You are on page 1of 22

After reading this Module , you should be able to:

Provide classification of distribution systems


Discuss design considerations Provide an analysis of AC and DC distribution systems

The part of the electrical-supply system existing between

the distribution substations and the distribution


transformers is called the primary system. It is made of circuits, known as primary feeders or

primary distribution feeders. The most commonly used


nominal primary voltage is 11 kV.

The secondary distribution system receives power from the secondary side of distribution transformers at low voltage and supplies power to various connected loads via service lines. The secondary distribution System is the final sub-system of the power system. The secondary distribution systems are generally of the radial type except for some specific service areas such as hospitals, business centers and military installations, which require highly reliable service, and therefore, may be of a grid or mesh type.

Figure : Radial secondary distribution system configuration

Good voltage regulation is the most important factor in a distribution system for delivering good service to the consumer. For this purpose, careful consideration is required for the design of feeders and distributor networks.

Feeders are the conductors that connect substations to consumer ports and have large current carrying capacity.

The current loading of a feeder is uniform along the whole


of its length since no tappings are taken from it. The design of a feeder is based mainly on the current that is to be

carried.

Distributors are the conductors, which run along a street or an area to supply power to consumers. These can be easily recognized by the number of tappings, which are taken from them for the supply to various consumer terminals. The current loading of a distributor is not uniform and it varies along the length while its design is largely influenced by the voltage drop along it.

Service Main and Sub Main The service mains are the
conductors forming connecting links between distributors and metering points of the consumer's terminal. Figure 14.1 shows the layout of a distribution system. The term sub main refers to the several connections given to consumers from one service main.

It has been established that 70% of the total losses occur in the primary and secondary distribution system while transmission and sub-transmission lines account for only 30% of the total losses. Distribution losses amount to 15.5% of the generation capacity and the target level is to bring it down to 7.5%. Therefore the primary and secondary distribution systems must be planned with care to ensure losses within

acceptability limits

Inadequate Size of Conductor : The rural load is usually scattered and fed by radial feeders. Feeder Length In practice, 11 kV and 415 V lines in rural areas are hurriedly extended radially over long distances to feed loads scattered over large areas. This results in high line resistance, low voltage, and high current, and therefore, leads to high I 2R losses in the line.

Location of Distribution Transformers Often the distribution transformers are not located centrally in relation to the intended customer. Consequently, the farthest customers obtain an extremely low voltage even though a reasonably

good voltage level is maintained at the secondary


transformer. This again leads to higher line losses.

Therefore, in order to reduce the voltage drop in the line


transmitting power to consumers located farthest from the line, the DT should be located at the load center to keep the

voltage drop within permissible limits.

Low Voltage Whenever the voltage applied to an induction


motor deviates from rated voltage, its performance is adversely affected. A reduced voltage, in case of an induction motor, results in higher currents drawn for the same output leading to higher losses. This can be overcome by adjusting the tap changer at power transformer and at distribution transformer, if available.

Use of Over-rated Distribution Transformers


Studies on 11 kV feeders have revealed that often the rating of distribution transformers (DTs) is much higher than the maximum kVA demand on the LT feeder. An overrated transformer produces an unnecessarily high iron loss. From the above, it is clear that the rating should be judiciously selected to keep the losses within the permissible

limits.

Low Power Factor In most of the LT distribution


systems, it is found that the power factor varies from as
worse as 0.65 to 0.75. A low power factor contributes towards high distribution losses.

For a given load, if the power factor is low, the current


drawn is high, consequently the losses proportional to a square of the current, will be more. Thus, line losses owing to the poor power factor can be reduced by improving the power factor by using shunt capacitors for the purpose.

The following methods are adopted for the reduction of


distribution-system losses: 1. HV distribution system

2. Feeder reconfiguration
3. Grading of conductor 4. Construction of new substation

5. . Reactive-power compensation

1 . HV Distribution System
The low-voltage distribution system contributes a majority of the total distribution losses because of poor voltage regulation .

The present situation is that LV lines are extended, irrespective of


voltage drops, up to the full capacity of the DT and sometimes over and above the transformer capacity. Hence, no purpose will

be served by prescribing low kVA-km loading limits for LV lines.


The only practice and feasible solution is to eliminate or minimize LV lines by switching over to single- phase high voltage distribution. By adopting HV distribution, the losses in the LV distribution can be minimized.

2 . Feeder Reconfiguration
It is defined as the process of altering the topological structure of distribution feeders by changing the open/closed status of the sectionalising and tie switches. Feeder reconfiguration allows the transfer of loads from

heavy loaded feeders to moderately heavy loaded feeders.


Such transfers are effective in improving the voltage profile along the feeders and effecting reduction in the

overall system power losses.

3. Grading of Conductor
In normal practice, the conductor used for radial distribution

feeders is of uniform cross-sectional area. However, the load


magnitude at the substation is high and it reduces as we proceed to the tail-end of the feeder. This indicates that the

use of a higher-sized conductor, which is capable of supplying


load from the source point, is not necessary at the tail-end point. Similarly, the use of different conductor cross-sections

for intermediate sections will lead to a minimum capital


investment cost and line loss.

4. Construction of New Substation


If a new substation is to be constructed and connected to an existing network, several possible solutions are to

be studied. These solutions may include various


connection schemes of the substation and several feasible locations .

The optimum site for a substation is defined as that


location which will result in minimum cost for construction and minimum losses. Therefore, by constructing a new

substation at load centres, the line osses will be reduced


due to an improvement in the voltage profile and a reduction in the length of the lines.

5. Reactive Power Compensation


Voltage-reactive power control function has a pivotal role
to play in the distribution automation. The problem of reactive power compensation can be

attempted by providing static capacitors.


The method presently used to compensate the reactive power component is to increase the reactive power by

increasing the terminal voltage of the generator (or), by


increasing the field current of the synchronous machine in condenser mode at the generating stations. This procedure is

not effective because the power-system losses will be further


increased due to the increase of reactive power in the transmission system.

An alternative method for compensating the reactive power is the use of capacitors in distribution systems at customer points. Shunt capacitors supply the amount of reactive power to the system at the point where they are connected. There are two methods of capacitor compensation viz. 1. Series compensation (capacitors are placed in series with line) 2. Shunt compensation (capacitors are placed in parallel with

load)

The fundamental function of capacitors, whether they are

series or shunt in a power system is to generate reactive


power to improve power factor and voltage, thereby enhancing the system capacity and reducing losses.

In series capacitors, the reactive power is proportional to


the square of the load current, whereas in shunt capacitors it is proportional to the square of the voltage.

You might also like