED ON CALCULATED
THERMAL LOAD. AS PER LAW OF NATURE, THE
AIR ALWAYS TAKES THE LEAST PATH OF
RESISTANCE. SELDOM DUCT SIZE IS SELF
BALANCED. PROVIDE DAMPERS FOR AIR
BALANCING.
AIR DISTRIBUTION
AIR BALANCING
SUPPLY AIR
PLENIUM
TERMINAL
UNITS
SUPPLY
AIR
SUPPLY
AIR
:- VCD
AIR DISTRIBUTION
BUTTERFLY
SPLITER DAMPER
DAMPER
AIR DISTRIBUTION
VOLUME CONTROL DAMPER
A. BUTTERFLY DAMPER
FOR SMALL DUCTS
B. SPLITTER DAMPER ( ONLY FOR
DIRECTION CONTROL)
OPPOSSED PARALLEL
BLADE BLADE
A. AEROFOIL SECTION
B. PLAIN
AIR DISTRIBUTION
VOLUME CONTROL DAMPER
AIR DISTRIBUTION
PARALLEL BLADE - DIVERTING FLOW &
OPPOSSED BLADE - NON DIVERTING FLOW
NOT TO BE USED
BEFORE ANY COIL,
BRANCH TAKE OFF,
AIR WASHER
FILTERS ETC.
AIR IS DIRECTED
TOWARDS DUCT WALL
CAN BE USED
BEFORE COILS,
FILTERS,
AIR WASHER ETC.
AIR DISTRIBUTION
FAN OUTLET DAMPER
AIR DISTRIBUTION
FAN OUTLET DAMPER - AS PER AMCA , BLADE
SHOULD BE PERPENDICULAR TO SHAFT
AIR DISTRIBUTION
FIRE & SMOKE DAMPERS
SINCE HVAC DUCTS PENETRATE THROUGH
BUILDING MEMBRANES ( WALL, FLOORS ) IT
CAUSES RAPID TRANSPORT OF FIRE AND
SMOKE FROM SOURCE TO ALL OTHER
ADJACENT AREAS CAUSING DANGER OF LIFE
& PROPERTY.
AIR DISTRIBUTION
WHAT IS A FIRE / SMOKE DAMPER ?
IT IS A DEVICE INSTALLED IN AN AIR
DISTRIBUTION SYSTEM THAT IS DESIGNED
TO CLOSE AUTOMATICALLY ON DETECTION
OF HEAT / SMOKE TO INTERRUPT AIR FLOW
AND TO RESTRICT PASSAGE OF FLAME OR
SMOKE.
AIR DISTRIBUTION
DESIGN CONSIDERATIONS
DUCTS TO BE CONFINED TO EACH FLOOR
SUCH THAT EVERY FLOOR HAS ITS
DEDICATED AHU.
FIRE CUM SMOKE DAMPER TO BE INSTALLED
IN DUCT AT EACH PENETRATION & FIRE WALL
e.g. FOR BOTH SUPPLY & RETURN AIR.
RETURN AIR IS BETTER IF DUCTED OR ELSE
PROVIDE DAMPER AT EACH PENETRATION OF
FIRE WALL.
DO NOT USE EGRESS PATH / CORRIDOR AS
RETURN AIR PLENUM AS THEY ASSIST IN
SPREAD OF SMOKE AND OTHER
CONTAMINANTS.
AIR DISTRIBUTION
FIRE RATED DOORS TO BE PROVIDED IN
EQUIPMENT / AHU ROOMS.
AIR DISTRIBUTION
IN THE EVENT OF FIRE SOME
ACTIONS ARE
THE CONTROL SIGNAL IS TAKEN FROM
BUILDING FIRE ALARM PANEL.
AIR DISTRIBUTION
AIR HANDLING UNIT
CENTRAL UNITARY
AIR DISTRIBUTION
COMPONENTS OF A CENTRAL AIR
HANDLING STATION
MIXING BOX
PREFILTER SECTION AND FILTERS.
PRE HEAT COIL SECTION - HOT WATER/
STEAM
COOLING COIL SECTION & COOLING COIL
SPARY SECTION & ELIMINATOR SECTION/
WETTED MEDIA PADS.
REHEAT COIL SECTION, HOT WATER / STEAM.
HUMIDIFIER SECTION, SPRAY / PAN
HUMIDIFIER/ WETTED MEDIA.
AIR DISTRIBUTION
FINE FILTER SECTION
HEPA FILTER SECTION
SUPPLY AIR FAN SECTION
RETURN AIR FAN SECTION
HEAT RECOVERY DEVICES, HRW ( WHEEL )
FACE AND BY PASS DAMPER SECTION.
AIR DISTRIBUTION
CENTRAL AIR HANDLING UNIT
SINGLE ZONE
MULTI ZONE
DRAW THROUGH
BLOW THROUGH
AIR DISTRIBUTION
DRAW / BLOW THRO’ ARRANGEMENT
COIL COIL
FAN FAN
L
COIL
FAN
1. PROVIDE BAFFLE PLATE
WITH 50% PERFORATION
2. BAFFLE AREA SHOULD
BE FOUR TIMES
FAN OUTLET AREA
2/3 x L
AIR DISTRIBUTION
PRE COOLING
FILTER COIL FAN
AIR DISTRIBUTION
ZONE - 2
HEATING
PRE COIL
FILTER
FAN
ZONE - 3 ZONE - 1
COOLING
COIL
AIR DISTRIBUTION
AHU CONSTRUCTION
SINGLE SKIN
DOUBLE SKIN
SINGLE TIER
DOUBLE TIER
AIR DISTRIBUTION
SINGLE TIER ARRANGEMENT
FA
(-) (+)
FA
AIR DISTRIBUTION
TWO TIER ARRANGEMENT
HEPA FINE SUPPLY AIR
FILTER FILTER PLENIUM
FRESH
AIR
AIR DISTRIBUTION
UNITARY AHU
FLOOR MOUNTED CEILING SUSPENDED
AIR DISTRIBUTION
SINGLE SKIN CONSTRUCTION
UNIT CASING IS GENERALLY FABRICATED
FROM HEAVY GAUGE GI SHEET.
FANS ARE FORWARD CURVED, SINGLE OR TWIN
MOUNTED ON A COMMON SHAFT. MOTOR IS
EITHER OUT SIDE OR INSIDE THE CASING.
CASING PANELS ( FAN & COIL ) ARE
THERMALLY INSULATED FOR AVOIDING HEAT
GAIN & SWEATING DOWN STREAM OF COIL.
FACE & BYPASS DAMPER CAN BE EITHER
INTERNAL OR EXTERNAL.
CONSTRUCTION IS GENERALLY OF COMPOSITE.
AIR DISTRIBUTION
SINGLE SKIN AHU
AIR DISTRIBUTION
DOUBLE SKIN
STRUCTURE CAN BE COMPOSITE OR
MODULAR TYPE. IN MODULAR TYPE
SECTIONS CAN BE ISOLATED AND RE
ARRANGED. HOWEVER IT IS EXPENSIVE.
AIR DISTRIBUTION
SOUND POWER LEVEL OUT SIDE THE CASING
IS LOW SINCE MOTOR IS INSIDE AND
CASING PANELS ARE HEAVIER IN MASS.
AIR DISTRIBUTION
DOUBLE SKIN-HORIZONTAL
AIR DISTRIBUTION
DOUBLE SKIN-CEILING SUSPENDED
AIR DISTRIBUTION
WHAT IS FACE & BYPASS DAMPER ?
BYPASS COOLING COIL
FACE
FILTER FAN
DAMPER
GRAIN / LB
IS REQUIRED
TO MAINTAIN
TOA CLASS
CONDITIONS.
TMIX
• MODULATING
T ADP TROOM
TMIX AIR BYPASS :
AFTER BYPASS WITH DX
SYSTEM
DBT
AIR DISTRIBUTION
FAN FUNDAMENTALS
A FAN IS A VOLUMETRIC DISPLACEMENT DEVICE USED
TO PROVIDE FLOW OF AIR. IT CONSISTS OF A
ROTATING IMPELLER AND A HOUSING CALLED THE
SCROLL . IT IS MEASURED BY INCREASE IN TOTAL
PRESSURE. A FAN CONVERTS ROTATONAL MECH.
ENERGY TO AIR ENERGY.
TYPES OF FANS
AIR DISTRIBUTION
FOR AIR HANDLING UNITS MOSTLY
CENTRIFUGAL FANS ARE USED
AEROFOIL
ROTATION ROTATION
AIR DISTRIBUTION
FAN APPLICATION
AIR DISTRIBUTION
CENTRIFUGAL FAN
FLOW OF AIR IS RADIAL, AIR TURNS BY 900
AIR DISTRIBUTION
AXIAL FLOW
FLOW OF AIR IS AXIAL, EASY FOR DUCT
CONNECTION
AIR DISTRIBUTION
CLEARANCE
HUB DIAMETER
IMPELLER DIA
MOTOR
AIR DISTRIBUTION
PARALLEL AXIAL FLOW FAN
AIR DISTRIBUTION
CENTRIFUGAL SINGLE INLET, SINGLE WIDTH
(BASED ON NO.
OF INLETS DOUBLE INLET, DOUBLE WIDTH
OUTLET OUTLET
INLET INLET
AIR DISTRIBUTION
SISW vs DIDW
MOSTLY DIDW FANS ARE USED IN AIR
HANDLING UNITS.
AIR DISTRIBUTION
CETRIFUGAL FAN COMPONENTS
AIR DISTRIBUTION
PERFORMANCE
AIR DISTRIBUTION
Q,CFM RPM SP AMBIENT TEM. DENSITY
& PRESSURE LB/CUFT
AIR DISTRIBUTION
FORWARD CURVED FAN
A. OPERATING RANGE : 30% TO 80% OF WIDE OPEN
VOLUME
AIR DISTRIBUTION
FORWARD CURVED FAN
AIR DISTRIBUTION
BACKWARD CURVED FANS
A. OPERATING RANGE : 40% TO 85% OF WIDE OPEN
VOLUME
AIR DISTRIBUTION
BACKWARD vs FORWARD CURVE
BACKWARD CURVED FANS HAVE HIGHER SPEED.
HIGH STATIC EFFICIENCY & HENCE LOWER NOISE
LEVEL AND POWER CONSUMPTION.
MAXIMUM EFFICIENCY REQUIRES CLOSE CLEARANCE
AND ALIGNMENT BETWEEN WHEEL & AIR INLET.
CONSTRUCTION IS MORE STURDY, WELDED IMPELLER.
SHAFT & BEARINGS IS HEAVY.
AIR DISTRIBUTION
MEASUREMENT OF FAN STATIC
PRESSURE
FAN TP = TP2 - TP1
OR
OUT LET
2 DUCT
STATIC TUBE
IMPACT
TUBE FAN STATIC
1 PRESSURE
INLET DUCT
AIR DISTRIBUTION
PERFORMANCE - FORWARD CURVE
AIR DISTRIBUTION
SAFETY MARGIN
BLOCKED SURGE
TIGHT ZONE
STATIC
PRESSURE
100%
GOOD SELECTION
AREA
STATIC PRESSURE/BHP/
STATIC
EFFICIENCY
STATIC EFFICIENCY
BHP
STATIC
PRESSURE
FREE DELIVERY
OR WIDE
OPEN CFM
0%
100%
VOLUME FLOW RATE
AIR DISTRIBUTION
PERFORMANCE - BACKWARD CURVE
UNSTABLE
ZONE
STATIC
EFFICIENCY
HORSE POWER
BHP
PERFORMANCE CURVE -
BACKWARD CURVED FAN
SP = 4" A
2
STATIC
PRESSURE
INCHES 1"
WG
0 1000 2000
AIR DISTRIBUTION
FAN - SYSTEM CURVE INTERACTION
• THE POINT OF INTERSECTION OF THE SYSTEM
CURVE AND FAN PERFORMANCE CURVE
DETERMINE THE POINT OF OPERATION.
AIR DISTRIBUTION
THE LEFT HUMP WILL ONLY
DUCT SYSTEM B
MAKE THE FAN UNSTABLE
FAN CURVE IF LITTLE THROTTLING
IS DONE
B
DUCT SYSTEM A
A
DUCT SYSTEM C
DESIGN C
SP
RPM, N ( CONSTANT )
B A C
DESIGN CFM
AIR DISTRIBUTION
SOME EXAMPLES
IN CLEAN ROOM JOBS WITH PRE, FINE &
HEPA FILTERS, INITIALLY ALL FILTERS ARE
CLEAN. FAN IS SELECTED BASED ON CLOGGED
FILTERS. HOWEVER INITIALLY FILTERS ARE
CLEAN. THUS FAN DELIVERS MORE AIR AND
CONSUME MORE POWER.
DECREASE IN C'
RESISTANCE
C
SYSTEM
RESISTANCE 1.1 N
STATIC CURVE
PRESSURE N
DIAMETER D,
0.9 N RPM N
B' A C'
DESIGN CFM
VOLUME FLOW RATE, CFM
AIR DISTRIBUTION
FAN LAWS
RPM 1
SE
EA ED
PRESSURE
C SPE
R
IN N
STATIC
RPM 2
I
RPM 3
CFM
AIR DISTRIBUTION
EFFECTIVE OF FAN WHEEL
DIAMETER, CONSTANT RPM
CFM ( DIAMETER )3
BHP ( DIAMETER )2
AIR DISTRIBUTION
EFFECTIVE OF DENSITY ,
CONSTANT RPM
CFM1 = CFM2
SP1 / SP2 = D1 / D2
BHP1 / BHP2 = D1 / D2
AIR DISTRIBUTION
FAN ARRANGEMENT
AIR DISTRIBUTION
FAN ARRANGEMENT
AIR DISTRIBUTION
LOCATION OF ELBOW AT FAN OUTLET
AIR DISTRIBUTION
INCORRECT LOCATION OF ELBOW
AIR DISTRIBUTION
FAN OUTLET DAMPER - AS PER AMCA ,
BLADE SHOULD BE PERPENDICULAR TO
SHAFT
AIR DISTRIBUTION
ROTATION & ARRANGEMENT
AS SEEN FROM THE DRIVE END. FOR SISW ,
IT IS SIDE OPPOSITE TO INLET.
AIR DISTRIBUTION
MOTOR LOCATION AS PER AMCA
MOTORS
Z W
Y X
AIR DISTRIBUTION
CENTRIFUGAL FAN - CORRECT ROTATION
AIR DISTRIBUTION
AXIAL FLOW FAN - CORRECT ROTATION
AIR DISTRIBUTION
WRONG DUCT CONNECTION
AIR DISTRIBUTION
WRONG DUCT CONNECTION
AIR DISTRIBUTION
FAN CONSTRUCTION & ARRANGEMENT
AMCA STANDARD 99 HAS ESTABILISHED
STANDARDS FOR FAN SIZE & CLASSIFICATION.
OLD CLASSIFICATION
CLASS - I 3 3/4” TOTAL PRESSURE
CLASS - II 6 3/4” TOTAL PRESSURE
CLASS - III 12 1/4” TOTAL PRESSURE
CLASS - IV ABOVE 12 1/4” TOTAL PRESSURE
AIR DISTRIBUTION
HIGHER THE CLASS OF FAN, MORE STURDY IS
THE FAN CONSTRUCTION & THUS EXPENSIVE.
AIR DISTRIBUTION
FAN - CLASS OF CONSTRUCTION
AIR DISTRIBUTION
MOISTURE ELIMINATOR USED IN AHU
AIR DISTRIBUTION
AIR DISTRIBUTION
AIR DISTRIBUTION
FAN COIL UNIT
AIR DISTRIBUTION
THERMAL INSULATION
• REDUCES HEAT LOSS.
• SAVES ENERGY.
AIR DISTRIBUTION
INSULATION TYPES
INORGANIC
ORGANIC
• CELLULAR MATERIAL LIKE FOAMED RUBBER ,
EXPANDED POLYSTRENE (THERMOCOLE) AND
POLYURETHANE FOAM.
AIR DISTRIBUTION
FIBRE GLASS INSULATION
AIR DISTRIBUTION
AIR DISTRIBUTION
SELECTION CRITERIA
AIR DISTRIBUTION
COMPARISION OF VARIOUS TYPES
AIR DISTRIBUTION
THERMAL CONDUCTIVITY
AIR DISTRIBUTION
VAPOUR PERMEABILITY
AIR DISTRIBUTION
APPLICATION
• SUPPLY AIR DUCTS CARRYING COLD AIR
FROM AIR HANDLING UNIT.
AIR DISTRIBUTION
DUCT
INSULATION
AIR DISTRIBUTION
PIPE INSULATION
AIR DISTRIBUTION
INSULATION OVER FALSE CEILING
AIR DISTRIBUTION
UNDER DECK INSULATION OF
EXPOSED ROOF
AIR DISTRIBUTION
THANK
YOU
AIR DISTRIBUTION